Loading...
7102-Flush Truck Expansion - ADDENDUM #12717 Wind River Lane, Suite 230 Denton, Texas 76210 940-566-0266 info@nelsonmorgan.com to the FLUSH TRUCK STORAGE EXPANSION for the City of Denton PROJECT NO. NMA 18023 October 21, 2019 1.1 GENERAL: A. This addendum consisting of 1 pages supersedes plans and information dated April 4, 2019. B. This addendum is issued to: 1. Update the Table of Contents to the project specifications 2. Modify or add new specification sections. 2.1 SPECIFICATIONS: A. Replace or add the following specification sections with the attached new sections: a. Section 00050 Table of Contents (replace and update) b. Section 02260 Soils Poisoning (new) c. Section 13600 Pre-Engineered Building System Components (replace and update) d. Section 15330 Automatic Fire Protection System (new) e. Section 16602 Fire Alarm and Detection System (new) END OF ADDENDUM NO. 1 00050 - 1 Table of Contents – Addendum #1 Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 TABLE OF CONTENTS Addendum No. 1 Flush Truck Storage Expansion for the City of Denton Nelson + Morgan, Architects Project No. 18023 GENERAL INFORMATION 00010 Project Information and Professional Seals 1 page 4April19 00050 Table of Contents (reissued Add #1) 3 pages 21Oct19 DIVISION ONE: GENERAL REQUIREMENTS 01010 Summary of Work 3 pages 4April19 01060 Regulatory Requirements 1 page 4April19 01096 ADA/TAS Standards 3 pages 4April19 01100 Job Requirements 7 pages 4April19 01250 Contract Modification Procedures 3 pages 4April19 01290 Payment Procedures 4 pages 4April19 01295 Schedule of Values 2 pages 4April19 01310 Project Management and Coordination 6 pages 4April19 01320 Construction Progress Documentation 2 pages 4April19 01340 Submittal Procedures 8 pages 4April19 01420 References 4 pages 4April19 01421 Structural Testing and Inspection Agency Services 9 pages 4April19 01450 Quality Control 3 pages 4April19 01600 Materials and Equipment 10 pages 4April19 01731 Cutting and Patching 2 pages 4April19 01740 Cleaning 2 pages 4April19 01750 Starting and Adjusting 2 pages 4April19 01770 Closeout Procedures 2 pages 4April19 01780 Closeout Submittals 5 pages 4April19 DIVISION TWO: SITE WORK 02070 Selective Demolition 2 pages 4April19 02115 Site Clearing 2 pages 4April19 02260 Soils Poisoning (reissued Add #1) 1 page 21Oct19 02270 Erosion and Sediment Control 3 pages 4April19 02300 Earthwork 5 pages 4April19 02310 Grading 2 pages 4April19 02751 Concrete Pavement 5 pages 4April19 02764 Paving Joint Sealants 3 pages 4April19 DIVISION THREE: CONCRETE 03100 Concrete Forming 3 pages 4April19 03200 Concrete Reinforcing 2 pages 4April19 03300 Cast in Place Concrete 7 pages 4April19 03366 Concrete Sealer, Densifier, Hardener 3 pages 4April19 00050 - 2 Table of Contents – Addendum #1 Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 DIVISION FOUR: MASONRY DIVISION FIVE: METALS DIVISION SIX: WOOD AND PLASTICS 06100 Rough Carpentry 3 pages 4April19 DIVISION SEVEN: THERMAL AND MOISTURE PROTECTION: 07900 Sealants 3 pages 4April19 DIVISION EIGHT: DOORS AND WINDOWS 08110 Hollow Metal Doors and Frames 4 pages 4April19 08330 Sectional Overhead Door 3 pages 4April19 08710 Door Hardware 9 pages 4April19 DIVISION NINE: FINISHES 09900 Painting 4 pages 4April19 DIVISION TEN: SPECIALTIES DIVISION ELEVEN: EQUIPMENT DIVISION TWELVE: FURNISHINGS: Not used DIVISION THIRTEEN: SPECIAL CONSTRUCTION 13600 Pre-Engineered Building Systems (reissued Add #1) 13 pages 21Oct19 DIVISION FOURTEEN: Not used. DIVISION FIFTEEN: MECHANICAL 15050 Basic Mechanical Materials and Methods 6 pages 4April19 15075 Mechanical System Identification 3 pages 4April19 15140 Hangers and Supports 7 pages 4April19 15330 Automatic fire Protection System (reissued Add #1) 9 pages 21Oct19 15410 Plumbing Piping Systems 14 pages 4April19 15580 Gas Fired Heaters 2 pages 4April19 15760 Electric Heaters 2 pages 4April19 15820 Ductwork Accessories 4 pages 4April19 15830 Power Ventilators 3 pages 4April19 15850 Air Inlet and Outlet Devices 4 pages 4April19 15890 Ductwork and Vents 7 pages 4April19 15950 Testing, Adjusting, and Balancing 7 pages 4April19 DIVISION SIXTEEN: ELECTRICAL 16000 General Electrical Requirements 9 pages 4April19 16060 Grounding and Bonding 3 pages 4April19 16070 Supporting Devices 3 pages 4April19 16080 Electrical Identification 2 pages 4April19 16110 Underground Electrical Conduits 2 pages 4April19 16120 Conductors and Cables 4 pages 4April19 00050 - 3 Table of Contents – Addendum #1 Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 16130 Raceways and Fittings 7 pages 4April19 16140 Wiring Devices 3 pages 4April19 16405 Enclosed Motor Controllers 3 pages 4April19 16420 Lighting and Appliance Panelboards 4 pages 4April19 16500 Lighting Fixtures 6 pages 4April19 16602 Fire Alarm and Detection System (reissued Add #1) 13 pages 21Oct19 END OF TABLE OF CONTENTS 02260- 1 Soil Poisoning-Addendum #1 Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 SECTION 02260 SOIL POISONING PART l - GENERAL 1.1 DESCRIPTION A. Scope: This work comprises furnishing and applying soil chemicals for the prevention of termite infestation. l.2 QUALITY ASSURANCE A. Applicator Qualifications: This work shall be performed by a licensed, reputable, pest control operator with experience in this work. B. Applicator shall provide documentation that he is, in fact, licensed by the state of Oklahoma for approval by Architect. l.3 GUARANTEE A. Upon completion of the soil poisoning and as a condition for its acceptance, the Contractor shall furnish a written and insured guarantee for the effectiveness of the soil poisoning against termite infestation for a period of 5 years from date of treatment. Any evidence of reinfestation within the guarantee period will require retreatment without extra cost to the Owner. The guarantee shall be non- cancelable by all parties to the contract except the Owner. PART 2 - PRODUCTS 2.l MATERIALS A. Toxicants: Only water-based emulsion soil chemicals may be used. Cyren TC 1. Active Ingredient: Chlorpyrifos - O, O-diethyl O-(3,5,6-trichloro-2-pyridinyl) phosphorodithioate. Cyren TC - 43.2% a.i. 2. Registered for use on: Preconstruction termite treatment at 0.5%, utility poles and fence posts. 3. Pests controlled: Subterranean Termites and other wood infesting insects. B. Mixes: If combinations of toxicants are used, at least one of them must be at or above the minimum percentage listed above: PART 3 - EXECUTION 3.l APPLICATION A. Applying Chemicals: Apply the solution approximately 48 hours prior to placing concrete slabs and at such time as there is reasonable assurance that no rain will fall until after the slabs have been placed. a. Apply an over-all treatment under the entire building area, including covered passages and entrance platforms. Apply at a rate not less that l gallon per 7 sq. ft. b. Apply to critical areas along both sides of grade beams and around piers at a rate of l gallon per 2- l/2 linear feet. c. Unless the treated areas are covered immediately, take precautions to prevent disturbance of the treatment by human or animal contact with the treated soil. END OF SECTION 13600- 1 Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 SECTION 13600 PREFABRICATED METAL BUILDING SYSTEM COMPONENTS PART 1 - GENERAL 1.1 WORK INCLUDED: A. Furnishing a complete Pre-Engineered Metal Building structural framing system as indicated on the drawings. a. 4 bay expansion to the existing warehouse building B. Secondary structural framing, bracing, metal panels for walls, flashings, fasteners, sealants, accessories, and miscellaneous component parts required and or as shown on Drawings. C. Pre-Engineered Metal Building Systems shall be equal to MBCI, Inc. or approved equal. D. Some changes and modifications to the conventional pre-engineered building components are required by the drawings in this project. Contractor shall be responsible to field verify exact conditions, heights, dimensions, sizes, etc. as required to confirm proper integration of new construction into the building design. 1.2 WORK INCLUDED ELSEWHERE: A. Section 08310: Sectional Overhead doors 1.3 GUARANTEE: Provide a three-year material warranty and a one-year erection warranty. 1.4 QUALITY ASSURANCE A. Fabricator Qualifications: The building shall be the design of a manufacturer regularly engaged in the fabrication of pre-engineered structures, conforming to the Metal Building Manufacturers Association's "Recommended Code of Standard Practices" and "Recommended Design Practices Manual". B. Design Criteria: 1. Steel Construction Manual of American Institute of Steel Construction, current issue. 2. American Iron and Steel Institute's Cold Formed Steel Design Manual, current issue. 3. American Welding Society Code of Welding in Building Construction, current issue. 4. ASTM Standards A 325-76b for Quenched and Tempered Steel Bolts and A 307-76b for Steel Machine Bolts and Nuts. C. Design Loads: 1. Live load and wind load shall be as specified by the 2018 International Building Code. 2. Dead load shall be equal to the self weight of the members. 3. The metal building shall be designed for the following minimum loads and shall be designed in accordance with the 2018 International Building Code: a. Main Frames: 20 psf (This shall NOT be reduced) b. Components: 20 psf (This shall NOT be reduced) c. Collateral load: 6 psf d. Wind load per ASCE 7-02: 1. 3 second gust design wind speed=90 mph 2. Exposure category: C 13600- 2 Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 3. Importance factor=1.00 4. Assume all windows and doors are openings for the enclosure classification, but assume they are cladding for the calculation of loads on secondary framing. e. Ground snow load: pg=10 psf f. Earthquake design data: 1. Seismic importance factor, i: 1.00 2. Mapped spectral response accelerations: 3. Soil site class: D 4. Seismic design category: C 4. The lateral deflection of the lateral force resisting systems shall not exceed h/180 for any building, and h/300 for any building with masonry veneer higher than 8 feet above finish floor. The lateral deflection of the grits and metal siding shall be l/120 for any wall, and l/240 for any tributary area with masonry veneer. 5. All cold-formed steel shall be designed by the metal building engineer per AISI-NASPEC 2001. The following are additional minimum requirements for the purlins and girts on this project: 1. Both flanges shall be braced at 8 ft oc maximum. 2. Bracing lines shall consist of 16 gage straps x 1.5" with a #12 screw at each flange. 3. Bracing lines shall be anchored with 2 horizontal and 2 diagonal l1.5x1.5x16 gage angles at each end bay, at both sides of ridges, and at 50 ft o.c. maximum. Horizontal angles shall be coped and attached to each flange with 2 #12 screws. Attach diagonals to horizontals with 2#12 screws. 4. Bracing straps may be omitted on flanges that are braced with through-fastened roof panels or metal siding. 6. The metal building engineer shall determine the diameter of the anchor bolts required for the typical anchor bolt detail. D. Engineering Certification: 1. Metal building manufacturer shall provide complete engineering drawings and computer calculations for the metal building proposed. 2. Drawings shall show complete data regarding bolt setting for base plates and other anchorage points. Anchor bolt diameter shall be as specified by the metal building manufacturing company’s standard anchor bolt layout drawings and the length shall be defined by the Structural Engineer. 3. A letter of certification shall be submitted with the design calculations. This letter shall certify that the building conforms to the applicable Specifications and the letter shall be signed and sealed by an engineer registered in the State of Texas. 4. The design of the structural system shall be a continuous rigid frame, parallel roof beams and a single slope roof. The roof shall have slopes as indicated on the drawings. All components and parts of the structural system shall be as indicated on the engineering drawings and specifications. All components and parts shall be clearly marked and erection drawings shall be supplied for identifications and assembly of the parts. All drawings shall carry the seal of the State of Texas registered professional Engineer. Field modification of parts shall be in accordance with the best standard procedures and shall be the responsibility of the building erector. 1.5 SUBMITTALS: A. SHOP DRAWINGS: Submit shop drawings to the Architect for review prior to fabricating the building. Show complete details, design loads, and calculations for all members. All calculations shall be prepared and sealed by a registered Professional Engineer licensed by the State of Texas. 13600- 3 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 PART 2 - MATERIALS 2.1 STRUCTURAL FRAMING A. Primary Framing: Rigid Frame solid web framing consisting of tapered or uniform depth rafters rigidly connected to uniform depth and dimension columns. Provide a clear span that supports the loads at bay spacing indicated a. All members shall be shop-fabricated for bolted field assembly. b. All members shall be cleaned and receive one shop coat of red oxide alkyd primer. c. Secondary framing may be cold-formed using pre-painted coil stock. d. Flanges and webs shall have continuous weld on one side. e. All material shall have a minimum yield strength of 50,000 psi, except S shapes, which shall be 36,000 psi. f. Bracing rods shall have minimum yield strength of 50,000 psi. g. Secondary members (purlins, girts, eave struts, base members, flange bracing, gable angles, fascia and soffit framing and bracing, clips, etc.) shall be of 55,000 psi material. h. Purlins to be roll-formed Z sections. i. Girts shall be roll-formed Z sections or cold-formed C sections. j. Eave struts be roll-formed C sections. k. End Wall Framing: Half-loaded full frames. B. Secondary Framing: Purlins: Zee-shaped; depth as required; with minimum yield strength of 60,000 psi (410 MPa); simple span or continuous span as required for design. G-30 galvanized standard material with G-90 availability. Welded members are manufacturer's standard primer. Girts: Zee- or Cee-shaped; depth as required, with minimum yield strength of 60,000 psi (410 MPa); simple span or continuous span as required for design. G-30 galvanized standard material with G-90 availability. Welded members are manufacturer's standard primer. C. Wind Bracing: Portal, torsional, diagonal bracing or diaphragm in accordance with manufacturer's standard design practices; utilizing rods, angles, and other members, with minimum yield strengths as required for design but in most cases, 50 ksi. D. Primary Frame Flange Bracing: Attached from purlins or girts to the primary framing, minimum yield strength as required for design but in most cases 60 ksi. E. Miscellaneous Framing a. Base Angles: 2 inch by 3 inch by 0.060 inch (50 mm by 75 mm by 1.5 mm) galvanized steel angles, with minimum yield strength of 55 ksi (380 MPa), anchored to the floor slab or grade beam with power driven fasteners or equivalent at a maximum spacing of 4 feet (1220 mm) on center and not more than 6 inches (150 mm) from the end of any angle member. Anchors are not provided by the metal building manufacturer. b. Door Headers and Jambs: Zee- or Cee-shaped; depth as required; with minimum yield strength of 60 ksi (410 MPa). 2.2 ROOF PANELS: A. PBR Roof Panels: 13600- 4 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 1. Basis of design: Equal to MBCI "BPR" roof system or approved equal. 2. Panels shall be a premium quality, 26-gauge, structural roof panels with 1 1/4" high x 12” wide ribs with 2 stiffeners between each rib. Overall panel width of 36”. 3. Panels shall be secured with an exposed screw designed to allow for expansion and contraction of roof panels, located at each purlin. Include all closures, related sheet metal trim, fasteners, and sealants to provide a complete system. 4. Roof panels shall have galvalume finish. Panel coating shall be a silicone polyester coating system. Interior shall be a wash coat of primer. Color shall be selected from the manufacturer’s full range of standard colors. 5. Roof panels shall carry an Underwriters' Laboratory wind uplift classification of 90 (U.L. Construction Number 62). 2.3 WALL PANELS: A. Exposed to view: 1. Wall panels shall be a premium quality, 26 gauge, standing seam panel with 1-1/4" high closed ribs spaced at 12" o.c.. Between each major rib are two minor stiffening ribs. Equal to MBCI “PBR” panel wall system or approved equal. 2. Panel coating shall be a silicone polyester coating system. Interior shall be a wash coat of primer. Color shall be selected from the manufacturers full range of standard colors. MBCI Signature 200 or equal. 2.4 INSULATION: A. Thermal Performance for Building Envelope: Provide the following maximum U-factors and minimum labeled R-values when tested according to ASTM C 1363 or ASTM C 518: 1. Roof: Labeled R-Value: R-30 Minimum (0.037 U-factor) 2. Walls: Labeled R-Value: R-13 minimum (0.079 U-factor) B. Filled Cavity / Long Tab Banded (LTB) Metal Building Roof Insulation Systems. 1. Description: High Performance / Low U-Factor Double Layer Filled Cavity / Long Tab Banded (LTB) roof insulation systems providing U-Factors ranging from 0.037 to 0.029 when installed in accordance with the supplier's recommendations and details below. a. U-Factor: 0.037. 1) Faced Bottom Layer: R-19.(or thickness as required) 2) Unfaced Top Layer: R-11. 3) Purlin Depth: 8 inch (203 mm). 2. Components: a. Fiberglass Insulation: Complying with NAIMA 202-96 specification. 13600- 5 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 1) Bottom Layer: Installed parallel to, and between purlins. a) Insulation: Metal Building Insulation with a Vapor Retarder Facing. b) Facing: Lamtec Corporation WMP-30 or equal covering interior face of insulation. c) Faced Bottom Layer Composite Surface Burning Characteristics: Flame spread index of 25 or less and a smoke developed index of 50 or less per ASTM E 84 or UL 723. d) Finish color: Provide black finished vinyl insulation for all areas where installation will be visible to view. 2) Top Layer: Installed perpendicular to purlins. a) Unfaced Fiberglass, supplied in rolls compatible with roof panel widths. b. Metal Banding: Minimum 3/4 inch (19 mm) wide, installed under and perpendicular to purlins, 30 inches (762 mm) o.c. (nominal spacing) on the interior side. c. Banding Screws: Minimum 1/2 inch (13 mm) hex-head TEK screws. d. Thermal Blocks: R-5. 2.5 FASTENERS: A. Wall fasteners shall be No. 12, self-drilling carbon steel hex screws, minimum length l l/4" for structural, 3/4" for stitch work. B. Roof fasteners shall be No. 12 self-drilling carbon steel screws with extended life hex heads and sealing washers. Minimum length of l". 2.6 SEALANTS Sealants for side laps, etc. shall be preformed, butyl rubber-based compound, in tape mastic form with paper backing. Tube sealants are to supplement the above, and be synthetic, elastomeric based material. 2.7 STRUCTURAL PAINTING A. All structural steel components shall be factory cleaned to remove all loose dirt, grease and mill scale and chemically treated with phosphoric type cleaner and then painted with one coat of zinc chromate alkyd formulated to equal or exceed the performance requirements of Federal Specification TT-P-636c or TT-P-664c. G. 2.8 ACCESSORIES A. Provide all other accessories required to complete the metal building structure and coverings. These items include but are not limited to the following: gable trim, gutter, downspouts, closures, screws, fasteners, bolts, rivets, sealants, tape and other accessories. B. All accessories shall be made watertight and shall be firmly secured in place. Sheet 13600- 6 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 metal items shall be in the longest single lengths possible without splices, where splices are necessary, lap the edges not less than 3". Support gutters as recommended by the manufacturer and provide downspouts as shown. ` 2.9 METAL ROOF PANEL ACCESSORIES A. General: Provide complete metal roof panel assembly incorporating trim, copings, fasciae, gutters and downspouts, and miscellaneous flashings, in profiles as indicated. Provide required fasteners, closure strips, thermal spacers, splice plates, support plates, and sealants as indicated in manufacturer's written instructions. B. Flashing and Trim: Match material, thickness, and finish of metal panel face sheet. C. Panel Clips: Provide panel clip of type specified, at spacing indicated on approved shop drawings. 1. Two-piece Floating: ASTM C 645, with ASTM A 653/A 653M, G90 (Z180) hot-dip galvanized zinc coating, configured for concealment in panel joints, and identical to clips utilized in tests demonstrating compliance with performance requirements. 2. Single-Piece Fixed: ASTM A 980 with zinc electroplated galvanized coating D. Panel Fasteners: Self-tapping screws and other acceptable corrosion-resistant fasteners recommended by roof panel manufacturer. Where exposed fasteners cannot be avoided, supply fasteners with EPDM or neoprene gaskets and heads matching color of metal panels by means of factory-applied coating. E. Joint Sealers: Manufacturer's standard or recommended liquid and preformed sealers and tapes, and as follows: 1. Factory-Applied Seam Sealant: Manufacturer's standard hot-melt type. 2. Tape Sealers: Manufacturer's standard non-curing butyl tape, AAMA 809.2. F. Steel Sheet Miscellaneous Framing Components: ASTM C 645, with ASTM A 653/A 653M, G60 (Z180) hot-dip galvanized zinc coating. 2.10 FABRICATION G. General: Provide factory fabricated and finished metal panels and accessories meeting performance requirements, indicated profiles, and structural requirements. H. Fabricate metal panel joints configured to accept factory-applied sealant providing weathertight seal and preventing metal-to-metal contact and minimizing noise resulting from thermal movement. I. Form panels in continuous lengths for full length of detailed runs, except where otherwise indicated on approved shop drawings. J. Sheet Metal Flashing and Trim: Fabricate flashing and trim to comply with manufacturer's written instructions, approved shop drawings, and project drawings. Form from materials matching metal panel substrate and finish. 13600- 7 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 PART 3 - EXECUTION 3.1 EXAMINATION A. Examine metal panel system substrate and supports with Installer present. Inspect for erection tolerances and other conditions that would adversely affect installation of metal panel installation. 1. Inspect metal panel support substrate to determine if support components are installed as indicated on approved shop drawings. Confirm presence of acceptable supports at recommended spacing to match installation requirements of metal panels. 2. Panel Support Tolerances: Confirm that panel supports are within tolerances acceptable to metal panel system manufacturer but not greater than the following: a. 1/4 inch (6 mm) in 20 foot (6.1 m) in any direction. b. 3/8 inch (9 mm) over any single roof plane. B. Correct out-of-tolerance work and other deficient conditions prior to proceeding with insulated metal roof panel system installation. C. Wall panels to be continuous from base to eave, and eave to ridge. 1. Fastener population to be shown on erection details. D. Erection shall in all respects be in accordance with industry standards, by qualified, experienced erectors using proper tools and equipment, and in accordance with manufacturer's recommendations. E. Correction of minor misalignments by the use of drift pins and a moderate amount of reaming or cutting will be permitted. 3.2 ERECTION OF STRUCTURAL FRAMING A. Erect metal building system according to manufacturer's written instructions and drawings. B. Do not field cut, drill, or alter structural members without written approval from metal building system manufacturer's professional engineer. C. Set structural framing accurately in locations and to elevations indicated, according to AISC specifications referenced in this Section. Maintain structural stability of frame during erection. D. Base and Bearing Plates: Clean concrete- and masonry-bearing surfaces of bond-reducing materials, and roughen surfaces prior to setting plates. Clean bottom surface of plates. 1. Set plates for structural members on wedges, shims, or setting nuts as required. 2. Tighten anchor rods after supported members have been positioned and plumbed. Do not remove wedges or shims but, if protruding, cut off flush with edge of plate before packing with grout. 3. Promptly pack grout solidly between bearing surfaces and plates so no voids remain. Neatly finish exposed surfaces; protect grout and allow to cure. Comply with manufacturer's written installation instructions for shrinkage-resistant grouts. 13600- 8 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 E. Align and adjust structural framing before permanently fastening. Before assembly, clean bearing surfaces and other surfaces that will be in permanent contact with framing. Perform necessary adjustments to compensate for discrepancies in elevations and alignment. 1. Level and plumb individual members of structure. F. Primary Framing and End Walls: Erect framing level, plumb, rigid, secure, and true to line. Level baseplates to a true even plane with full bearing to supporting structures, set with double-nutted anchor bolts. Use grout to obtain uniform bearing and to maintain a level base-line elevation. Moist-cure grout for not less than seven days after placement. 1. Make field connections using high-strength bolts installed according to RCSC's "Specification for Structural Joints Using High-Strength Bolts" for bolt type and joint type specified. a. Joint Type: Snug tightened or pre-tensioned as required by manufacturer. G. Secondary Framing: Erect framing level, plumb, rigid, secure, and true to line. Field bolt secondary framing to clips attached to primary framing. 1. Provide rake or gable purlins with tight-fitting closure channels and fasciae. 2. Locate and space wall girts to suit openings such as doors and windows. 3. Provide supplemental framing at entire perimeter of openings, including doors, windows, louvers, ventilators, and other penetrations of roof and walls. H. Framing for Openings: Provide shapes of proper design and size to reinforce openings and to carry loads and vibrations imposed, including equipment furnished under mechanical and electrical work. Securely attach to structural framing. I. Erection Tolerances: Maintain erection tolerances of structural framing within AISC 303. 3.3 METAL PANEL INSTALLATION, GENERAL A. Fabricate and finish metal panels and accessories at the factory, by manufacturer's standard procedures and processes, as necessary to fulfill indicated performance requirements demonstrated by laboratory testing. Comply with indicated profiles and with dimensional and structural requirements. B. Examination: Examine primary and secondary framing to verify that structural-panel support members and anchorages have been installed within alignment tolerances required by manufacturer. 1. Examine roughing-in for components and systems penetrating metal panels, to verify actual locations of penetrations relative to seams before metal panel installation. C. General: Anchor metal panels and other components of the Work securely in place, with provisions for thermal and structural movement. 1. Field cut metal panels as required for doors, windows, and other openings. Cut openings as small as possible, neatly to size required, and without damage to adjacent metal panel finishes. 13600- 9 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 a. Field cutting of metal panels by torch is not permitted unless approved in writing by manufacturer. 2. Install metal panels perpendicular to structural supports unless otherwise indicated. 3. Flash and seal metal panels with weather closures at perimeter of openings and similar elements. Fasten with self-tapping screws. 4. Locate and space fastenings in uniform vertical and horizontal alignment. 5. Locate metal panel splices over structural supports with end laps in alignment. 6. Lap metal flashing over metal panels to allow moisture to run over and off the material. D. Lap-Seam Metal Panels: Install screw fasteners using power tools with controlled torque adjusted to compress EPDM washers tightly without damage to washers, screw threads, or metal panels. Install screws in predrilled holes. 1. Arrange and nest side-lap joints so prevailing winds blow over, not into, lapped joints. Lap ribbed or fluted sheets one full rib corrugation. Apply metal panels and associated items for neat and weathertight enclosure. Avoid "panel creep" or application not true to line. E. Metal Protection: Where dissimilar metals contact each other or corrosive substrates, protect against galvanic action by painting contact surfaces with corrosion-resistant coating, by applying rubberized-asphalt underlayment to each contact surface, or by other permanent separation as recommended by metal roof panel manufacturer. F. Joint Sealers: Install gaskets, joint fillers, and sealants where indicated and where required for weatherproof performance of metal panel assemblies. Provide types of gaskets, fillers, and sealants indicated; or, if not indicated, provide types recommended by metal panel manufacturer. 1. Seal metal panel end laps with double beads of tape or sealant the full width of panel. Seal side joints where recommended by metal panel manufacturer. 2. Prepare joints and apply sealants to comply with requirements in Section 079200 "Joint Sealants." 3.4 METAL ROOF PANEL INSTALLATION A. General: Provide metal roof panels of full length from eave to ridge unless otherwise indicated or restricted by shipping limitations. 1. Flash and seal metal roof panels with weather closures at eaves and rakes. Fasten with self-tapping screws. B. Standing-Seam Metal Roof Panels: Fasten metal roof panels to supports with concealed clips at each standing-seam joint, at location and spacing and with fasteners recommended by manufacturer. 1. Install clips to supports with self-drilling or self-tapping fasteners. 2. Install pressure plates at locations indicated in manufacturer's written installation instructions. 3. Snap Joint: Nest standing seams and fasten together by interlocking and completely engaging factory-applied sealant. 4. Seamed Joint: Crimp standing seams with manufacturer-approved motorized seamer tool so that clip, metal roof panel, and factory-applied sealant are completely engaged. 5. Rigidly fasten eave end of metal roof panels and allow ridge end free movement for thermal expansion and contraction. Predrill panels for fasteners. 13600- 10 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 6. Provide metal closures at rake edges, rake walls and each side of ridge caps. C. Lap-Seam Metal Roof Panels: Fasten metal roof panels to supports with exposed fasteners at each lapped joint, at location and spacing recommended by manufacturer. 1. Provide metal-backed sealing washers under heads of exposed fasteners bearing on weather side of metal roof panels. 2. Provide sealant tape at lapped joints of metal roof panels and between panels and protruding equipment, vents, and accessories. 3. Apply a continuous ribbon of sealant tape to weather-side surface of fastenings on end laps and on side laps of nesting-type metal panels, on side laps of ribbed or fluted metal panels, and elsewhere as needed to make metal panels weatherproof to driving rains. 4. At metal panel splices, nest panels with minimum 6-inch (152-mm) end lap, sealed with butyl-rubber sealant and fastened together by interlocking clamping plates. D. Metal Fascia Panels: Align bottom of metal panels and fasten with blind rivets, bolts, or self- drilling or self-tapping screws. Flash and seal metal panels with weather closures where fasciae meet soffits, along lower panel edges, and at perimeter of all openings. E. Metal Roof Panel Installation Tolerances: Shim and align metal roof panels within installed tolerance of 1/4 inch in 20 feet (6 mm in 6 m) on slope and location lines and within 1/8-inch (3- mm) offset of adjoining faces and of alignment of matching profiles. 3.5 METAL WALL PANEL INSTALLATION A. General: Install metal wall panels in orientation, sizes, and locations indicated on Drawings. Install panels perpendicular to girts, extending full height of building, unless otherwise indicated. Anchor metal wall panels and other components of the Work securely in place, with provisions for thermal and structural movement. 1. Unless otherwise indicated, begin metal panel installation at corners with center of rib lined up with line of framing. 2. Shim or otherwise plumb substrates receiving metal wall panels. 3. When two rows of metal panels are required, lap panels 4 inches (102 mm) minimum. 4. When building height requires two rows of metal panels at gable ends, align lap of gable panels over metal wall panels at eave height. 5. Rigidly fasten base end of metal wall panels and allow eave end free movement for thermal expansion and contraction. Predrill panels. 6. Flash and seal metal wall panels with weather closures at eaves and rakes, and at perimeter of all openings. Fasten with self-tapping screws. 7. Install screw fasteners in predrilled holes. 8. Install flashing and trim as metal wall panel work proceeds. 9. Apply elastomeric sealant continuously between metal base channel (sill angle) and concrete, and elsewhere as indicated on Drawings; if not indicated, as necessary for waterproofing. 10. Align bottom of metal wall panels and fasten with blind rivets, bolts, or self-drilling or self- tapping screws. 11. Provide weatherproof escutcheons for pipe and conduit penetrating exterior walls. B. Metal Wall Panels: Install metal wall panels on exterior side of girts. Attach metal wall panels to supports with fasteners as recommended by manufacturer. 13600- 11 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 C. Installation Tolerances: Shim and align metal wall panels within installed tolerance of 1/4 inch in 20 feet (6 mm in 6 m), noncumulative; level, plumb, and on location lines; and within 1/8-inch (3- mm) offset of adjoining faces and of alignment of matching profiles. 3.6 THERMAL INSULATION INSTALLATION A. General: Install insulation concurrently with metal panel installation, in thickness indicated to cover entire surface, according to manufacturer's written instructions. B. Blanket Roof Insulation: Comply with the following installation method: 1. Over-Framing Installation: Install in accordance with the industry guidelines found in North American Insulation Manufacturers Association (NAIMA) MB-316. C. Long Tab Banded (LTB) Filled Cavity Roof Insulation System. 1. Inspect materials for damage, proper sizes, and quantities upon delivery. Store materials in a dry secure manner. Notify carrier and laminator of any damaged material, improper sizes, or shortages immediately upon delivery. 2. Precautions: Long Tab Banded (LTB) Filled Cavity Insulation System does not act as fall protection. When installing the Long Tab Banded Insulation System; the Contractor, Builder, Erector, and Insulation Installer must meet Federal and State OSHA safety and fall protection standards. 3. Banding Installation: a. Install banding perpendicular to purlins to create a support system for insulation. Cut banding in lengths long enough to run from eave to eave, or eave to ridge, depending upon roof design. For gabled buildings, add extra length to accommodate irregular roof geometry. b. Spacing: 1) For purlins spaced 60 inches (1524 mm) on center, space banding a maximum of 30 inches (762 mm) on center. 2) Cut enough banding to accommodate spacing. c. Attach banding to bottom of eave strut and to each purlin using minimum 1/2 inch (13 mm) TEK screws. Pull banding as tight as possible to keep all subsequent runs parallel. 4. Lower Layer - Long Tab Faced Insulation Installation: a. Preparation: Organize insulation provided. 1) Faced insulation rolls are custom laminated to specific length and width to fit each purlin space. Each roll will have a "roll tag", indicating its correct location. Use correct roll of insulation for each location. b. Install faced insulation layer between and parallel to purlins. 1) Unroll insulation into cavity between purlins, on top of the metal banding. 13600- 12 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 2) Extend long tabs over top of each purlin, orientated such that tabs from adjacent runs are overlapping to create a continuous vapor retarder. For critical applications, tape or seal overlapping tabs with a suitable tape or sealant. 3) Do not pull tabs so tight that they cause the lower edges of the insulation to pull away from the sides of the purlins. 4) At End Wall: Peel insulation back from facing approximately 6 inches (152 mm) to 12 inches (305 mm), and remove to create an external tab that can be attached to the rake angle with tape or sealant. 5) At Internal Purlin Bracing: Ensure that insulation is not excessively compressed. In cases where the bracing will "substantially compress" the insulation, temporarily remove bracing to allow the faced insulation to be installed, and then replace the bracing. In applications where bracing removal is not practical, insulation and facing can be cut to fit around the bracings as follows: a) Determine where insulation will need to be cut to fit the bracing. b) Cut the entire width of the fiberglass and slit the facing tab to the depth of the brace to accommodate the bracing offset (distance from top of bracing to purlin's lower flange) on the purlin. Do not cut facing completely from edge to edge. (Example: If bracing is located 3 inches (76 mm) above the bottom flange of the purlin, cut the full width of the fiberglass and slit the facing tab starting 3 inches (76 mm) beyond each edge of the fiberglass, leaving the remainder intact.) c) After insulation is installed, seal facing from the bottom with a suitable tape to encapsulate the bracing. 6) Install the faced layer of insulation in the entire width of the roof slope before installing the top layer of unfaced fiberglass, thermal spacer blocks (where applicable), and roof sheets. 5. Installation of Top Layer of Unfaced Insulation and Roof. a. Unroll unfaced insulation perpendicular to purlins, making certain there are no gaps between edges of adjacent runs. b. Where it is necessary to splice the unfaced insulation, overlap the ends approximately 1 inch (25 mm) to 2 inches (50 mm) , before installing roof panels as follows: 1) Standing Seam Roofs: Install roof clips and spacer blocks, and attach roof panels. Care should be taken to ensure thermal spacer blocks remain in place directly above the purlins. 2) Plan installation to ensure there is no exposed insulation at the end of a work day or at the onset of inclement weather. a) Only install insulation as far out as can be covered in one day or as weather permits. b) Do not leave any insulation exposed to the elements overnight; the system is not designed to support the added weight associated with heavy rain or snow. c) Erector/Installer assumes responsibility for all materials once on site, and therefore should protect insulation from getting wet. 13600- 13 (ASI #1) Prefabricated Metal Building System Components Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 D. Blanket Wall Insulation: Install in accordance with the industry guidelines found in North American Insulation Manufacturers Association (NAIMA) MB-316. 3.7 CLEANING AND PROTECTION A. Repair damaged galvanized coatings on galvanized items with galvanized repair paint according to ASTM A 780/A 780M and manufacturer's written instructions. B. Touchup Painting: After erection, promptly clean, prepare, and prime or reprime field connections, rust spots, and abraded surfaces of prime-painted structural framing[, bearing plates,] and accessories. 1. Clean and prepare surfaces by SSPC-SP 2, "Hand Tool Cleaning," or by SSPC-SP 3, "Power Tool Cleaning." 2. Apply a compatible primer of same type as shop primer used on adjacent surfaces. C. Touchup Painting: Cleaning and touchup painting are specified in Section 099113 "Exterior Painting" and Section 099123 "Interior Painting." D. Metal Panels: Remove temporary protective coverings and strippable films, if any, as metal panels are installed. On completion of metal panel installation, clean finished surfaces as recommended by metal panel manufacturer. Maintain in a clean condition during construction. 1. Replace metal panels that have been damaged or have deteriorated beyond successful repair by finish touchup or similar minor repair procedures. E. Doors and Frames: Immediately after installation, sand rusted or damaged areas of prime coat until smooth and apply touchup of compatible air-drying primer. 1. Immediately before final inspection, remove protective wrappings from doors and frames. F. Windows: Clean metal surfaces immediately after installing windows. Avoid damaging protective coatings and finishes. Remove excess sealants, glazing materials, dirt, and other substances. Clean factory-glazed glass immediately after installing windows. END OF SECTION 15330 - 1 Automatic Fire Sprinkler Systems Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction March 18, 2019 SECTION 15330 AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Certified sprinkler Contractor shall design and install a complete, operable, code compliant fire sprinkler system for the existing building and new addition. B. The Contract Drawings indicate only the location of the existing fire riser location. It shall be the responsibility of the certified sprinkler Contractor to prepare shop drawings indicating the entire automatic fire sprinkler system. C. Any pipe sizes indicated are to be considered minimum. Where sizes are not indicated, the certified sprinkler Contractor shall provide the sizes as necessary to meet all code requirements. D. Sprinkler system shall protect the entire building. System shall be designed to hazard classifications listed with local Fire Marshal approval. 1. Offices Light Hazard 2. Shop Ordinary Hazard E. Provide sprinkler system protection to exterior canopies or overhangs where required by NFPA 13 or local Fire Marshal. F. Areas subject to freezing shall be protected by a dry pipe sprinkler system. G. Provide fire department connections within 100 feet of a fire hydrant and within 50 feet of a fire lane. Variation from these distances shall be approved by the local Fire Marshal. H. Contractor shall determine volume and pressure of incoming water supply from site water flow test data. For hydraulic calculations, Contractor shall pay for new site water flow test performed. I. Install indicating valve at each riser. Valves shall be locked and electrically supervised. J. Provide approved double detector check valve assembly at sprinkler system water supply connection as required by local Fire Department. 1.2 REGULATORY REQUIREMENTS A. Codes and Standards: 1. NFPA 13, Installation of Sprinkler Systems. 2. NFPA 14, Standpipe and Hose Systems. 3. NFPA 24, Private Fire Service Mains 4. Underwriters Laboratories (UL) Fire Protection Equipment Directory. 5. Current Factory Mutual (FM) Approval Guide. 6. Welding performed to ASME Standards. 7. International Building Code. 8. International Fire Code. 9. Local Fire Department Requirements. B. Hydraulic calculations, product data sheets, and sprinkler system shop drawings shall be approved by local Authority Having Jurisdiction, Owner’s Fire Insurance Company, and Engineer prior to beginning work. 1.3 QUALITY ASSURANCE A. The fire sprinkler system shall be designed by a Contractor licensed in the State of Texas and under direct supervision of a Responsible Managing Employee holding a current Class III N.I.C.E.T. certification or by a Registered Professional Fire Protection Engineer. 15330 - 2 Automatic Fire Sprinkler Systems Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction March 18, 2019 1.4 SUBMITTALS A. System Design Drawings: Indicate pipe sizes, materials used, jointing methods, supports, floor and wall penetration seals. Indicate installation, layout, weights, mounting and support details, and piping connections. B. Product Data: Provide data on sprinkler heads, valves, and specialties, including manufacturer’s catalog information. Submit performance ratings rough-in details, weights, support requirements, and piping connections. 1. Sprinklers shall be referred to on drawings, submittals, and other documentation, by the sprinkler identification or model number as specifically published in the appropriate agency listing or approval. Trade names or other abbreviated designations shall not be allowed. C. Manufacturer's Certificate: Certify that system has been tested and meets or exceeds requirements specified and required codes. D. All grooved joint couplings, fittings, valves, and specialties shall be the products of a single manufacturer. Grooving tools shall be of the same manufacturer as the grooved components. 1.5 PROTECTION A. All work, equipment and materials shall be protected at all times. Contractor shall repair all damage caused either directly or indirectly by his own work persons. Contractor shall also protect his own work from damage. He shall close all pipe openings with caps or plugs during installation. He shall protect all his equipment and materials against dirt, water, chemical and mechanical injury. Upon completion, all work shall be thoroughly cleaned and delivered in a new condition B. Contractor shall be held responsible for all damage to equipment and materials until he has received written notice from the Architect or Engineer that his work has been accepted. 1.6 UNINSPECTED WORK A. Contractor shall not allow or cause any of his work to be covered up before it has been duly inspected, tested and approved by the authorized inspectors having legal jurisdiction over his work. Should he fail to observe the above, he shall uncover his work and, after it has been inspected, tested and approved, recover it at his own expense. 1.7 RECORD DRAWINGS A. Contractor shall provide and keep up-to-date a complete "as-built" record set of drawings, which shall show every change from the original approved shop drawings and the exact "as- built" locations and sizes of the work provided under this Section of the specifications. This set shall include locations, dimensions, depth of buried piping, shut-off valves, etc. On completion of the work, this set of prints shall be delivered to the Architect. 1.8 FINAL APPROVAL A. Prior to final acceptance of the installation, the Contractor shall furnish to the Architect "certificates of approval" signed by all legally constituted authorities, stating that the systems, as installed, have been inspected and tested and meet all governing code requirements. 1.9 WARRANTY A. Contractor shall guarantee the automatic fire sprinkler systems unconditionally for a period of one (1) year after final acceptance. If, during this period, any materials, equipment, or any part of the systems fail to function properly, Contractor shall make good the defects promptly and without any expense to the Owner. 15330 - 3 Automatic Fire Sprinkler Systems Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction March 18, 2019 PART 2 - PRODUCTS 2.1 PIPE A. Below Ground: 1. Ductile iron pressure pipe, mechanical joint, Class 52, 150 psi working pressure, ANSI A21.51. 2. C-900 Poly Vinyl Chloride (PVC), DR18, Class 150, ASTM D3139, AWWA C900. B. Above Ground: 1. Steel pipe, black, Schedule 10, ASTM A53 or A135. 2. Steel pipe, black, Schedule 40, ASTM A53 or A135. 3. Steel pipe with wall thinner than Schedule 10 is not permitted. 4. CPVC pipe is not permitted. 2.2 FITTINGS A. Below Ground: 1. Ductile iron fittings, ANSI Standard A21.10. 2. PVC Fittings: AWWA C907 PVC injected molded gasketed for pressure applications (150 psi), ASTM D3139. B. Above Ground: 1. Cast iron threaded, Class 125, 175 psi WOG pressure rating, ANSI B16.4. 2. Cast iron flanged, Class 125, 175 psi WOG pressure rating, ANSI B16.1. 3. 2 inch and smaller sizes, precision cold drawn steel with elastomer O-ring seals, 175 psi CWP pressure rating, UL Listed and FM approved. Equal to Victaulic Pressfit®. 4. 5. Grooved: a. Ductile iron short-pattern with flow equal to standard fittings, 300 psi CWP pressure rating, ASTM Specification A536. b. Fitting, gasket, and coupling shall be furnished by same manufacturer. Grooving tools shall be of the same manufacturer as the grooved components. c. Acceptable manufacturers: Victaulic and Gruvlok. d. Reducing couplings will not be permitted. 6. Wrought copper fittings, pressure rated, solder type, ANSI B16.22. 7. Hole cut bolted branch outlets shall be full-bodied outlet. Equal to model 920/920N by Victaulic. 2.3 JOINTS A. Below Ground: 1. Mechanical joint for ductile iron pressure pipe and fittings; rubber gaskets, ANSI A21.11. 2. Push-fitting bell and spigot joint with gasket, ASTM F477. B. Above Ground: 1. Screwed joints: Tapered pipe threads, ANSI Standard B1.20.1. 2. Flanged: a. Cast iron, 250 psi WOG pressure rating, ANSI Standard B16.1. b. Square head machine bolts with semi-finished hexagon nuts, ASTM Specification A183. c. Neoprene gasket. 3. Mechanical coupling: a. Grooved couplings shall be of same manufacturer as used for grooved fittings. 15330 - 4 Automatic Fire Sprinkler Systems Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction March 18, 2019 b. Ductile iron in conformance with ASTM Specification A536, equal to Victaulic No. 75 or rigid mechanical coupling with offsetting angle-pattern bolt pads, installation-ready type. Equal to Victaulic Style 009-EZ or-equal to Victaulic style No. 005, ASTM A-536. 1). Rigid couplings shall be fully installed at visual pad-to-pad offset contact. (Tongue and recess type couplings, or any coupling that requires exact gapping of bolt pads on each side of the coupling at specified torque ratings, are not allowed.) c. Gaskets: 1). Wet systems: Grade E EPDM gasket, ASTM Specification D2000. 2). Dry systems: Victaulic "FlushSeal.” d. Rigid or zero flex type couplings shall be used when operating pressures may cause piping to move out of place or sway on hangers. Flexible couplings may be used where piping is properly braced or clamped into rigid position for flexibility and seismic applications. 2.4 PIPE SUPPORTS A. Hangers and supports shall be listed and labeled by Underwriters Laboratory and shall comply with NFPA 13. 1. In grooved installations, use equal to Victaulic Style 009, 005, and 07 rigid couplings with offsetting angle-pattern bolt pads, which permit support and hanging in accordance with NFPA-13. B. Seismic Supports: 1. In areas classified as seismic by the International Building Code, all sprinkler system piping shall be braced to withstand seismic movement per the requirements of NFPA 13. 2. Pipe sway bracing shall be installed to resist lateral and longitudinal seismic loads and to prevent unrestrained vertical movement per the requirements of NFPA 13. This shall include 4-way bracing of all building risers to the building structure. 3. Flexible couplings shall be installed where required to provide expansion capability, and for earthquake protection per the requirements of NFPA 13. 4. Clearances around all system piping between building components and other trades shall be strictly maintained per the requirements of NFPA 13. 2.5 VALVES A. All valves shall be UL Listed or FM Approved for application. B. Gate Valve: Outside screw and yoke (OS&Y), bronze body and trim or ductile iron body bronze mounted and rated for 175 psi non-shock cold water working pressure, equal to Nibco Series 609 or Victaulic Series 771 (grooved ends). C. Check Valve: 1. Non-slam: 175 psi, iron body, bronze seat, stainless steel clapper and spring with replaceable rubber seal, equal to Nibco series 480. 2. 250 psi, grooved end ductile iron body, welded-in nickel or PPS coated seat, stainless steel spring and shaft, elastomer seal or disc coating, equal to Victaulic Series 717. 3. Swing: 175 psi, iron body, bronze trim, replaceable rubber seat, equal to Nibco series 403. D. Butterfly Valve: 1. Indicating type: 300 psi WOG, equal to Nibco series 3510 or Victaulic Series 705W (grooved end). a. Operator shall be weatherproof, with factory-wired supervisory switches and handwheel. 2. Non-indicating type: 175 psi WOG, equal to Nibco series 3510. 3. Lug type: 250 psi non shock cold water, ductile iron body. suitable for bidirectional dead-end service at rated pressure without use of downstream flange. 15330 - 5 Automatic Fire Sprinkler Systems Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction March 18, 2019 4. Grooved end type: 300 psi non shock cold water, ductile iron body, elastomer coated disc with integrally cast stem, suitable for bidirectional dead-end service at rated pressure. E. Test and Drain Valves: 1. Threaded bronze globe type with composition disc, 175 psi WOG, equal to Nibco KT- 65 for piping assemblies built on site. 2. Combined test and drain valve, equal to Victaulic style 720 TestMaster II. F. Drain Valves: 1. Screw-in bonnet bronze globe valves, rated to 175-psi non-shock cold water working pressure. 2. Low point drain valves shall have, in addition, 3/4" brass nipple with 3/4" male hose threads and cap. G. Indication Signs: 1. All control, drain, and test connection valves shall be provided with permanently marked weatherproof metal or rigid plastic identification signs. 2. The identification sign shall be secured with corrosion-resistant wire, chain, or other approved means. 3. The control valve sign shall identify the portion of the building served. H. Valves installed in galvanized piping shall be bronze. I. Acceptable Manufacturers: Central, Nibco, Milwaukee, Mueller, Reliable, Victaulic, Kitz, or Viking, model equal to number listed. 2.6 PRESSURE GAUGES A. Pressure gauges shall be installed in each system riser. B. Pressure gauges shall be installed above and below each alarm check valve or system riser check valve where such devices are present. 2.7 DOUBLE DETECTOR CHECK VALVE ASSEMBLY A. The double check detector assembly shall consist of two independently operating, spring loaded check valves, two UL/FM, OSY resilient wedge gate valves, and bypass assembly. B. The bypass assembly consists of a meter, a double check including shutoff valves and required test cocks. C. Each cam-check shall be internally loaded and provide a positive drip tight closure against reverse flow. Cam-check includes a stainless steel cam arm and spring, rubber faced disc and a replaceable seat. D. The body shall be manufactured from 300 series stainless steel, 100% lead free, through the water way, with a single two-bolt grooved style access cover. E. No special tools shall be required for servicing. F. Double Check Detector Assembly shall be an Ames Fire & Waterworks 3000SS series or approved equal by local Authority Having Jurisdiction. Febco is an approved manufacturer. G. Install in riser room or concrete vault as noted on plans and required by local Fire Marshal. 2.8 DRY PIPE VALVE A. Acceptable manufacturers: Viking, Central, Reliable, or Victaulic (grooved end). B. Each dry pipe valve assembly shall be independent of each other and must contain separate valves and accessories. C. Dry pipe valve shall be mechanical advantage check valve assembly. D. Dry valve internal components shall be replaceable without removing the valve from the installed position. 15330 - 6 Automatic Fire Sprinkler Systems Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction March 18, 2019 E. Dry valve shall be externally resettable. F. Required air pressure shall be 13 psi / 90-kPa. G. Each system shall include, but not be limited to the following components: 1. Dry pipe valve. 2. Standard dry pipe valve trim. 3. Alarm pressure switch. 4. Supply control valve. 5. Air supervisory pressure switch. 6. Air supply control valve. 7. Electric accelerator for fast response time. H. Air Compressor: 1. Air compressor shall be UL listed 2125 for dry sprinkler systems. 2. Compressor shall be oil-less, piston type with no lubrication required. 3. Compressor shall be motor mounted with pipe mounting bracket. 4. Air compressor shall be equal to Gast. 5. Water motor alarm gong shall be included with dry pipe valve. 2.9 WATERFLOW ALARM A. A water motor alarm shall be connected to each alarm valve and shall discharge to a brass alarm gong located on the exterior of the building. The alarm valves shall be Underwriters' Laboratories approved, wet type, connected to water supply and indicated on the Shop Drawings. Each alarm valve shall be provided with a circuit closer. Valves shall conform to the equipment of NFPA 13, complete with retarding chamber and pressure switch. B. Provide at sprinkler risers, McDonnell UL approved line size water flow alarm switches. See Division 16 for electrical signal connection by Electrical and Fire Alarm Contractors. 2.10 FIRE DEPARTMENT CONNECTION A. Wall-Type, Fire Department Connection: 1. UL 405, 175-psig minimum pressure rating; with corrosion-resistant-metal body with brass inlets, brass wall escutcheon plate, brass lugged caps with gaskets and brass chains, and brass lugged swivel connections. 2. Include inlets with threads according to NFPA 1963 and matching local fire department sizes and threads, outlet with pipe threads, extension pipe nipples, check devices or clappers for inlets, and escutcheon plate with marking similar to "AUTO SPKR & STANDPIPE." B. At the low-point near each fire department connection, install a 90-degree elbow with drain connection to allow for system drainage to prevent freezing. Elbow equal to Victaulic #10- DR. 2.11 SPRINKLER HEADS A. Ceilings Areas: Recessed with chrome heads. Heads shall be quick response type in light hazard areas per NFPA 13. B. Exposed Areas: Upright type with chrome plated finish. C. Sidewall Areas: Sidewall type with chrome plated finish. D. Extended Coverage: Use when necessary due to construction limitations. E. Dry System Heads: Heads used in dry pipe systems shall be approved by manufacturer for dry system application. F. Automatic sprinkler heads used under or on finished ceilings or wall shall be equipped with a metallic escutcheon plate of the same finish at the sprinkler head. Utilized recessed escutcheons when possible. 15330 - 7 Automatic Fire Sprinkler Systems Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction March 18, 2019 1. Escutcheons and guards shall be listed, supplied, and approved for use with the sprinkler by the sprinkler manufacturer. G. Sprinklers shall be glass-bulb type, with hex-shaped wrench boss integrally cast into the sprinkler body to reduce the risk of damage during installation. 1. Wrenches shall be provided by the sprinkler manufacturer that directly engage the hex-shaped wrench boss integrally cast in the sprinkler body. H. Sprinkler head temperature rating shall be for specific area hazard and be based on maximum ambient temperature of the environment per NFPA 13. I. Sprinkler heads installed in freezers, coolers, or unconditioned medical gas bottle rooms shall be freeze proof pendent or sidewall type. PART 3 - EXECUTION 3.1 PREPARATION A. Ream pipe and tube ends, remove burrs and bevel or groove plain end ferrous pipe. B. Remove scale and foreign material, from inside and outside, before assembly. C. Prepare piping connections to equipment with flanges, grooved joint couplings or unions. D. Flush entire system of foreign matter 3.2 INSTALLATION A. Install piping in accordance with NFPA 13 for sprinkler systems, NFPA 14 for standpipe and hose systems, and NFPA 24 for service mains. The Certified Contractor shall provide proper sizes, materials and installation per approved calculations as required in the appropriate NFPA Standard. B. Sprinkler risers shall be located within five (5) feet of the building perimeter or as required by local Fire Marshal. Sprinkler water supply pipe shall not be installed beneath building structure beyond this distance. Install concrete thrust blocks at underground pipe change of direction. C. Provide a water flow switch for each sprinkler zone. Install control valve with supervisor switch and water flow switch in easily accessible locations. D. Qualified and trained personnel, experienced with the products involved, and the recommended methods of preparation, shall prepare all piping and fittings. All cuts, threads and grooves shall be made according to applicable codes, standards and accepted good practices. Pipe shall be free of damage, flaws and burrs. Threads and grooves shall not be excessively shallow or deep. Fittings shall be made onto pipe no tighter than necessary. Contractor shall replace cracked or broken fittings, without exception. Excess thread sealants and oils shall be removed before shipment to job site. 1. The grooved coupling manufacturer’s factory trained representative shall provide on- site training for contractor’s field personnel in the use of grooving tools and installation of grooved joint products. The representative shall periodically visit the jobsite and review contractor is following best recommended practices in grooved product installation. (A distributor’s representative is not considered qualified to conduct the training or jobsite visit(s).) E. Route piping in orderly manner, plumb and parallel to building structure and maintain gradient. F. All penetrations of rated walls, floors, or assemblies shall include fire stopping seal complying with ASTM E814. 15330 - 8 Automatic Fire Sprinkler Systems Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction March 18, 2019 G. The Contractor is responsible for all cutting and patching work required for this installation. Locations shall be marked carefully and holes shall be no larger than necessary for the pipe involved. Hole size shall be strictly limited to a size, which can be covered by a standard sized escutcheon. The Contractor at no additional cost to the owner shall patch misaligned and oversized holes. Cutting/drilling of exterior wall shall require the re-insulation and packing of the opening to meet original R-value and prevent air infiltration. Any cutting of structure shall be subject to approval by the Architect. Beams, decks and other structural components shall not be cut or altered in any way unless previously approved. H. Contractor shall be responsible for all welded joints and any qualifying procedures or certification required for welders and related personnel. Welding methods shall meet or exceed the requirement described in NFPA 13 I. Holes in pipe for welded outlets shall be cut to full inside diameter of fitting, prior to welding in place. Holes shall be free of slag and welding residue, and of smooth, continuous bore. Fittings shall not penetrate internal diameter of run piping. Holes shall be cut by hole saw or other rotary bit. Torch cutting of holes is strictly prohibited. J. All supports shall be UL listed and comply with NFPA 13. Support all piping from building’s structural elements. K. Slope piping and arrange systems to drain at low points. Use eccentric reducers to maintain top of pipe level. Entire sprinkler system shall be installed in such a manner so that it can be drained in accordance with NFPA 13. Drains shall be located at suitable points as approved by Architect. No primary or auxiliary drain shall be located in any public area or electrical room. All drains shall discharge into exterior or dedicated plumbing receptors. L. Provide drain valves at main shut-off valves, low points of piping and apparatus. Provide Fire Department test station, piped to drain. M. Locate outside alarm gong on building wall directly outside sprinkler riser room. N. Place pipe runs to minimize obstructions with other work. Coordinate with General, Mechanical, and Electrical Contractors. O. Place piping in concealed spaces above finished ceilings. Location of exposed pipe in occupied spaces shall be coordinated with architect. P. Coordinate heads within architectural ceiling grid. Center heads in two directions in ceiling tile and provide piping offsets as required. Avoid conflict with lights and HVAC diffusers. 1. A stainless steel flexible drop system, equal to Victaulic EX-Flex, may be used to properly locate sprinkler heads. The drop system shall be supplied with required supporting members and bracing. Q. Do not install sprinklers that have been dropped, damaged, or show a visible loss of fluid. Never install sprinklers with cracked bulbs. R. The sprinkler bulb protector shall be removed by hand after installation. Do not use tools or any other device(s) to remove the protector that could damage the bulb in any way. S. Apply paper cover to ensure concealed sprinkler head and cover plates do not receive field paint finish. Remove cover when painting work is complete. T. Locate fire department connection with sufficient clearance from walls, obstructions, parking to comply with required NFPA access and to allow full swing of fire department wrench handle. U. No work shall be covered or enclosed until inspected, tested, and approved by Architect and authority having jurisdiction. Should any work be concealed before inspection, the Contractor shall, at his own expense, uncover such work and after it has been inspected, tested and approved, provide for all repairs as may be necessary to restore any other affected work to its original and proper condition. 15330 - 9 Automatic Fire Sprinkler Systems Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction March 18, 2019 V. Upon completion of the work specified, and at other times during the progress of the work when required, the Contractor shall remove all surplus materials, rubbish and debris resulting from this work, and shall leave the entire building and involved portions of the site, insofar as the work of these Sections are concerned, in a neat, clean and acceptable condition. W. The Sprinkler Contractor shall be held responsible during the installation and testing periods of the sprinkler system for any damage to the work of others, to the building, its contents, etc., caused by leaks in any sprinkler equipment, by unplugged or disconnected sprinkler pipes, fittings, etc., or by overflow. Sprinkler Contractor shall pay for necessary replacements or repairs to items damaged by such leakage. 3.3 SYSTEM CONNECTIONS A. Flushing Connections: Provisions shall be made to facilitate the flushing of the system. A flushing connection shall be provided at the end of each cross main terminating in 2 inch and larger pipe. Each flushing connection shall have a 2 inch capped nipple not less than 4 inches long. B. Drain Connections: Provisions shall be made to drain all pockets or low points occurring in the piping systems. The two inch system drainpipe shall be arranged to discharge to the exterior of the building unless prohibited by regulatory authorities. The discharge point shall be low on exterior wall and away from normal pedestrian travel paths. C. Test Connections: The Sprinkler Contractor shall provide a test connection at the highest point in the main portion of each sprinkler system. Each test connection shall be provided with a 1inch pipe and valve. The test pipe shall be connected to a sprinkler pipe at least 1- 1/4 inches in size and shall discharge outside the building through a 1/2-inch smooth bore brass outlet where it can easily be seen. 3.4 TESTING AND FLUSHING A. All piping in this installation shall be thoroughly cleaned and tested during the progress of the work, at the completion of the work, or at other times as may be required. All piping shall be hydrostatically tested per NFPA 13 to meet the approval of the local Fire Department or Authority Having Jurisdiction. B. The Sprinkler Contractor shall complete a standard Contractor's Material & Test Certificate for all above ground piping and forward same to the building owner at completion of all testing. C. No piping shall be concealed before being tested. All joints shall be inspected for leaks during the test, and any leaks, which develop, shall be repaired and the complete test repeated. D. Leaks shall be repaired by disassembly, correction and reassembly only. Caulking of joints will not be permitted and leaking joints must be remade. Stuffing boxes on all valves shall be repacked with new packing and made tight. Systems shall be tested and repaired until all requirements are met. E. Testing shall be done at the expense of the Sprinkler Contractor, with all required equipment furnished by him. 3.5 MAINTENANCE MANUALS A. Two complete sets of equipment maintenance manuals shall be assembled in 3-ring binders and placed in the sprinkler room. Binders shall include all manufacturer’s cuts and maintenance information on equipment used in this fire protection installation. B. Equipment shall include: valves, check valves, flow switches, tamper switches, hose equipment and all other relevant fire protection equipment which could require future maintenance. END OF SECTION 16602 - 1 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 SECTION 16602 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm box. 3. System smoke detector. 4. Notification appliance. 5. Digital alarm communicator transmitter. 1.3 SYSTEM DESCRIPTION A. Non-coded, UL Listed intelligent analog addressable fire alarm system with multiplexed signal transmission. B. The System supplied under this specification utilize independently addressed, input/output modules, power supply(s) as described in this specification. The system contains a fire alarm control panel, remote annunciator(s) and NAC power supply(s). 1.4 SUBMITTALS A. The Contractor shall purchase no equipment for the system specified herein until the Owner has approved the project submittals in their entirety and has returned them to the contractor. It is the responsibility of the contractor to meet the entire intent and functional performance detailed in these specifications. Approved submittals shall only allow the contractor to proceed with the installation and shall not be construed to mean that the contractor has satisfied the requirements of these specifications. The Contractor shall submit three (3) complete sets of documentation within 30 calendar days after award of purchase order. B. Each submittal shall include a cover letter providing a list of each variation that the submittal may have from the requirements of the Contract Documents. In addition the Contractor shall provide specific notation on each Shop Drawing, sample, catalog cut, data sheet, installation manual, etc. submitted for review and approval, of each such variation. 1. Submittals shall be approved by authorities having jurisdiction prior to submitting them to the Architect. 2. Shop Drawings shall be prepared by persons with the following qualifications: a. Trained and certified by manufacturer in fire-alarm system design. b. NICET-certified fire-alarm technician, Level III minimum C. Product Data: Product Data sheets with the printed logo or trademark of the manufacturer of all equipment. Indicated in the documentation shall be the type, size, rating, style, and catalog number for all items proposed to meet the system performance detailed in this specification. The proposed equipment shall be subject to the approval of the Owner. 16602 - 2 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 D. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work. 1. Comply with recommendations in the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter in NFPA72. 2. Include voltage drop calculations for notification appliance circuits. 3. Include battery-size calculations. E. Operation and Maintenance Data: In addition to items specified in Division 1 Section "Operation and Maintenance Data, include the following: 1. Comply with the "Records" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA72. 2. Record copy of site-specific software database file, hardcopy print-out and CD, with password for delivery to the owner. Proprietary system/service companies will not be acceptable. 3. Provide "Maintenance, Inspection and Testing Records" according to NFPA72 and include the following: a. Frequency of testing of installed components. b. Frequency of inspection of installed components. c. Requirements and recommendations related to results of maintenance. d. Manufacturer's user training manuals (hardcopy) and electronic on CD. 4. Manufacturer's required maintenance related to system warranty requirements. 5. Abbreviated operating instructions for mounting at fire-alarm control unit. F. Software and Firmware Operational Documentation: 1. Software operating and upgrade manuals. 2. Program Software Backup: On magnetic media or compact disk, complete with data files. 3. Device address list. 4. Printout of software application. 5. CD of site-specific software database file with password, and electronic product data sheets. Provide hard copy print-out of the software program. Proprietary system/service companies will not be acceptable. 6. Provide a list of global system settings 7. Provide a list of the contents of each system cabinet and their settings 8. Provide a list of all addressable devices with their addresses and settings 1.5 QUALITY ASSURANCE A. Installer Qualifications: Personnel shall be trained and certified by manufacturer for installation of units required for this Project. B. Installer Qualifications: Installation shall be by personnel certified by a licensed Fire Alarm Technician by the State of Texas. C. Source Limitations for Fire-Alarm System and Components: Obtain fire-alarm system from single source from single manufacturer. Components shall be compatible with, and operate as, an extension of existing system. D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA70, by a qualified testing agency, and marked for intended location and application. 16602 - 3 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 1.6 WARRANTY AND SOFTWARE SERVICE AGREEMENT A. The contractor shall warranty all materials, installation and workmanship for one (1) year from date of acceptance, unless otherwise specified. B. The System Supplier shall maintain a service organization with adequate spare parts stocked within 75 miles of the installation. Any defects that render the system inoperative shall be repaired within 24 hours of the Owner notifying the contractor. C. Technical Support: Beginning with Substantial Completion, provide software support for one (1) year shall be included in this project. D. Detector Sensitivity Testing: During the warranty period, each year the contractor is to perform detector sensitivity testing and provide report to the Owner. Unless, the system is UL Listed to perform automatic sensitivity testing without any manual intervention and should detector fall outside of sensitivity window, the system will automatically indicate a device trouble. A copy of UL letter is to be provided as proof of system operation. E. Upgrade Service: Update software to latest version at Project completion. Install and program software upgrades that become available within one (1) year from date of Substantial Completion. Upgrading software shall include operating system. Upgrade shall include new or revised licenses for use of software. 1. Provide 30 days' notice to Owner to allow scheduling and access to system and to allow Owner to upgrade computer equipment if necessary. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Manufacturers: The materials, appliances, equipment and devices shall be tested and listed by a nationally recognized approvals agency for use as part of a protected premises protective signaling fire alarm system. The authorized representative of the manufacturer of the major equipment, such as control panels, shall be responsible for the satisfactory installation of the complete system. B. The Contractor shall provide, from the acceptable manufacturer's current product lines, equipment and components, which comply, with the requirements of these Specifications. Equipment or components, which do not provide the performance and features, required by these specifications are not acceptable, regardless of manufacturer. C. Strict conformance to this specification is required to ensure that the installed and programmed system will function as designed, and will accommodate the future requirements and operations of the building Owner. All specified operational features must be met without exception. D. All control panel assemblies and connected (new) field appliances shall be provided by the same System Supplier, and shall be designed and tested to ensure that the system operates as specified. All equipment and components shall be installed in strict compliance with the manufacturer's recommendations. E. Upon completion of the project the Owner shall be provided with a hard copy printout of the system software database and an electronic version of the system program and database with all required passwords. F. That equipment proposed to be supplied will be considered only if it meets all sections of the performance specification. Any deviations of system performance outlined in this specification will only be considered when the following requirements have been met: 16602 - 4 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 1. A complete description of proposed alternate system performance methods with three (3) copies of working drawings thereof for approval by the Owner, not less than ten (10) calendar days prior to the scheduled date for submission of bids. 2. The supplier of alternate equipment shall furnish evidence that the proposed alternate system performance is equal to or superior than the system operation stated in the specification. Such evidence shall be submitted to the Owner, not less than ten (10) calendar days prior to the scheduled date for submission of bids. 3. The supplier shall submit a point-by-point statement of compliance for all sections in this specification. The statement of compliance shall consist of a list of all paragraphs within these sections. Where the proposed system complies fully with the paragraph as written, placing the word "comply" opposite the paragraph number shall indicate such. Where the proposed system does not comply with the paragraph as written, and the supplier feels the proposed system will accomplish the intent of the paragraph, a full description of the function as well as a full narrative description of how its proposal will meet its intent shall be provided. Any submission that does not include a point-by-point statement of compliance as described herein shall be disqualified. Where a full description is not provided, it shall be assumed that the proposed system does not comply. 4. The supplier of alternate equipment shall submit a list from the alternate manufacture on the manufactures letterhead indicating the names and addresses of all authorized suppliers in the area. Proprietary products will not be considered. 5. The acceptability of any alternate proposed system shall be the sole decision of the Owner or his authorized representative G. Approved Products: All panels and peripheral devices shall be of the standard product of single manufacturer and shall display the manufacturer’s name of each component. H. Approved manufacturers that will be considered are as follows: 1. Notifier NFS-320 2.2 SYSTEMS OPERATIONAL DESCRIPTION A. Fire-alarm signal initiation shall be by one or more of the following devices: 1. Manual station. 2. Smoke detector. 3. Automatic sprinkler system water flow. B. Fire-alarm signal shall initiate the following actions: 1. Activate the audible and visual notification appliance. 2. Identify alarm at fire-alarm control unit. 3. Transmit an alarm signal to the remote alarm receiving station. 4. Record events in the system memory. C. Supervisory signal initiation shall be by one or more of the following devices and actions: 1. Valve supervisory switch. D. System trouble signal initiation shall be by one or more of the following devices and actions: 1. Open circuits, shorts, and grounds in designated circuits. 2. Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating devices. 3. Loss of primary power at fire-alarm control unit. 4. Ground or a single break in fire-alarm control unit internal circuits. 5. Abnormal ac voltage at fire-alarm control unit. 16602 - 5 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 6. Break in standby battery circuitry. 7. Failure of battery charging. 8. Abnormal position of any switch at fire-alarm control unit. E. System Trouble and Supervisory Signal Actions: Initiate notification appliance and annunciate at fire-alarm control unit. Record the event on system printer. 2.3 FIRE-ALARM CONTROL UNIT A. The control panel shall contain a microprocessor with 10/100 ethernet media access controller (MAC). The system shall be designed specifically for fire detection, and notification applications. The control panel shall be listed and approved for the application standard(s) as listed under the General section. Panel shall be Notifier NFS-320. B. The control panel shall include all required hardware, software and system programming to provide a complete and operational system. The control panel shall assure that life safety takes precedence among all panel activities. C. The control panel shall include the following capacities: 1. Support up to 318 analog/addressable points. 2. Support digital dialer with Contact ID format 3. Support up to 1000 chronological events. D. The control panel shall include the following features: 1. Ability to download or upload site applications and system diagnostics remotely through an Ethernet connection, or DACT. 2. Provide electronic addressing of analog/addressable devices. Rotary and dip switch addressing shall not be considered equal. 3. Provide an operator interface display that shall include functions required to annunciate, command and control system functions. 4. Provide an internal audible signal with different programmable patters to distinguish between alarm, supervisory, trouble and monitor conditions. 5. Provide system reports that provide detailed description of the status of system parameters for corrective action or for preventative maintenance programs. Reports shall be displayed by the operator interface or capable of being printed on a printer. 6. Provide an authorized operator with the ability to operate or modify system functions like system time, date, passwords, holiday dates, restart the system and clear control panel event history file. 7. Provide an authorized operator to perform test functions within the installed system. E. The control panel shall provide the following intelligent and intuitive diagnostic software tools. 1. Fast Ground Check a. Allow quick wiring diagnostics for ground faults every 4 seconds to troubleshoot ground faults much quicker and determine if they have been fixed or not. 2. Recalibrate Device a. The control panel recalibrates any devices that have been cleaned. The Recalibrate Device feature will immediately reset the environmental compensation and dirtiness levels for faster verification of cleaned devices. 3. Test Fire a. The control panel sends a test command to a detector or input module to activate. This allows for proper operation and programming testing of the device. 16602 - 6 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 4. Flash Device LED a. It shall be possible to activate any device LED from the control panel menu to help troubleshooting or locate a specific device on a loop. 5. Walk Test a. Walk test will allow the operator to test individual zones or devices without placing an alarm event on the system. b. It shall be possible to perform a walk test in a silent or audible test mode. Silent test mode shall display the test results on the LCD display. Audible test confirmation shall sound a coded signal on the systems NAC circuits. c. It shall be possible to activate Walk Test by zone or device to ensure the balance of the system remains in service to protect the premises. d. It shall be possible to view and print a walk test report showing the activation and restoration of all walk test events. 6. Device Maintenance a. It shall be possible to view and print a report of all detectors dirtiness levels to optimize cleaning schedules. The report shall filter for all devices, devices that are 20% dirty or devices that are 80% dirty. The report shall show the device, how dirty it is by percentage and its sensitivity setting. b. Detectors shall automatically send an alert message to the LCD Users Interface and illuminate the service detector LED when they reach 80% dirty and latch a trouble when they reach 100% dirty to ensure maintenance action is performed. F. Main Operators Display Operations: 1. Provide a discreet system control switch for reset, alarm silence, panel silence, remote disconnect, drill switch, and up/down/right/left switches. 2. Backlit LCD display shall be 80 character display. a. Each point shall have a 40 character custom message. 3. Service Detector LED: Provide indication when a detector needs servicing 4. Programmable Switches: Provide minimum of 2 programmable switches with corresponding LED . The switches shall be programmed for disable/enable or activate restore functions as follows; a. Disable NAC b. Disable Elevator Recall c. Disable Fan Shutdown 5. Alarm and Trouble Annunciator: Provide minimum of 16 zones of LED annunciation with red alarm and yellow trouble indicators; 4 zones may be utilized for supervisory zone annunciation. Devices on addressable loop circuits shall be identified by display or their address and by their condition (alarm, pre-alarm, monitor, supervisory, and trouble). G. Instructions: Computer printout or typewritten instruction card mounted behind a plastic or glass cover in a stainless-steel or aluminum frame. Include interpretation and describe appropriate response for displays and signals. Briefly describe the functional operation of the system under normal, alarm, and trouble conditions H. Circuits Requirements: 1. Signaling Line Circuits for Intelligent Analog Addressable Loop: a. Class A (style 7) 2. Notification Appliance Circuits: a. Class B (style Y) 16602 - 7 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 3. Activation of alarm notification appliances, elevator recall and other functions shall occur within 3 seconds after the activation of an initiating device. I. Door Controls: Door hold-open devices that are controlled by smoke detectors at doors in smoke barrier walls shall be connected to fire-alarm system. J. Smoke-Detector Sensitivity Adjustment: Controls shall select specific addressable smoke detectors for adjustment, display their current status and sensitivity settings, and change to alternate settings. Allow controls to be used to program repetitive, time-scheduled, and automated changes in sensitivity of specific detector groups. Record sensitivity adjustments and sensitivity-adjustment schedule changes in system memory, and print out the final adjusted values on system printer. K. Digital Alarm Communicator Transmitter: The system shall have an integrated off premise communications capability using a digital alarm communications transmitter (DACT) for sending system events to multiple central monitoring station (CMS) receivers. The system shall provide the CMS(s) with point identification of system events using Contact ID protocol. The dialer shall have the capability to support up to two (2) individual accounts and to send account information to two (2) different receivers, each having a primary and secondary telephone access number. System events shall be capable of being directed to one or more receivers depending on event type or location as specified by the system designed. 1. Digital data transmission shall include the following (Contact ID) a. Address of the alarm-initiating device. b. Loss of ac supply or loss of power. c. Low battery. d. Abnormal test signal. e. Communication bus failure f. Shall be internal to the panel. L. Ethernet Port: Provide a standard 10/100 Base T Ethernet port for connecting to an intranet or a local network. This connection shall support the downloading of configuration programming to the panel over the network, and provide the capability of diagnostic information from a remote location. M. Primary Power: 24-V dc obtained from 120-V ac service and a power-supply module. Initiating devices, notification appliances, signaling lines, trouble signals, shall be powered by nominal 24- V dc source. 1. Alarm current draw of entire fire-alarm system shall not exceed 80 percent of the power- supply module rating. N. Secondary Power: Shall provide 24 hours supervisory and 5 minutes of alarm with batteries, automatic battery charger, and automatic transfer switch. O. NAC Power Supply: The NAC power supply shall be independent unit that will provide power to visual strobe notification appliances. It shall be possible to configure the NAC’s to follow the main panel’s NAC or activate from intelligent synchronized modules. The booster NAC’s must be configurable to operate independently at any one of the following rates: continuous synchronized, or 3-3-3 temporal. Fault conditions on the power supply shall not impede alarm activation of host NAC circuits or other power supplies. The NAC power supply must be able to provide concurrent power for notification devices, security devices, access control equipment and auxiliary devices such as door holders. All the NAC Power Supplies shall be synchronized. The power supply shall support up to 24 amp hour batteries. 1. Power supply shall be a minimum of 10 amps and UL 864 Listed. 16602 - 8 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 2. Four independent 3amp NAC circuits. Each being configurable as auxiliary power. 3. All circuits shall be synchronized. 2.4 SYSTEM PRINTER A. Printout of Events: On receipt of signal, print alarm, supervisory, and trouble events. Identify zone, device, and function. Include type of signal (alarm, supervisory, or trouble) and date and time of occurrence. Differentiate alarm signals from all other printed indications. Also print system reset event, including same information for device, location, date, and time. Commands initiate the printing of a list of existing alarm, supervisory, and trouble conditions in the system and a historical log of events. 1. Each control panel shall be capable of supporting a printer. All control panel printer ports shall be configurable to output any combination of alarm, supervisory, trouble, monitor, or group event messages. 2.5 MANUAL FIRE-ALARM BOXES A. General Requirements for Manual Fire-Alarm Boxes: Comply with UL38. Boxes shall be finished in red with molded, raised-letter operating instructions in contrasting color; shall show visible indication of operation; and shall be mounted on recessed outlet box. If indicated as surface mounted, provide manufacturer's surface back box. 1. Double-action mechanism requiring two actions to initiate an alarm, pull-lever type; with integral addressable module arranged to communicate manual-station status (normal, alarm, or trouble) to fire-alarm control unit. 2. The manual pull station will have an intelligent module integral of the unit. 3. Station Reset: key operated switch shall match the control panel key. 4. Manual pull stations that initiated an alarm condition by opening the unit are not acceptable. 2.6 INTELLIGENT ANALOG SYSTEM SMOKE DETECTORS A. General Requirements for Intelligent Analog Detectors 1. Integral Microprocessor: All decisions are made at the detector determining if the device is in the alarm or trouble condition. 2. Non-Volatile Memory: Permanently stores serial number, and type of device. Automatically updates historic information including hours of operation, last maintenance date, number of alarms and troubles, time of last alarm and analog signal patterns for each sensing element just before last alarm. 3. Electronic Addressing: Permanently stores programmable system address. It shall be possible to address each intelligent module without the use of DIP or rotary switches. Devices using switches for addressing shall not be acceptable. 4. Automatic Device Mapping: Each detector transmits wiring information regarding its location with respect to other devices on the circuit, creating an As-Built wiring diagram. This will also provide enhanced supervision of the device physical location and the device message shall reside with the location and not the device address. Devices installed in the wrong location will always report the correct message of the physical location. 5. Sensitivity Range: Each analog addressable smoke detector's sensitivity shall be capable of being programmed individually as: most sensitive, more sensitive, normal, less sensitive or least sensitive. It shall be possible to automatically change the sensitivity of individual analog/addressable detectors for the day and night periods. It shall be possible to program control panel activity to each level. 6. Pre-Alarm: Detector stores 8 pre-alarm sensitivity values to alert local personnel prior to the sensor reaching a full evacuation sensitivity. Sensitivity values can be set in 5-10% increments. 16602 - 9 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 7. Environmental Compensation: The detector's sensing element reference point shall automatically adjust, compensating for background environmental conditions such as dust, temperature, and pressure. Periodically, the sensing element real-time analog value shall be compared against its reference value. The detector shall provide a maintenance alert signal when the detector reaches 80% compensation has been used. The detector shall provide a dirty fault signal and illuminate Service Detector LED on control panel. 8. Twin Status LEDs: Flashing Green LED shows normal; flashing RED shows alarm state; steady RED and steady GREEN show alarm state in stand-alone mode, visible from any direction. 9. UL Sensitivity Testing: The detector shall utilize a supervised microprocessor that is capable of monitoring the sensitivity of the detector. If the detector sensitivity shifts outside of the UL limits, a trouble signal is sent to the panel. 10. Device Replacement: The system shall allow for changing of detector types for service replacement purposes without the need to reprogram the system. The replacement detector type shall automatically continue to operate with the same programmed sensitivity levels and functions as the detector it replaced. System shall display an off- normal condition until the proper detector type has been installed or change in the application program profile has been made. B. Intelligent Photoelectric Detector 1. Provide intelligent analog addressable photoelectric smoke detectors at the locations shown on the drawings. C. Detector Base Types 1. Provide standard detector mounting bases suitable for mounting on 1-gang, or 4inch octagon box and 4 inch square box. The base shall, contain no electronics and support all series detector types. Bases with electronics or dip-switches are not acceptable. 2. Provide relay detector mounting bases suitable for mounting on 1-gang, or 4” octagon box and 4” square box. The relay base shall support all detector types and have the following minimum requirements: a. The relay shall be a bi-stable type and selectable for normally open or normally closed operation. b. The position of the contact shall be supervised. c. The relay shall automatically de-energize when a detector is removed. d. The operation of the relay base shall be controlled by its respective detector processor or under program control as required by the application. Detector relays not capable of operational programming independent of the detector shall not be considered equal. Form “C” Relay contacts shall have a minimum rating of 1 amp @ 30 Vdc and be listed for “pilot duty”. e. Removal of the respective detector shall not affect communications with other detectors. 2.7 Intelligent Modules A. It shall be possible to address each intelligent module without the use of DIP or rotary switches. Devices using switches for addressing shall not be acceptable. The personality of multifunction modules shall be programmable at site to suit conditions and may be changed at any time using a personality code downloaded from the Analog Loop Controller. 1. Integral Microprocessor: All decisions are made at the module determining if the device is alarm or trouble condition. Each module provides its own ground fault detection. 2. Non-Volatile Memory: Permanently stores serial number, and type of device. Automatically updates historic information including hours of operation, number of alarms and troubles, time of last alarm. 16602 - 10 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 3. Automatic Device Mapping: Each detector transmits wiring information regarding its location with respect to other devices on the circuit, creating an As-Built wiring diagram. This will also provide enhanced supervision of the device physical location. The device message shall reside with the location and not the device address. Devices installed in the wrong location will always report the correct message of the physical location. 4. Twin Status LEDs: The modules shall have a minimum of 2 diagnostic LEDs mounted behind a finished cover plate. A green LED shall flash to confirm communication with the loop controller. A red LED shall flash to display alarm status. 5. Input and output circuit wiring shall be supervised for open and ground faults. 6. Two styles of modules shall be available, those designed for gang box mounting, and where multiple modules are required in a single location, plug in modules shall be provided with a Universal Input/Output motherboard. B. Intelligent Input Module. The Input Module shall provide one or two supervised Class B input circuit capable of a minimum of 4 personalities, each with a distinct operation. The module shall be suitable for mounting on North American 2 ½” (64mm) deep 1-gang boxes and 1 ½” (38mm) deep 4” square boxes with 1-gang covers. The single input module shall support the following circuit types: 1. Normally-Open Alarm Latching (Manual Stations, Heat Detectors, etc.) 2. Normally-Open Alarm Delayed Latching (Waterflow Switches) 3. Normally-Open Active Non-Latching (Monitor, Fans, Dampers, Doors, etc.) 4. Normally-Open Active Latching (Supervisory, Tamper Switches) C. Intelligent Relay Module. Provide addressable control relay circuit modules shall provide one (1) form C dry relay contacts rated at 24Vdc @ 2 amps (pilot duty) to control external appliances or equipment. The position of the relay contact shall be confirmed by the system firmware. The module shall be suitable for mounting on North American 2 ½” (64mm) deep 1-gang boxes and 1 ½” (38mm) deep 4” square boxes with 1-gang covers. D. NAC Control Module: Provide intelligent NAC control module shall provide one (1) supervised Class B output circuit capable of a minimum of 2 personalities, each with a distinct operation. The gang box -mounted version shall be suitable for mounting in North American 2 ½” (64mm) deep 2-gang boxes and 1 ½” (38mm) deep 4” square boxes with 2-gang covers, or European 100mm square boxes. The plug-In version shall plug into a universal multi-module motherboard. The NAC control module shall support the following operations: 1. 24volt NAC circuit 2. Audio notification circuit 25v or 70v 3. Telephone Power Selector with Ring Tone (Firefighter’s Telephone) 4. Visual Synchronized Output to Genesis appliances or to NAC Power Supply. 2.8 NOTIFICATION APPLIANCES A. All appliances shall be of the same manufacturer as the Fire Alarm Control Panel specified to insure absolute compatibility between the appliances and the control panels, and to insure that the application of the appliances are done in accordance with the single manufacturers’ instructions. B. Any appliances, which do not meet the above requirements, and are submitted, for use must show written proof of their compatibility for the purpose intended. Such proof shall be in the form of documentation from all manufacturers which clearly states that their equipment (as submitted) are 100% compatible with each other for the purposes intended. All appliances shall be UL listed Fire Protective Service and shall be UL 1971. C. Notification Appliances – Visual 16602 - 11 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 1. Provide wall or ceiling mounted white strobes with in-out screw terminals shall be provided for wiring. Strobes shall provide a smooth light distribution pattern field selectable candela 15 cd, 30 cd, 75 cd, and 110 cd flash output rating. The strobe (15, 30, 75, 110) candela rating shall be view from the side window to verify the setting. All strobes shall be synchronization to within 10 milliseconds for an indefinite period and shall not require the use of separately installed remote synch modules. The strobes shall mount to one-gang electrical box. 2. The device shall have plastic protective cover. 3. The actual candela setting on the visual shall be marked on the appliance. D. Notification Appliance - Horn 1. Provide low profile wall mount white horns at the locations shown on the drawings. The horn shall provide an 95 dBA sound output at 10 ft. when measured in reverberation room per UL-464. The horn shall have a selectable steady or synchronized temporal output. In and out screw terminals shall be provided for wiring. The horn shall mount in a 1-gang box. 2. The device shall have plastic protective cover. E. Notification Appliance – Horn/Strobe 1. Provide low profile wall mount white horn/strobes at the locations shown on the drawings. The horn/strobe shall provide an audible output of 95 dBA at 10 ft. when measured in reverberation room per UL-464. Strobes shall provide synchronized flash outputs. The strobe output shall be determined as required by its specific location and application from a family of 15cd, 30cd, 60cd, 75cd & 110cd devices. The horn shall have a selectable steady or synchronized temporal output. In and out screw terminals shall be provided for wiring. Low profile horn/strobes shall mount to one-gang box. 2. The device shall have plastic protective cover. F. Notification Appliance – Harsh Environment Temporal Horn/Strobes: 1. Provide red electronic horn/strobes at the locations shown on the drawings. Horns shall be temporal output. At the high output setting, the horn shall provide a 85 dBA continuous sound output or a 95 dBA temporal sound output, when measured in reverberation room per UL-464. Strobes shall provide 15 cd, 75 cd, 110 cd synchronized flash outputs without the use of separate “synchronizing” modules. The strobe shall have lens markings oriented for wall or ceiling mounting. 2. In - Out screw terminals shall be provided for wiring. Horns shall mount to a North American 4” electrical boxes (2-1/8” deep) or to a 2-gang (2-3/4” deep) electric box. Weatherproof wall boxes shall be provided for outdoor applications. G. Notification Appliance – Exterior Temporal Horn/Strobes: 1. Provide red electronic horn/strobes at the FDC location shown on the drawings. Horn shall be temporal output. At the high output setting, the horn shall provide a 85 dBA continuous sound output or a 95 dBA temporal sound output, when measured in reverberation room per UL-464. Strobes shall provide 15 cd, 75 cd, 110 cd synchronized flash outputs without the use of separate “synchronizing” modules. The strobe shall have lens markings oriented for wall mounting. 2. In - Out screw terminals shall be provided for wiring. Horns shall mount to a North American 4” electrical boxes (2-1/8” deep) or to a 2-gang (2-3/4” deep) electric box. Weatherproof wall boxes shall be provided for outdoor applications. 2.9 INSPECTION BAR CODES A. Inspection bar codes shall be installed on all initiating devices, control panels and power supplies. 16602 - 12 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 B. Inspection bar codes used by the system must utilize Code 3 of 9 or other approved format, and contain a minimum of eight (8) digits that comprise a unique serial identifier within the Web- based Reporting System. There shall be no duplication of serial numbers. Serial number shall be printed below the bar code for identification purposes. C. Inspection bar codes shall be limited in size to no more than 2” (5cm) in width, and 3/8” (2 cm), in height and shall include a Mylar® or other protective coating to protect the bar code from fading due to sunlight or exposure. D. Inspection bar codes shall be installed on each device in such a manner as to require that scanning of the bar code take place no further than 12” from the device during inspection. 2.10 WIRE AND CABLE A. Signaling Line Circuits – Annunciator Data: Twisted pair, not less than No. 18Awg or as recommended by the manufacturer. B. Signaling Line Circuits – Intelligent Loop: Twisted pair, not less than No. 18Awg or as recommended by the manufacturer. 1. Circuit Integrity Cable: Provide as required to meet NFPA or Local Code requirements. 2. CI Cable shall meet National Electrical Code, power limited fire alarm service. C. Notification Appliance Circuits – 1. Horn and Visual. 12AWG THHN or FPLP or as recommended by the manufacturer. PART 3 - EXECUTION 3.1 EQUIPMENT INSTALLATION A. Comply with NFPA72 for installation of fire-alarm equipment. B. Notification Appliance Devices: Install between 80 and 96 inches on the wall. C. Fire-Alarm Control Unit: Surface mounted, with tops of cabinets not more than 72 inches above the finished floor. 3.2 IDENTIFICATION A. Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Division 16 Section "Electrical Identification." B. Install framed instructions in a location visible from fire-alarm control unit. C. All initiating devices shall have bar code label installed visibly on the device. This bar code shall be used for digital inspection of the fire alarm system using Building Reports.Com. 3.3 GROUNDING A. Ground fire-alarm control unit and associated circuits; comply with IEEE 1100. Install a ground wire from main service ground to fire-alarm control unit. 3.4 FIELD QUALITY CONTROL A. Field tests shall be witnessed by Architect, Engineer and authorities having jurisdiction. B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. 16602 - 13 Fire Alarm And Detection System Nelson + Morgan, Architects Flush Truck Storage Expansion NMA 18023 Issued for Bidding and Construction April 4, 2019 C. Perform tests and inspections. 1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. D. Tests and Inspections: 1. System Testing: Comply with "Test Methods" Table in the "Testing" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA72. 2. Test audible appliances for the public operating mode according to manufacturer's written instructions. Perform the test using a portable sound-level meter complying with Type 2 requirements in ANSI S1.4. 3. Test audible appliances for the private operating mode according to manufacturer's written instructions. 4. Test visible appliances for the public operating mode according to manufacturer's written instructions. 5. Factory-authorized service representative shall prepare the "Fire Alarm System Record of Completion" in the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter in NFPA72 and the "Inspection and Testing Form" in the "Records" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA72. E. Reacceptance Testing: Perform reacceptance testing to verify the proper operation of added or replaced devices and appliances. F. Fire-alarm system will be considered defective if it does not pass tests and inspections. G. Prepare test and inspection reports. H. Maintenance Test and Inspection: Perform tests and inspections listed for weekly, monthly, quarterly, and semiannual periods. Use forms developed for initial tests and inspections. I. Annual Test and Inspection: During the warranty period, test the fire-alarm system to verify compliance with visual and testing inspection requirements in NFPA72. Use forms developed for initial tests and inspections. J. Detector Sensitivity Testing: During the warranty period, the contractor is to perform detector sensitivity testing and provide report to the Owner. Unless, the system is UL Listed to perform automatic sensitivity testing without any manual intervention and should detector fall outside of sensitivity window, the system will automatically indicate a devices trouble. A copy of UL letter is to be provided as proof of system operation 3.5 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain fire-alarm system. END OF SECTION