Loading...
6576C - Construction of Cooper Creek Interceptor I & II, Addendum2 - Additional Info & ModificationADDENDUM NO.2 TO PLANS, SPECIFICATIONS AND CONTRACT DOCUMENTS FOR CITY OF DENTON, TEXAS COOPER CREEK INTERCEPTOR I & II IFB 6576 TO: PROSPECTIVE BIDDERS AND PLAN HOLDERS The Plans, Specifications and Contract Documents shall be modified as required by the following items: Ttam ')-1 PLANS: Multiple Sheets: Additional Information The vent elevations for the vented manholes were left off of the construction plans. The following table specifies the elevation for the manhole vent at each vented manhole: Manhole Plan Set Elevation 13+89.70 Cooper I 578.00 29+75.69 Cooper I 585.00 10+35.09 Cooper II 590.00 21+14.98 Cooper II 592.00 33+93.44 Cooper II 596.00 Item 2-2 PLANS: Sheet 20, Detail U208A: Modification Note 2 of Detail U208A is incorrect. Non -pressurized pipe does not require a longitudinal thrust restraint system. Only vertical restraints through casing spacers are required. All items in conflict with this addendum are hereby deleted. THIS ADDENDUM IS MADE PART OF THE PLANS, SPECIFICATIONS AND CONTRACT DOCUMENTS AND SHALL BE ACKNOWLEDGED ON THE PROPOSAL. City of Denton, Texas Jim Wilder, P.E. Addendum 2 — Page 1 1 JAMES E. WILDER 438 10/i3/n