Exhibit 4 - Retaining Wall Design - Brinker SubstationA TYPICAL MODULAR BLOCK WALL SECTION Scale: 1/2" = 1'-0" SETBACK =2 3/16" (5° BATTER)EXPOSED WALL (HEIGHT VARIES WITH DESIGN)REINFORCED SOIL (SELECT GRANULAR BACKFILL, SEE NOTE 'F') STRATAGRID SG500 GEOGRID SHALL HAVE FRICTION CONNECTION WITH BLOCKS AND SHALL EXTEND FULL LENGTH BACK INTO REINFORCED FILL ZONE (TYP) RETAINED SOIL 10" THICK LAYER OF IMPERVIOUS CLAY MATERIAL COMPACTED TO 95% STANDARD PROCTOR 1'-0"LEVELINGPADWALL HEIGHT (H) VARIES4'-6"2'-0"MIN.6" PERFERATED PVC UNDERDRAIN WRAPPED IN FILTER FABRIC, SEE DET. 'E' COMPACTED 12" CRUSHED STONE AGG. LEVELING PAD LENGTH OF GEOGRID (L) (TYP) FREE DRAINING GRANULAR BACKFILL, (SEE NOTE 'F') FILL CORES W/ FREE DRAINING GRANULAR BACKFILL AS EACH COARSE IS SET 1'-0" MIN FOUNDATION SOIL - SANDSTONE OR SHALE 6 MIN1 START GEOGRID AT FRONT OF BLOCK NON-WOVEN GEOTEXTILE FABRIC, COVER LAP GEOGRID 12" MIN. (TYP) 1'-0" 3'-0"6"1'-0" VERTI-BLOCK 36" STANDARD BLOCK (TYP) TOP OF WALL WALL STATION CONTROL LINE 6" CAP BLOCK CONC. FLUME, SEE DET. 'H' 4'-0" MIN (TYP) 4" TOPSOIL & HYDROMULCH SAFETY RAIL NOT SHOWN (SEE DETAIL BELOW)3'-10"4'-2" MIN.5"2"1" X 3" TUBULAR STEEL RAIL 3" X 3" TUBULAR STEEL POST; WITH FLAT CAP; POSTS AT 8'-0" O.C. MAX 1" X 1" TUBULAR STEEL PICKETS; 5" O.C. TYPICAL 1" X 3" TUBULAR STEEL RAIL TOP OF MODULAR BLOCK WALL (SEE RAIL CONNECTION DETAIL 'D') NOTES: 1.FENCE PANELS SHALL NOT SLOPE WITH TOPOGRAPHY. STEP PANELS AT POSTS SET INTERMEDIATE POSTS AS NEEDED. MAX. GROUND CLEARANCE IS 8" AT STEP. 2.ALL WELDS SHALL BE GRINDED SMOOTH BEFORE FINISH. 3.ALL FENCE COMPONENTS SHALL HAVE A HOT DIPPED GALVANIZED FINISH PRIOR TO INSTALLATION. 4.ALL FENCE COMPONENTS SHALL BE 12 GA. STEEL. C SAFETY RAIL FENCE NOT TO SCALE D RAIL CONNECTION DETAILS NOT TO SCALE4'-0"FREE DRAINING GRANULAR BACKFILL CONCRETE FILL SECOND BLOCK VOID SPACE AT EA. POST CONCRETE FILL TOP BLK CELL AT EA. POST STEEL POST CORE THROUGH CAP BLOCK CONCRETE FILL TOP BLK CELL AND SECOND BLOCK VOID SPACE AT EA. POST (TYP) SQUARE STEEL POST (TYP)8'-0" VERTI-BLOCK 36" STANDARD BLOCK (TYP) VERTI-BLOCK 36" STANDARD BLOCK OR HALF-STEP BLOCK (TYP) VERTI-BLOCK 36" STANDARD BLOCK OR HALF-STEP BLOCK (TYP) SECTION PLAN B TYPICAL MODULAR BLOCK WALL SECTION Scale: 1/2" = 1'-0" SETBACK =2 3/16" (5° BATTER)EXPOSED WALL (HEIGHT VARIES)REINFORCED SOIL (SELECT GRANULAR BACKFILL, SEE NOTE 'F') STRATAGRID SG500 GEOGRID SHALL HAVE FRICTION CONNECTION WITH BLOCKS AND SHALL EXTEND FULL LENGTH BACK INTO REINFORCED FILL ZONE (TYP) RETAINED SOIL 10" THICK LAYER OF IMPERVIOUS CLAY MATERIAL COMPACTED TO 95% STANDARD PROCTOR 1'-0"LEVELINGPADWALL HEIGHT (H) VARIES4'-6"2'-0"MIN.6" PERFERATED PVC UNDERDRAIN WRAPPED IN FILTER FABRIC, SEE DET. 'E' COMPACTED 12" CRUSHED STONE AGG. LEVELING PAD LENGTH OF GEOGRID (L) (TYP) FREE DRAINING GRANULAR BACKFILL, (SEE NOTE 'F') FILL CORES W/ FREE DRAINING GRANULAR BACKFILL AS EACH COARSE IS SET 1'-0" MIN FOUNDATION SOIL - SANDSTONE OR SHALE 6 MIN1 START GEOGRID AT FRONT OF BLOCK NON-WOVEN GEOTEXTILE FABRIC, COVER LAP GEOGRID 12" MIN. (TYP) 1'-0" 3'-0"6"1'-0" VERTI-BLOCK 36" STANDARD BLOCK (TYP) WALL STATION CONTROL LINE 6" CAP BLOCK CONC. FLUME, SEE DET. 'H' TOP OF WALL HALF-STEP BLOCK 4" TOPSOIL & HYDROMULCH SAFETY RAIL NOT SHOWN (SEE DETAIL BELOW) 4'-0" MIN (TYP) DME13222City of Denton, Texas Denton Municipal Electric Brinker Substation Gravity Wall Dec 2018revisionno.dateby date scale vert horiz tnp project sheet1517 Centre Place Drive, Suite 320 Denton, Texas 76205 940.383.4177 ph 940.383.8026 fx TBPE Registration No. F-230 www.tnpinc.com teague nall & perkins N/A N/A 10 Modular Block Wall Details GENERAL STRUCTURAL NOTES: GEOGRID REINFORCEMENT SCHEDULE (VERTI-BLOCK) WALL STATION RANGES MAX. WALL HT. 'H' LENGTH OF GEOGRID 'L' MIN. GEOGRID LAYERS 1+96 TO 3+28 8+76 TO 9+22 6'-0"6'-6"2 3+28 TO 4+82 7+80 TO 8+76 12'-0"10'-6"5 4+82 TO 6+02 6+24 TO 6+36 7+10 TO 7+80 18'-0"14'-0"8 6+02 TO 6+24 6+36 TO 7+10 20'-0"15'-6"9 MATERIAL EFFECTIVE FRICTION ANGLE (DEG) EFFECTIVE COHESION MOIST UNIT WEIGHT * RETAINED SOIL 30 0 PSF 119 PCF ** FOUNDATION SOIL 0 1500 PSF 131 PCF REINFORCED FREE DRAINING 34 0 PSF 115 PCF * CLAYEY SAND (SC) A.ALL MODULAR BLOCK GEOGRID REINFORCED RETAINING WALLS SHALL BE VERTI-BLOCK 36" STANDARD BLOCK (24"H X 48"L X 36"D) BY VERTI-CRETE, LLC. OR APPROVED EQUIVALENT. ARCHITECTURAL FINISH SHALL BE COORDINATED WITH OWNER. ACCEPTABLE ALTERNATIVE MODULAR BLOCK WALL SYSTEMS: 1.RECON STANDARD 24" BLOCK (16"H X 48"L X 24"D) 2.REDI-ROCK 28" POSITIVE CONNECTION (PC) SYSTEM BLOCKS (18"H X 46"L X 28"D) B.REFER TO PROJECT GEOTECHNICAL REPORT NO. 13-0278-21 AND REPORT ADDENDUM NO. 1 BY D&S ENGINEERING LABS FOR BORING AND CONSTRUCTION REQUIREMENTS. THE TESTING AGENCY OF RECORD SHALL FIELD VERIFY WALL FOUNDATION SOIL PROPERTIES ARE IN ACCORDANCE WITH DESIGN TABLE 'J' REQUIREMENTS. C.ALLOWABLE BEARING PRESSURE FOR WALL FOUNDATIONS DESIGN SHALL BE 2.0 KSF. D.ALL WALL DESIGNS WILL BE IN CONFORMANCE WITH THE NCMA-09-3RD EDITION PUBLICATION. E.COMPACTION SHALL BE ACCOMPLISHED USING HAND COMPACTION EQUIPMENT AND SHALL BE COMPACTED BETWEEN 90% AND 95% OF STANDARD PROCTOR DENSITY. AVOID HEAVY CONSTRUCTION EQUIPMENT BEHIND WALLS DURING CONSTRUCTION. F.ALL FREE DRAINING GRANULAR WALL BACKFILL MATERIAL SHALL EXTEND TO ONE FOOT BEYOND LIMITS OF GEOGRID AND SHALL BE CRUSHED ROCK, STONE, SAND/GRAVEL MIXTURE, OR SAND/CRUSHED STONE MIXTURE. THE MATERIAL SHALL HAVE LESS THAN 3% PASSING #200 SIEVE AND LESS THAN 30% PASSING #40 SIEVE. THE MINUS #40 SIEVE MATERIAL SHOULD BE NON-PLASTIC. GRANULAR WALL BACKFILL SHOULD NOT BE WATER JETTED DURING INSTALLATION. G.CONTRACTOR SHALL PROVIDE PROFESSIONAL LICENSED ENGINEER SIGNED AND SEALED SHOP DRAWINGS AND DESIGN CALCULATIONS FOR ALTERNATIVE WALL INSTALLATIONS FOR OWNER'S APPROVAL PRIOR TO CONSTRUCTION. CONTRACTOR'S ALTERNATIVE WALL DESIGN SHALL BE IN CONFORMANCE WITH GEOMETRIC CONSTRAINTS PROVIDED ON WALL PLAN LAYOUTS. H.MINIMUM LENGTH OF GEOGRID (L) IS SHOWN ON TYPICAL WALL SECTIONS AND GEOGRID REINFORCEMENT SCHEDULE. I.ALL WALLS SHALL BE DESIGNED FOR THE FOLLOWING CRITERIA: ·FACTOR OF SAFETY IN SLIDING >1.5 ·FACTOR OF SAFETY IN OVERTURNING ≥ 2.0 ·FACTOR OF SAFETY OF EARTH REINF. PULLOUT ≥ 1.5 ·FACTOR OF SAFETY FOR CONNECTION ≥ 1. 5 ·FACTOR OF SAFETY FOR GLOBAL STABILITY ≥1.5 ·FACTOR OF SAFETY FOR BEARING ≥ 2.0 ·FACTOR OF SAFETY FOR SHEAR ≥ 1.5 ·SURCHARGE = 40 PSF ·THE BASE PRESSURE RESULTANT SHALL FALL WITHIN THE MIDDLE THIRD OF THE RETAINING WALL. J.DESIGN OF THE REINFORCED EARTH RETAINING WALLS SHALL BE BASED UPON THE FOLLOWING PARAMETERS: K.NOTIFY ENGINEER IF SANDSTONE OR SHALE IS NOT ENCOUNTERED AT BASE OF WALL PRIOR TO CONSTRUCTION. L.ALL MISCELLANEOUS CONCRETE SHALL MEET THE REQUIREMENTS OF 3000 PSI CONCRETE STRENGTH AT 28 DAYS. M.REINFORCING BARS SHALL BE ASTM A615, GRADE 60. ** SANDSTONE OR SHALE GRANULAR BACKFILL (NOTE F) F TYPICAL WALL ELEVATION & STEP DETAIL NOT TO SCALE FINISHED GRADE 2'-0"CRUSHED STONE LEVELING PAD BOTTOM OF WALL"H" SEE PROFILESMIN.UNDERDRAIN SHALL BE WRAPPED WITH FILTER FABRIC MEETING THE REQUIREMENTS OF TXDOT DMS-620. TYPE I.3"6" DIA. PERFORATED PIPE FILTER MATERIAL SEE NOTE 'F'1'-0"1'-0" 3" OF SOIL FILL IS REQUIRED BETWEEN OVERLAPPING GEOGRID FOR PROPER ANCHORAGE (TYP.) PLACE ADDITIONAL PIECES OF GEOGRID WHEN ANGLE EXCEEDS 20° DRAINAGE FILL20°E UNDERDRAIN DETAIL NOT TO SCALE G FRICTION CONNECTION DETAIL NOT TO SCALE VERTI-BLOCK 36" STANDARD BLOCK (TYP) CUT MESH FOR LIFTING RINGS MESH SHALL LAY FLAT ON TOP OF BLOCK BOTTOM OF WALL 2' STEP I GEOGRID INSTALLATION ON CURVES NOT TO SCALE INSIDE CURVES: BOTTOM ROW MINIMUM RADIUS IS 16'. SETBACK IS 2 3/4" AND EACH ROW WILL INCREASE THE RADIUS BY 2 3/4" MORE THAN THE ROW BELOW IT. OUTSIDE CURVES: TOP ROW MINIMUM RADIUS IS 16'. SETBACK IS 1 5/16" AND EACH ROW WILL INCREASE THE RADIUS BY 1 5/16" MORE THAN THE ROW ABOVE IT. J INDIVUDUAL BLOCK VIEWS NOT TO SCALE 4'- 0 "2'-0"3'-0" STANDARD BLOCK STANDARD HALF-STEP BLOCK 4'- 0 "1'-0"3'-0" 48" 26"6"26" 49"6"2 SIDED CAP 3 SIDED CAP SIDE VIEW CONFLICTING AREA WILL REQUIRE THE USE OF A 13" NUB BLOCKOUT OR SAW CUT AND REMOVAL OF PICK POINT WHEN CAP IS USED K 6" CAP BLOCK DETAIL NOT TO SCALE 4'- 0 "2'-0"2'-0" CORNER BLOCK 1'-0"4'- 0 " 2'-0" HALF-STEP CORNER BLOCK H FLUME DETAIL NOT TO SCALE 3"6"1'-6"6"3" 3 - #3 BARS @ EQ. SPA. 3'-0" #3 BARS @ 18" O.C. 3" CLR (TYP) 1/2" PREFORMED EXPANSION JOINT MATERIAL WITH SEALANT VERTI-BLOCK 36" STANDARD BLOCK OR HALF-STEP BLOCK (TYP) 6" CAP BLOCK FIN. GRADE CONC. INFILL TOP BLOCK CELL FLUSH WITH TOP OF FLUME 6"6"DME13222City of Denton, Texas Denton Municipal Electric Brinker Substation Gravity Wall Dec 2018revisionno.dateby date scale vert horiz tnp project sheet1517 Centre Place Drive, Suite 320 Denton, Texas 76205 940.383.4177 ph 940.383.8026 fx TBPE Registration No. F-230 www.tnpinc.com teague nall & perkins Modular Block Wall Details N/A N/A 11