HomeMy WebLinkAbout2001-447ORDINANCENO AXI-O /
AN ORDINANCE OF THE CITY OF DENTON, TEXAS AMENDING SECTION 28-
27 OF THE CODE OF ORDINANCES TO PROVIDE FOR THE ADOPTION OF THE
2000 INTERNATIONAL BUILDING CODE, 2000 INTERNATIONAL
RESIDENTIAL CODE FOR ONE AND TWO FAMILY DWELLINGS, 2000
INTERNATIONAL FUEL GAS CODE, 2000 INTERNATIONAL PLUMBING CODE,
2000 INTERNATIONAL MECHANICAL CODE, AND THE 2000 INTERNATION
ENERGY CONSERVTION CODE, ALL PUBLISHED BY THE INTERNATIONAL
CODE COUNCIL, PROVIDING FOR AMENDMENTS THERETO, PROVIDING FOR
A PENALTY FOR VIOLATION OF A FINE NOT TO EXCEED $2,000 00,
PROVIDING FOR A SEVERABILITY CLAUSE, REPEALING ALL ORDINANCES
IN CONFLICT THEREWITH, AND PROVIDING FOR AN EFFECTIVE DATE
SECTION 1 That Chapter 28, Section 28-27 of the Code of Ordinances of the
City of Denton is hereby amended so that said section shall hereafter be and read as
follows Adoption of the building code The International Building Code, 2000 Edition,
as published by the International Conference of Building Officials, a copy of which shall
be filed in the Office of the City Secretary and available for public inspection, is hereby
adopted and designated as the building code for other than 1 & 2 family dwellings for the
city, the same as though the edition of such code were copied at length herein subject to
the deletions and amendments enumerated in section 28-28, That Chapter 28, Section 28-
33 of the Code of Ordinances of the City of Denton is hereby added so that said section
shall hereafter be and read as follows Adoption of the residential code The International
Residential Code, 2000 edition as published by the International Code Council, a copy of
which shall be filed in the Office of the City Secretary and available for public
inspection, is hereby adopted and designated as the residential code for the city, the same
as though the edition of such code were copied at length herein subject to the deletions
and amendments enumerated in section 28-34 That Chapter 28, Section 28-123 of the
Code of Ordinances of the City of Denton is hereby added so that said section shall
hereafter be and read as follows Adoption of the fuel gas code The International Fuel
Gas Code, 2000 edition as published by the International Code Council, a copy of which
shall be filed in the Office of the City Secretary and available for public inspection, is
hereby adopted and designated as the fuel gas code for the city, the same as though the
edition of such code were copied at length herein subject to the deletions and
amendments enumerated in section 28-124 That Chapter 28, Section 28-144 of the Code
of Ordinances of the City of Denton is hereby amended so that said section shall hereafter
be and read as follows Adoption of the plumbing code The International Plumbing
Code, 2000 edition as published by the International Code Council, a copy of which shall
be filed in the Office of the City Secretary and available for public inspection, is hereby
adopted and designated as the plumbing code for the city, the same as though the edition
of such code were copied at length herein subject to the deletions and amendments
enumerated in section 28-145 That Chapter 28, Section 28-251 of the Code of
Ordinances of the City of Denton is hereby amended so that said section shall hereafter
be and read as follows Adoption of the mechanical code The International Mechanical
Code, 2000 edition as published by the International Code Council, a copy of which shall
be filed in the Office of the City Secretary and available for public inspection, is hereby
adopted and designated as the mechanical code for the city, the same as though the
edition of such code were copied at length herein subject to the deletions and
amendments enumerated in section 28-252 That Chapter 28, Section 28-253 of the Code
of Ordinances of the City of Denton is hereby added so that said section shall hereafter be
and read as follows The International Energy Conservation Code, 2000 edition as
published by the International Code Council, a copy of which shall be filed in the Office
of the City Secretary and available for public inspection, is hereby adopted and
designated as the energy code for the city, the same as though the edition of such code
were copied at length herein subject to the deletions and amendments enumerated in
section 28-254
Section 28-28 is hereby amended to read as follows
(1) Section 101.4, change to read as follows.
101.4 Referenced codes. The other codes listed in Sections 1014 1 through 1014 7 and
referenced elsewhere in this code, when specifically adopted, shall be considered part of
the requirements of this code to the prescribed extend of each such reference Whenever
amendments have been adopted to the referenced codes and standards, each reference to
said code and standard shall be considered to reference the amendments as well Any
reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as
adopted
(2) Section 109.3 S; delete.
(3) Section 202; add a new definition to read as follows
HIGH-RISE BUILDING is a building having floors used for human occupancy located
more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access
(4) Table 302.3.3, footnote e, change to read as follows
c Assembly uses accessory to Group E Occupancy must comply with the provisions for
Group A Occupancy but for the purpose of Section 302 3 are not considered separate
occupancies
(5) Section 403.1; change to read as follows:
403.1, Applicability. The provisions of this section shall apply to buildings having
occupied floors located more than 55 feet (22 860 16 764 mm) above the lowest level of
fire department vehicle access
(6) Section 403.1, exception #3: change to read as follows:
3 Buildings with an occupancy in Group A-5 in accordance with Section 303 1 when
used for open air seating, however, this exception does not apply to accessory uses
including but not limited to sky boxes, restaurants and similarly enclosed areas
(7) Section 403.2, exception #2, delete.
(8)Section 406.6.1; add a second paragraph to read as follows.
Page 2
This occupancy shall include garages involved in servicing of motor vehicles for items
such as lube changes, inspections, windshield repair or replacement, shocks, minor part
replacement and other such non -major repair When the repair garage is only involved in
such Minor repair, it need not comply with Section 406 6 2
(9) Section 506.2.2; add a sentence to read as follows
In order to be considered as accessible, if not in direct contact with a street or fire lane, a
minimum 10-foot wide pathway from the street or approved fire lane must be provided
(See International Fire Code Section 5031 1 for hose lay measurement pathway
requirements )
(10) Section 705.11; change the exception to read as follows
Exception: For other than hazardous exhaust ducts, penetrations by ducts and air transfer
openings of fire walls that are not on the lot line shall be allowed provided the
penetrations comply with Sections 711 and 715 The size and aggregate width of all
openings shall not exceed the limitations of Section 705 8
(11) Section 715.5.2, add exception #4 to read as follows
4 In the duct penetration of the separation between the private garage and its residence
when constructed in accordance with Section 302 3 3, exceptions #2 and 3
(12) Section 901.3. Amend Amend Building Official to read Fire Marshal or his
representative
(13) Section 901.5• Amend. Amend Building Official to read Fire Marshal or his
representative
(14) Section 9016.3 Amend Amend Building Official to read Fire Marshal or his
representative
(15) Sections 902 — 908 & Section 910 shall conform to the requirements of the 2000
International Fire Code.
(16) Section 1005.2.1, change to read as follows
1005.2.1 Minimum number of exits. Every floor area shall be provided with the
minimum number of approved independent exits as required by Table 1005 2 1 based on
the occupant load, except as modified in Section 1004 2 1 or 1005 2 2 For the purposes
of this chapter, occupied roofs shall be provided with exits as required for floors The
required number of exits from any story, basement or individual space shall be
maintained until arrival at grade or the public way
(17) Section 1101.2; add an exception to read as follows.
Exception: Buildings regulated under State Law and built in accordance with State
certified plans, including any variances or waivers granted by the State, shall be deemed
to be in compliance with the requirements of this Chapter
(18) Section 1108 2.1; change to read as follows
Page 3
1108.2.1 Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an
accessible unisex toilet room shall be provided where an aggregate of six or more male
and or, female water closets are required provided In buildings of mixed occupancy, only
those water closets required for the assembly or mercantile occupancy shall be used to
determine the unisex toilet room requirement In recreational facilities where separate -sex
bathing rooms are provided, an accessible unisex bathing room shall be provided
Fixtures located within unisex toilet and bathing rooms shall be included in determining
the number of fixtures provided in an occupancy
(19) Section 1209 2, exception #2; change to read as follows•
2 Toilet rooms that are not accessible to the public and which have not more than one
water closet, provided that walls around urinals comply with the minimum surrounding
material specified by Section 419 3 of the International Plumbing Code
(20) Section 1403.3; change to read as follows
1403.3 Vapor retarder An approved interior noncorrodible vapor retarder shall be
provided In all framed walls, floors and roof/ceilings comprising elements of the
building thermal envelope, a vapor retarder, when installed, shall be installed in a manner
so as to not trap moisture Vapor retarders shall be tested in accordance with ASTM E 96
(Delete all exceptions)
(21) Table 1505.1; replace footnotes b and c with the following.
b All individual replacement shingles or shakes shall be in compliance with the rating
required by this table
c Non -classified roof coverings shall be permitted on buildings of U occupancies having
not more than 120 sq ft of projected roof area When exceeding 120 sq ft of projected
roof area, buildings of U occupancies may use non -rated non-combustible roof coverings
d Untreated or fire -retardant treated wood shingles or shakes shall be prohibited
Exception The roof covering on existing dwellings and structures with wood shingles or
shakes may be repaired with factory treated fire -retardant wood shingles or shakes or
additions to these structures may be made with factory treated fire- retardant wood
shingles or shakes
(22) Section 1505.7, delete
(23) Add Section 2308 2.3 to read as follows:
2308.2.3 Application to engineered design. When accepted by the code official, any
portion of this section is permitted to apply to buildings that are otherwise outside the
limitations of this section provided that
1 The resulting design will comply with the requirements specified in Chapter 16,
2 The load limitations of various elements of this section are not exceeded, and
3 The portions of this section which will apply are identified by an engineer in the
construction documents
(24) Section 29011; add a sentence to read as follows•
Page 4
The provisions of this Chapter are meant to work in coordination with the provisions of
Chapter 4 of the International Plumbing Code Should any conflicts anse between the
two chapters, the Code Official shall determine which provision applies
(25) Section 29021, change to read as follows
2902.1 Minimum number of fixtures. Plumbing fixtures shall be provided for the type
of occupancy and in the minimum number as follows
1 Assembly Occupancies At least one drinking fountain shall be provided at each floor
level in an approved location
Exception- A drinking fountain need not be provided in a drinking or dining
establishment
2 Groups A, B, F, H, I, M and S Occupancies Buildings or portions thereof where
persons are employed shall be provided with at least one water closet for each sex except
as provided for in Section 2902 2
3 Group E Occupancies Shall be provided with fixtures as shown in Table 2902 1
4 Group R Occupancies Shall be provided with fixtures as shown in Table 2902 1
It is recommended, but not required, that the minimum number of fixtures provided also
comply with the number shown in Table 2902 1 Types of occupancies not shown in
Table 2902 1 shall be considered individually by the building code official The number
of occupants shall be determined by this code Occupancy classification shall be
determined in accordance with Chapter 3
2902 11 Finish material. Finish materials shall comply with Section 1209
2902.2 Unisex toilet and bath fixtures. Fixtures located within unisex toilet and bathing
rooms complying with Chapter 11 is permitted to be included in determining the
minimum required number of fixtures for assembly and mercantile occupancies
Section 28-34. Deletion and Amendments is added to read
The following sections of the residential code adopted by section 28-32 are amended to
read as follows
(1) R102 4 Referenced codes and standards The codes, when specifically adopted, and
standards referenced in this code shall be considered part of the requirements of this code
to the prescribed extent of each such reference Whenever amendments have been
adopted to the referenced codes and standards, each reference to said code and standard
shall be considered to reference the amendments as well Any reference made to NFPA
70 or the ICC Electrical Code shall mean the Electrical Code as adopted Where
differences occur between provisions of this code and referenced codes and standards, the
provisions of this code shall apply
Exception. Where enforcement of a code provision would violate the conditions of the
listing of the equipment or appliance, the conditions of the listing and manufacturer's
instructions shall apply
(2) Section R105.2, item #1 and #2, change as follows
Page 5
I One-story detached accessory structures, provided the floor area does not exceed 120
square feet (18 58 11 15 in 2)
2 Delete
(3) Section R109.1.3; change to read as follows
R109.1.3 Floodplam inspections. For construction permitted in areas prone to flooding
as established by Table R301 2(1), upon placement of the lowest floor, including
basement, and prior to further vertical construction, the building official may shall require
submission of a certification, prepared by a registered professional engineer or land
surveyor, of the lowest floor, including basement, required in Section R327
(4) Section R110 (RI101 through R110 4); delete
(5) Section R112 2.2, delete
(6) Section R202, change definition of "Townhouse" to read as follows
TOWNHOUSE. A single-family dwelling unit constructed in a group of three or more
attached units separated by property Imes in which each unit extends from foundation to
roof and with open space on at least two sides
(7) Table R301.2(1); fill in as follows
Roof Snow Load
Wind
Seismic Design Category
Speed MPH
5lb/ft sq
90 (3-sec-gust) 75 fastest
mile
A
Subi ect to dama e
Winter
Design
Flood
Hazards
Weathering
Frost line
Termite
I
Decay
depth
Temp
Moderate
6"
Very
Slight to
22 degrees
Local code
heavy
moderate
F
(8) SectionR302.1; add a second exception as follows
Exceptions-
1 Tool and storage sheds, playhouses and similar structures exempted from permits by
Section R105 2 are not required to provide wall protection based on location on the lot
Projections beyond the exterior wall shall not extend over the lot line
2 Open metal carport structures may be constructed within zero (0) feet of the property
line without fire -resistive or opening protection when the location of such is approved as
required by other adopted ordinances
(9) Section R303.3, exception, change to read as follows
Exception: The glazed areas shall not be required where artificial light and a mechanical
ventilation system, complying with one of the following, are provided
Page 6
I The minimum ventilation rates shall be 50 cfin (23 6 L/s) for intermittent ventilation or
20 cfin (9 4 L/s) for continuous ventilation Ventilation air from the space shall be
exhausted directly to the outside
2 Bathrooms that contain only a water closet, lavatory or combination thereof may be
ventilated with an approved mechanical recirculating fan or similar device designed to
remove odors from the air
(10) Section R303.6, change to read as follows.
R303.6 Required heating. When the winter design temperature in Table R301 2(1) is
below 60 degrees F(16 degrees Q, every dwelling unit shall be provided with heating
facilities capable of maintaining a minimum room temperature of 68 degrees F (20
degrees Q at a point 3 feet (914 mm) above the floor and 2 feet (610 mm)from exterior
walls in all habitable rooms at the design temperature
(11) Section R314.8, change to read as follows
R314.8 Under stair protection. Enclosed accessible space under stairs shall have walls,
under stair surface and any soffits protected on the enclosed side with 5/8-inch (15 8 mm)
fire -rated (12 7 mm) gypsum board or one -hour fire -resistive construction
(12) Section R321.1; add a second exception to read as follows
Exceptions-
1 (Existing exception unchanged)
2 Two-family dwelling units that are also divided by a property line through the structure
shall be separated as required for townhouses
(13) Section R322.1, change to read as follows•
R32i1 Moisture control. In all framed walls, floors and roof/ceilings comprising
elements of the building thermal envelope, a vapor retarder, when installed, shall be
installed in a manner so as to not trap moisture on the warm-m-winter side of the
insulation
(Delete the exceptions)
(14) Section R327.1; change to read as follows
R327,1 General. All buildings and structures, when permitted to be erected in areas
prone to flooding as identified in Table R301 2(1) and classified as either flood hazard
areas � (including V-Zones), shall be constructed and elevated as required by the
provisions contained in this section or by other local provisions as applicable
(1 S) Section R328, added to read as follows
R328 All Occupancies. An automatic sprinkler system shall be installed throughout all
buildings 7,500 sq ft or larger For the purpose of this provision, fire walls shall not
define separate buildings
(16) Section R703.7 41; add a second paragraph to read as follows
Page 7
For 31/a square feet (0 302 in 2 ) of wall area, the following dimensions shall be adhered
to
1 When ties are placed on studs 16" o c , they shall be spaced no further apart than 29"
vertically starting approximately 15" from the foundation
2 When ties are placed on studs 24" o c , they shall be spaced no further apart than 19"
vertically starting approximately 10" from the foundation
(17) Section R703.7.4.2, add a second paragraph to read as follows:
When using ties that will flex when pushed, spot bedding of cement mortar shall be
installed on all ties
(18) Add Section R902.3 to read as follows
R902.3 Minimum Roof Class. All roof coverings shall be a minimum Class C All
individual replacement shingles or shakes shall be a minimum Class C
Exception: Non -classified roof coverings shall be permitted on buildings of U
occupancies having not more than 120 sq ft of projected roof area When exceeding 120
sq ft of projected roof area, buildings of U occupancies may use non -rated non-
combustible coverings
(19) Section R9071; add a sentence to read as follows
All individual replacement shingles or shakes shall comply with Section R902 3
(20) Section R1005 2, changed to read as follows
R100$.2 Exterior air intake The exterior air intake shall be capable of providing all
combustion air from the exterior of the dwelling or from spaces within the dwelling
ventilated with outside air such as crawl or attic spaces The exterior air intake shall not
be located within the garage or basement of the dwelling nor shall the air intake be
located at an elevation higher than the firebox The exterior air intake shall be covered
with a corrosion -resistant screen of 1/4 —inch mesh
(21) Section N1101.2, amend as follows:
N1101.2.1 Residential Buildings, Type A-1 Compliance shall be demonstrated by
either one of the following
1 Meeting the requirements of this chapter for buildings with a glazing area that does not
exceed 15 percent of the gross area of exterior walls, or
2 Meeting the requirements of this chapter for buildings with a glazing area that is
greater than 15 percent but not exceeding 20 percent of the gross area of exterior walls
and air conditioning equipment rated 12 SEER or higher,
3 Meeting the requirements of this chapter for buildings with a glazing area that is
greater than 20 percent but not exceeding 25 percent of the gross area of exterior walls
and air conditioning equipment rated 14 SEER or higher, or
4 Meeting the requirements of the International Energy Conservation Code for
residential buildings, Type A-1
(22) Add Section N1101.3.4 to read as follows
Page 8
N1101.3.4 Exterior basement or slab insulation When susceptibility to termite damage
is classified as "very heavy" according to Table R301 2(1), designs employing basement
or slab exterior insulation capable of harboring termites shall not be utilized
(23) Section N11021 amend as follows:
N1102.1 Thermal performance criteria The minimum required insulation R-value or
maximum required U-factor for each element in the building thermal envelope
(fenestration, roof/ceiling, opaque wall, floor, slab edge, crawl space wall and basement
wall) shall be in accordance with the criteria in Table N101 4 2 5 of the International
Energy Conservation Code Residential building, Type A-1, with greater than 15-percent
glazing area, residential buildings, Type A-2, with greater than 25-percent glazing area,
and any building in climates with HDD equal to or greater than 13,000, shall determine
compliance using the building envelope requirements of the International Energy
Conservation Code
(24) Replace Table NI1021 with:
TABLE N1102.1
SIMPLIFIED PRESCRIPTIVE BUILDING ENVELOPE THERMAL COMPONENT
CRITERIA MINIMUM REQUIRED THERMAL PERFORMANCE (U-FACTOR AND R-
VALUE)
Maximum MINIMUM INSULATION R-VALUE ((HR-FT SQ)
Glazing DEGREES F/Btu
U-Factor Ceilings Rafter Walls Floors Basement Slab Crawl
(Btu/(hr*ft sq. * open to Assembly Walls Perimeter Space
degrees F)) Attic Walls
Space
65 R-38 R-22 R-13 I R-19 R-0 R-0 R-0
(25) Section N1102.2 amend as follows
N1102.2 Maximum solar heat gam coefficient for fenestration products The area -
weighted -average solar heat gam coefficient (SHGC) for glazed fenestration installed in
climate zones 1 and 2 (to a maximum of with less than 3,500 HDD) shall not exceed
040
(26) Add Section M1304 2 to read as follows•
M1304.2 Minimum burial depth. Underground fuel piping systems shall be installed a
minimum depth of 18 inches (458 mm) below grade
(27) Section M130513, change to read as follows•
M1305.1.3 Appliances in attics. Attics containing appliances requiring access shall be
provided with an opening and a clear and unobstructed passageway large enough to allow
removal of the largest appliance, but not less than 30 inches high and 22 inches wide and
not more than 20 feet in length when measured along the centerline of the passageway
from the opening to the appliance The passageway shall have a continuous solid flooring
in accordance with Chapter 5 not less than 24 inches wide A level service space at least
30 inches deep and 30 inches wide shall be present along all sides of the appliance where
Page 9
access is required The clear access opening dimensions shall be a minimum of 20 inches
by 30 inches (508 mm by 762 mm), or larger where such dimensions are not large
enough to allow removal of the largest appliance As a minimum, access to the attic space
shall be provided by one of the following
1 A permanent stair
2 A pull down stair
3 An access door from an upper floor level
Exception: The passageway and level service space are not required where the appliance
is capable of being serviced and removed through the required opening
(28) Add Section M1305.1 5, M1305 151 to read as follows
M1305.1.5 Water heaters above ground or floor When the mezzanine or platform in
which a water heater is installed is more than eight (8) feet (2438 mm) above the ground
or floor level, it shall be made accessible by a stairway or permanent ladder fastened to
the building
(29) M1305.1.51 Whenever the mezzanine or platform is not adequately lighted or
access to a receptacle outlet is not obtainable from the main level, lighting and a
receptacle outlet shall be provided in accordance with Section M1305 13 1
(30) Section M1305.131, add a sentence to read as follows:
Low voltage wiring of 50 Volts or less shall be installed in a manner to prevent physical
damage
(31) Section M13051.4.1, change to read as follows
M1305.1.4.1 Ground clearance. Appliances supported from the ground shall be level
and firmly supported on a concrete slab or other approved material extending above the
adjoining grade a mimmum of 3 inches (76 mm) Appliances suspended from the floor
shall have a clearance of not less than 6 inches (152 mm) above the ground
(32) Section M1305.1.4.3; add a sentence to read as follows
Low voltage wiring of 50 Volts or less shall be installed in a manner to prevent physical
damage
(33) Section M1307 3. 1, delete.
(34) Section M1501.2; change to read as follows
M1501.2 Exhaust duct size. The minimum diameter of the exhaust duct shall be as
recommended by the manufacturer, and shall be at least the diameter of the appliance
outlet and shall be a mimmum nominal size of 4 inches (102 mm) in diameter The size
of duct shall not be reduced along its developed length nor at the point of termination
(35) Section M1501.3; change to read as follows
M1501.3 Length limitation. The maximum length of a clothes dryer exhaust duct shall
not exceed 25 feet (7620 min) from the dryer location to the wall or roof termination with
not more than two bends When extra bends are installed, the maximum length of the
Page 10
duct shall be reduced 2 5 feet (762 mm) for each 45-degree (0 79 rad) bend and 5 feet
(1524 mm) for each 90-degree (1 6 rad) bend that occur after the first two bends,
measuring in the direction of airflow The maximum length of the exhaust duct does not
include the transition duct
(36)Section M16013.4, item #1; change to read as follows
1 Duct insulation shall conform to the requirements of Table M1601 3 4 and Section
N1101 2 Should there be any conflicts between this section and the energy efficiency
provisions, the energy efficiency provisions shall take precedence A vapor retarder in
accordance with Table M1601 3 4 having a maximum permeance of 0 05 perm [2 87
ng/(s in 2 Pa)] in accordance with ASTM E 96, or aluminum foil having a minimum
thickness of 2 mils (0 051 mm), shall be installed on the exterior of insulation on cooling
supply ducts that pass through nonconditioned spaces conducive to condensation
Insulations having a permeance of 0 05 perms [2 87 ng/(Pa s in 2 )] or less shall not be
required to be covered
Page 11
(37) Add Table M1601.3.4 to read as follows
Duct Location
Insulation Types
Heating
Insulation Types
Mechanically
Zone
Heating only
Cooled
On roof on exterior of building
C,V (2) W
I
A & W
II
B&W
III
C & W
Attics, garages & crawl spaces
A & V (2)
I
A
II
A
III
B
In walls (3), within floor ceiling
A & V (2)
I
A
spaces (3)
II
A
III
B
Within conditioned space or in
None Required
None Required
basements, return ducts in air
plenums
Cement slab or within ground
None Required
None Required
Note: Where ducts are used for both heating and cooling, the minimum insulation shall
be as required for the most restnctive condition
1 Heating Degree Days
Zone I below 4,500 D D
Zone II 4,501 to 8,000 D D
Zone III over 8,000 D D
2 Vapor retarders shall be installed on supply ducts in spaces vented to the outside in
geographic areas where the summer dew point temperature based on the 2 '/2 percent
column of dry-bulb and mean coincident wet -bulb temperature exceeds 60 0 F (15 4 0
C)
3 Insulation may be omitted on that portion of a duct which is located within a wall- or a
floor-peiling space where
3 1 Both sides of the space are exposed to conditioned air
3 2 The space is not ventilated
3 3 The space is not used as a return plenum
3 4 The space is not exposed to unconditioned air Ceilings which form plenums
need not be insulated
INSULATION TYPES 4
A -- A material with an installed conductance of 0 48 [2 72 W/(m*K)] or the equivalent
thermal resistance of 2 1 [0 367 (m*K)/W]
Example of materials capable of meeting the above requirements
I -inch (25 mm), 0 60 lb /cu ft (9 6 kg/m 3 ) mineral fiber, rock, slag or glass
blankets
Page 12
'/Z-inch (13 mm), 15 to 3 lb /cu ft (24 to 48 kg/m 3 ) mineral fiber blanket duct
liner
'/2-inch (13 mm), 3 to 10 lb /cu ft (48 to 160 kg/m 3 ) mineral fiber board
B -- A material with an installed conductance of 0 24 [1 36 W/(m*K)] or the equivalent
thermal resistance of 4 2 [0 735 (m*K)/W]
Example of materials capable of meeting the above requirements
2-inch (51 mm), 0 60 lb /cu ft (9 6 kg/m 3 ) mineral fiber blankets
1-inch (25 mm), 15 to 3 lb /on ft (24 to 48 kg/m 3 ) mineral fiber blanket duct
liner
1-inch (25 mm), 3 to 10 lb /cu ft (48 to 160 kg/m 3 ) mineral fiber board
C -- A material with an installed conductance of 0 16 [0 9 W/(m*K)] or the equivalent
thermal resistance of 6 3 [1 1 (m*K)/W]
Example of materials capable of meeting the above requirements
3-inch (76 mm), 0 60 lb /cu ft (9 6 kg/m 3 ) mineral fiber blankets
1 '/x-inch (38 mm), 15 to 3 lb /cu ft (24 to 48 kg/m 3 ) mineral fiber blanket duct
liner
1 '/z-inch (38 mm), 3 to 10 lb /cu ft (48 to 160 kg/m 3 ) mineral fiber board
V --Vapor Retarders Material with a perm rating not exceeding 0 05 perm [29
ng/Pa*s*m 2 ] All joints to be sealed
W - Approved weatherproof barrier
4 The example of materials listed under each type is not meant to limit other available
thickness and density combinations with the equivalent installed conductance or
resistance based on the insulation only
(38) Section M2005 2, change to read as follows
M2005.2 Prohibited locations. Fuel -fired water heaters shall not be installed in a room
used as a storage closet Water heaters located in a bedroom or bathroom shall be
installed in a sealed enclosure so that combustion air will not be taken from the living
space Access to such enclosure may be from the bedroom or bathroom when through a
solid door, weather-stripped in accordance with the exterior door air leakage
requirements of the International Energy Conservation Code and equipped with an
approved self -closing device Direct -vent water heaters are not required to be installed
within an enclosure
(39) Section G2403, amend definition of "Unvented Room Heater" to add a sentence
to read as follows.
For the purpose of installation, this definition shall also include "Unvented Decorative
Appliances "
(40) Section G2407.15, item #1, change the exception to read as follows.
Exception: Unobstructed stud and joist spaces within dwelling units shall not be
prohibited from conveying combustion air, provided that not more than one required
fireblock is removed
(41) Section G2408.3, delete
Page 13
(42) Section G2411.5, add a second paragraph to read as follows.
Both ends of each section of medium pressure corrugated stainless steel tubing (CSST)
shall identify its operating gas pressure with an approved tag The tags are to be
composed of aluminum or stainless steel and the following wording shall be stamped into
the tag
"WARNING 1/2 to 5 psi gas pressure Do Not Remove"
(43) Section G2412.3; add an exception to read as follows
Exception: Corrugated stainless steel tubing (CSST) shall be a minimum of 1/2"
(44) Section G2414.6, change to read as follows
G2424.6 (404.6) Piping in solid floors. Piping in solid floors shall be laid in channels in
the floor and covered in a manner what will allow access to the piping with a minimum
amount of damage to the building Where such piping is subject to exposure to excessive
moisture or corrosive substances, the piping shall be protected in an approved manner As
an alternative to installation in channels, the piping shall be installed in accordance with
Section G2414 11 (404 11) a casing of schedule 40 steel, wrought iron, PVC or ABS pipe
with tightly sealed ends and joints Both ends of such casing shall extend not less than 2
inches (51 mm) beyond the point where the pipe emerges from the floor
(45) Section G2414 9; change to read as follows.
G2414.9 (404.9) Minimum burial depth Underground piping systems shall be installed
a minimum depth of 12 18 inches (305 458 mm) below grade, except as provided for in
Section G2414 9 1
(46) Section G2414 91, delete
(47) Section G2416 4; add a sentence to read as follows
The equipment used shall be of an appropriate scale such that pressure loss can be easily
determined
(48) Section G2416 41, change to read as follows
G2416 4.1 (406 4 1) Test pressure The test pressure to be used shall be not less than
one and one-half times the proposed maximum working pressure, but not less than 3 10
psig (20 68 9 kPa gauge), or at the discretion of the Code Official, the piping and valves
may be tested at a pressure of at least six (6) inches (152 mm) of mercury, measured with
a manometer or slope gauge irrespective of design pressure Where the test pressure
exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces
a hoop stress in the piping greater than 50 percent of the specified minimum yield
strength of the pipe For welded piping, and for piping carrying gas at pressures in excess
of fourteen (14) inches water column pressure (3 48 kPa), the test pressure shall not be
less than sixty (60) pounds per square inch (413 4 kPa)
(49) Section G2416.4 2; change to read as follows.
G2416 4.2 (406 4.2) Test duration. Test duration shall be held for a length of time
satisfactory to the Code Official, but in no case for less than fifteen (15) minutes For
Page 14
welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches
water column pressure (3 48 kPa), the test duration shall be held for a length of time
satisfactory to the Code Official, but in no case for less than thirty (30) minutes
(50) Add Section G2419.1.4 to read as follows.
G2419.1.4 Valves in CSST installations. Shutoff valves installed with corrugated
stainless steel (CSST) piping systems shall be supported with an approved termination
fitting, or equivalent support, suitable for the size of the valves, of adequate strength and
quality, and located at intervals so as to prevent or damp out excessive vibration but in no
case greater than 12-inches from the center of the valve Supports shall be installed so as
not to interfere with the free expansion and contraction of the system's piping, fittings,
and valves between anchors All valves and supports shall be designed and installed so
they will not be disengaged by movement of the supporting piping
(51) Section G2420.1; add a second paragraph and exception to read as follows:
Access to regulators shall comply with the requirements for access to appliances as
specified in Section M1305
Exception: A passageway or level service space is not required when the regulator is
capable of being serviced and removed through the required attic opening
(52) Section G2437 5, add a sentence to read as follows
The size of duct shall not be reduced along its developed length nor at the point of
termination
(53) Section G2437.5.1; change to read as follows•
G2437.5.1 (613.6.1) Maximum length. The maximum length of a clothes dryer exhaust
duct shall not exceed 25 feet (7620 nun) from the dryer location to the outlet terminal
with not more than two bends When extra bends are installed, the maximum length of
the duct shall be reduced 2 1/2 feet (762 mm) for each 45-degree (0 79 rad) bend and 5
feet (1524 min) for each 90-degree (1 6 rad) bend that occur after the first two bends,
measuring in the direction of airflow (Exception is unchanged)
(54) Section G2443.2, change to read as follows
G2443.2 (620.2) Prohibited use. One or more unvented room heaters shall not be used
as the sole source of comfort heating in a dwelling unit
Exception Existing approved unvented heaters may continue to be used in dwelling
units, in accordance with the code provisions in effect when installed, when approved by
the Code Official unless an unsafe condition is determined to exist as described in
International Fuel Gas Code
Section 108 7
(55) Section G2446.1.1; change to read as follows.
G2446.1.1 (623.1.1) Installation requirements. The requirements for water heaters
relative to access, sizing, relief valves, dram pans and scald protection shall be in
accordance with tlus code access )
Page 15
(56) Section P2503.5.1, item 1, add a second paragraph to read as follows
Shower receptors shall be tested for water tightness by filling with water to the level of
the rough threshold The dram shall be plugged in a manner so that both sides of pans
shall be subjected to the test at the point where it is clamped to the drain
(57) Section P2503.7 2; change to read as follows
P2503.7.2 Testing. Reduced pressure principle backflow preventers, double check
assemblies, double -detector check valve assemblies, and pressure vacuum breaker
assemblies shall be tested at the time of installation, immediately after repairs or
relocation and at regular intervals as required by applicable state or local provisions least
annually
(58) Add Section P2603.6.1 to read as follows.
P2603.6.1 Sewer depth. Building sewers shall be a minimum of 12 inches (304 mm)
below grade
(59) Section P27081, change to read as follows
P2708.1 General. Shower compartments shall have at least 900 square inches of floor
area and be sufficient size to inscribe a circle with a diameter not less than 30 inches
Hinged shower doors shall open outward The wall area above built-in tubs having
installed shower heads and in -shower compartments shall be constructed as per Section
R307 2 R702 4 Such walls shall form a water -tight joint with each other and with either
the tub, receptor or shower floor
(60) Section P2708.1; add a sentence to read as follows
Thresholds shall be of sufficient width to accommodate a minimum twenty-two (22) inch
(559 min) door
(61) Section P2709.1; add an exception to read as follows
Exception: Showers designed to comply with ICC/ANSI A117 1
(62) Section P2710.1, change to read as follows
P2710.1 Finished. Shower walls shall be finished in accordance with Section R307 2
R702 4
(63) Section P2803.6.1; change to read as follows:
P2803.6.1 Requirements for discharge The outlet of a pressure relief valve,
temperature relief valve or combination thereof, shall not be directly connected to the
drainage system The discharge from the relief valve shall be piped full size separately to
the outside of the building or to an indirect waste receptor located inside the building In
areas subject to freezing, the relief valve shall discharge through an air gap into an
indirect waste receptor located within a heated space, or by other approved means The
discharge pipe shall not discharge into the pan required in Section P2801 5 The
discharge shall be installed in a manner that does not cause personal injury or property
damage and that is readily observable by the building occupants The discharge from a
relief valve shall not be trapped The diameter of the discharge piping shall not be less
Page 16
than the diameter of the relief valve outlet The discharge pipe shall be installed so as to
drain by gravity flow and shall terminate atmospherically not more than 6 inches (152
mm) above the floor When discharging outside the building, the point of discharge shall
be with the end of the pipe not more than two (2) feet (610 mm) nor less than six (6)
inches (152 mm) above the ground or the floor level of the area receiving the discharge
and pointing downward The end of the discharge pipe shall not be threaded
(64) Table P2904 4.1; delete "Polybutylene (PB) plastic pipe and tubing".
(65) Sections P2904.5, 2904 5.1 and 290412, delete reference to "PB "plasticpipe
(66) Section P3005.2.6, changed to read as follows
P3005.2.6 Upper terminal Base of stacks Each horizontal drain shall be provided with
a cleanout at its upper terminal Accessible cleanouts shall be provided near the base of
each vertical waste or soil stack Alternatively, such cleanouts may be installed outside
the building within 3 feet (914 mm) of the building wall
Exception: Cleanouts may be omitted on a horizontal drain less that five (5) feet (1524
mm) in length unless such line is serving sinks or urinals
(67) Section P3103.1; changed to read as follows
P3103.1 Roof extension All open vent pipes which extend through a roof shall be
terminated at least six (6) inches (152 mm) above the roof or [number] inches above the
anticipated snow accumulation, except that where a roof is to be used for any purpose
other than weather protection, the vent extensions shall be run at least 7 feet above the
roof
(68) Sections P3105 2 and P3105.3 and Figure P3105 3, delete
(69) Section P3111.1, change to read as follows
P3111.1 Type of fixture A combination waste and vent system shall not serve fixtures
other than floor drains, standpipes, sinks and lavatories indirect waste receptors
Combination dram and vent systems shall not receive the discharge of a food waste
grinder
(70) Section P3111.2; change to read as follows
P3111.2 Installation The only vertical pipe of a combination drain and vent system shall
be the connection between the fixture dram of a sink, lavatory or standpipe, and the
horizontal combination waste and vent pipe The maximum vertical distance shall be 36
inches 8 feet (914 2438 mm)
(71) Section E3301 1; add a sentence to read as follows:
All references to NFPA 70 shall mean the Electrical Code as adopted
(72) Section E3306 3; change to read as follows:
E3306.3 Minimum size of conductors. The minimum size of conductors for feeders
and branch circuits shall be No 14 copper and No 12 aluminum The minimum size of
Page 17
service conductors shall be as specified in Chapter 35 The minimum size of class 2
remote, signaling and power -limited circuits conductors shall be as specified in Chapter
42
(73) Section E3306.6, change to read as follows
E3306.6 Conductors in parallel. Circuit conductors that are electrically joined at each
end to form a single conductor shall be limited to sizes No 1/0 and larger Conductors in
parallel shall be of the same length, same conductor material, same circular mil area and
same insulation Conductors in parallel shall be terminated in the same manner Where
run in separate raceways or cables, the raceway or cable shall have the same physical
characteristics
(74) Section E3802.8; change to read as follows.
E3802.8 Exempt receptacles. Receptacles installed under exceptions to Sections
E3802 2 and E3802 4 E3802 5 shall not be considered as meeting the requirements of
Section E3801 10 E3 8019
Section 28-124. Deletion and Amendments is added to read
(1) Section 102.2; add an exception to read as follows
Exception: Existing dwelling units shall comply with Section 620 2
(2) Section 102.8, change to read as follows.
102.8 Referenced codes and standards The codes and standards referenced herein shall
be those that are listed in Chapter 7 and such codes, when specifically adopted, and
standards shall be considered part of the requirements of this code to the prescribed
extent of each such reference Where differences occur between provisions of this code
and the referenced standards, the provisions of this code shall apply Whenever
amendments have been adopted to the referenced codes and standards, each reference to
said code and standard shall be considered to reference the amendments as well Any
reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as
adopted
(3) Section 202, amend definition of "Unvented Room Heater" to add a sentence to
read as follows•
For the purpose of installation, this definition shall also include "Unvented Decorative
Appliances "
(4) Section 302 3, change to read as follows
302 3 Cutting, notching and boring in wood members. When permitted by the
International Building Code, the cutting, notching and boring of wood members shall
comply with Sections 302 3 1 through 302 3 3
(5) Section 305 4, delete
(6) Add Section 305.5 to read asfollows*
Page 18
305 5 Clearances from grade. Equipment and appliances installed at grade level shall be
supported on a level concrete slab or other approved material extending above adjoining
grade a mimmum of 3 inches (76 mm) or shall be suspended a minimum of 6 inches (152
mm) above adjoining grade
(7) Section 306 3; change to read as follows.
306 3 Appliances in attics. Attics containing appliances requiring access shall be
provided with an opening and unobstructed passageway large enough to allow removal of
the largest appliance The passageway shall not be less than 30 inches high and 22 inches
wide and not more than 20 feet in length measured along the centerline of the
passageway from the opening to the appliance The passageway shall have a continuous
solid flooring not less than 24 inches wide A level service space not less than 30 inches
deep and 30 inches wide shall be present at the front or service side of the equipment
The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508
mm by 762 mm), or larger where such dimensions are not large enough to allow removal
of the largest appliance As a minimum, access to the attic space of residential uses shall
be provided by one of the following
1 A permanent stair
2 A pull down stair
3 An access door from an upper floor level
Exception- The passageway and level service space are not required where the appliance
is capable of being serviced and removed through the required opening
(8) Section 306.3.1; add a sentence to read as follows
Low voltage wiring of 50 Volts or less shall be installed in a manner to prevent physical
damage
(9) Section 306.41, add a sentence to read as follows
Low voltage wiring of 50 Volts or less shall be installed in a manner to prevent physical
damage
(10) Section 306 5, change to read as follows:
306.5 Appliances on roofs or elevated structures Where appliances requiring access
are installed on roofs or elevated structures at a height exceeding 16 feet (4877 mm), such
access shall be provided by a permanent approved means of access the extent of which
shall be from Permanent exterior ladders providing roof access need not extend closer
than 8 feet (2438 mm) to the finish grade or floor level below and shall extend to the
appliance's level service space Such access shall not require climbing over obstructions
greater than 30 inches high or walking on roofs having a slope greater than 4 units
vertical in 12 umts horizontal (33-percent slope)
(11) Add Section 306 5.1.1 to read as follows:
306.5.1.1 Catwalk. On roofs having slopes greater than 4 units vertical in 12 units
horizontal, a catwalk at least 16 inches in width with substantial cleats spaced not more
than 16 inches apart shall be provided from the roof access to the working platform at the
appliance
Page 19
(12) Section 306.5.2; add a sentence to read as follows:
Low voltage wrong of 50 Volts or less shall be installed in a manner to prevent physical
damage
(13) Add Section 306.7 to read as follows.
306 7 Water heaters above ground or floor. When the attic, roof, mezzanine or
platform in which a water heater is installed is more than eight (8) feet (2438 mm) above
the ground or floor level, it shall be made accessible by a stairway or permanent ladder
fastened to the building
306.7.1. Whenever the mezzanine or platform is not adequately lighted or access to a
receptacle outlet is not obtainable from the main level, lighting and a receptacle outlet
shall be provided in accordance with Section 306 3 1
(14) Section 4015, add a second paragraph to read as follows•
Both ends of each section of medium pressure corrugated stainless steel tubing (CSST)
shall identify its operating gas pressure with an approved tag The tags are to be
composed of aluminum or stainless steel and the following wording shall be stamped into
the tag "WARNING 1/2 to 5 psi gas pressure Do Not Remove"
(15) Section 402.3; add an exception to read as follows
Exception. Corrugated stainless steel tubing (CSST) shall be a minimum of 1/2"
(16) Section 404.6, change to read as follows
404.6 iPiping in solid floors. Piping in solid floors shall be laid in channels in the floor
and covered in a manner that will allow access to the piping with a minimum amount of
damage to the building Where such piping is subject to exposure to excessive moisture
or corrosive substances, the piping shall be protected in an approved manner As an
alternative to installation in channels, the piping shall be installed in accordance with
Section 404 11 a casing of schedule 40 steel, wrought iron, PVC or ABS pipe with tightly
sealed ends and joints Both ends of such casing shall extend not less than 2 inches (51
mm) beyond the point where the pipe emerges from the floor
(17) Section 404.9, change to read as follows:
404 9 Minimum burial depth. Underground piping systems shall be installed a
minimum depth of 18 inches (305 458 mm) below grade, except as provided for in
Section 404 9 1
(18) Section 404.9.1; delete
(19) Section 406.4, add a sentence to read as follows
The equipment used shall be of an appropriate scale such that pressure loss can be easily
determined
(20) Section 406.4.1; change to read as follows
Page 20
406.4.1 Test pressure The test pressure to be used shall be not less than 1 1/2 times the
proposed maximum working pressure, but not less than 10 psig (20 68 9 kPa gauge), or at
the discretion of the Code Official, the piping and valves may be tested at a pressure of at
least six (6) inches (152 mm) of mercury, measured with a manometer or slope gauge
irrespective of design pressure Where the test pressure exceeds 125 psig (862 kPa
gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping
greater than 50 percent of the specified minimum yield strength of the pipe For welded
piping and for piping carrying gas at pressures in excess of fourteen (14) inches water
column pressure (3 48 kPa), the test pressure shall not be less than sixty (60) pounds per
square inch (413 4 kPa)
(21) Section 406.4 2, change to read as follows
406 4.2 Test duration. Test duration shall be held for a length of time satisfactory to the
Code Official, but in no case for not less than fifteen (15) minutes For welded piping,
and for piping carrying gas at pressures in excess of fourteen (14) inches water column
pressure (3 48 kPa), the test duration shall be held for a length of time satisfactory to the
Code Official, but in no case for less than thirty (30) minutes 1/2 hour for each 500 cubic
feet (14 in 3 ) of pipe volume or fraction thereof When testing a system having a volume
less than 10 cubic feet (0 28 in 3) or a system in a single-family dwelling, the test
duration shall be permitted to be reduced to 10 minutes For piping systems having a
volume of more than 24,000 cubic feet (680 in 3), the duration of the test shall not be
required to exceed 24 hours
(22) Add Section 409.1.4 to read as follows
409.1.4 Valves in CSST installations Shutoff valves installed with corrugated stainless
steel (CSST) piping systems shall be supported with an approved termination fitting, or
equivalent support, suitable for the size of the valves, of adequate strength and quality,
and located at intervals so as to prevent or damp out excessive vibration but in no case
greater than 12-inches from the center of the valve Supports shall be installed so as not
to interfere with the free expansion and contraction of the system's piping, fittings, and
valves between anchors All valves and supports shall be designed and installed so
movement of the supporting piping will not disengage them
(23) Section 410.1, add a second paragraph and exception to read as follows:
Access to regulators shall comply with the requirements for access to appliances as
specified in Section 306
Exception. A passageway or level service space is not required when the regulator is
capable of being serviced and removed through the required attic opening
(24) Section 613 6, add a sentence to read as follows
The size of duct shall not be reduced along its developed length or at the point of
termination
(25) Section 613.61; change to read as follows
613.6.1 Maximum length The maximum length of a clothes dryer exhaust duct shall not
exceed 25 feet (7620 mm) from the dryer location to the outlet terminal with not more
Page 21
than two bends When extra bends are installed, the maximum length of the duct shall be
reduced 2 5 feet (762 mm) for each 45-degree (0 79 rad) bend and 5 feet (1524 mm) for
each 90-degree (1 6 rad) bend that occur after the first two bends, measuring in the
direction of airflow
(Exception is unchanged)
(26) Section 620.2, change to read as follows
620 2 Prohibited use. One or more unvented room heaters shall not be used as the sole
source of comfort heating in a dwelling unit
Exception. Existing approved unvented heaters may continue to be used in dwelling
units, in accordance with the code provisions in effect when installed, when approved by
the Code Official unless an unsafe condition is determined to exist as described in
Section 108 7
(27) Section 623.11; change to read as follows
623.1.1 Installation requirements. The requirements for water heaters relative to access,
sizing, relief valves, drain pans and scald protection shall be in accordance with the
International Plumbing Code
Section 28-145 Deletions and amendments is amended to read
(1) Section 102.8, change to read as follows.
102.8'Referenced codes and standards The codes and standards referenced in this code
shall be those that are listed in Chapter 13 and such codes, when specifically adopted, and
standards shall be considered part of the requirements of this code to the prescribed
extent of each such reference Where the requirements of reference standards or
manufacturer's installation instructions do not conform to minimum provisions of this
code, the provisions of this code shall apply Whenever amendments have been adopted
to the referenced codes and standards, each reference to said code and standard shall be
considered to reference the amendments as well Any reference to NFPA 70 or the ICC
Electrical Code shall mean the Electrical Code as adopted
(2) Section 305.6.1; change to read as follows.
305.6.1 Sewer depth Building sewers that connect to private sewage disposal system
shall be a minimum of [number] inches (mm) below finished grade at the point of septic
tank connection Building sewers shall be a minimum of 12 inches (304 mm) below
grade disposal because a private sewage disposal code is not typically adopted in this
region )
(3) Section 305 9, change to read as follows*
305.9 Protection of components of plumbing system Components of a plumbing
system installed within 3 feet along alleyways, driveways, parking garages or other
locations in a manner in which they would be exposed to damage shall be recessed into
the wall or otherwise protected in an approved manner
(4) Section 310 4, delete
Page 22
(5) Sections HZ91 and 312 9 2; change to read as follows
312 9.1 Inspections. Annual inspections shall be made of all backflow prevention
assemblies and air gaps to determine whether they are operable In the absence of local
provisions, the owner is responsible to ensure that testing is performed
312.9.2 Testing. Reduced pressure principle backflow preventer assemblies, double
check -valve assemblies, double -detector check valve assemblies and pressure vacuum
breaker assemblies shall be tested at the time of installation, immediately after repairs or
relocation and at least annually The testing procedure shall be performed in accordance
with applicable local provisions In the absence of local provisions, the owner is
responsible to ensure that testing is done in accordance with one of the following
standards
ASSE 5010-1013-1, Sections 1 and 2
ASSE 5010-1015-1, Sections I and 2
ASSE 5010-1015-2
ASSE 5010-1015-3, Sections 1 and 2
ASSE 5010-1015-4, Sections I and 2
ASSE 5010-1020-1, Sections 1 and 2
ASSE 5010-1047-1, Sections 1,2,3 &4
ASSE 5010-1048-1, Sections 1,2,3 &4
ASSE 5010-1048-2
ASSE 5010-1047-3, Sections 1,2,3 &4
ASSE 5010-1047-4, Sections 1,2,3 &4
CAN/CSA B6410
(6) Section 314.21, modify second sentence to read as follows
314.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be
conveyed from the dram pan outlet to an approved place of disposal Condensate shall
not discharge in a publicly exposed area such as into a street, alley, sidewalk or other
areas so as to cause a nuisance
(7) Section 314.2.2; add a second paragraph to read as follows:
Condensate waste pipes from air-cooling coils may be sized in accordance with
equipment capacity as follows
Equipment Capacity in tons of
refrigeration
Minimum Condensate Pipe
Inside Diameter
Up to 20 tons
3/4 inch
Over 20 to 40 tons
1 inch
Over 40 to 90 tons
1 1/4 inch
Over 90 to 125 tons
1 '/2 inch
Over 125 to 250 tons
2 inch
The size of condensate waste pipes may be for one unit or a combination of units, or as
Page 23
recommended by the manufacturer The capacity of waste pipes assumes a 1/8-inch-per-
foot slope, with the pipe running three-quarters full
(8) Section 314.2.3; add item #4 to read as follows
4 Discharge, as noted, shall be to a conspicuous point of disposal to alert occupants in
the event of a stoppage of the drain However, the conspicuous point shall not create a
hazard such as dripping over a walking surface or other areas so as to create a nuisance
(9) Section 4011; add a sentence to read as follows•
The provisions of this Chapter are meant to work in coordination with the provisions of
the Building Code Should any conflicts anse between the two chapters, the Code
Official shall determine which provision applies
(10) Section 403.1; change to read as follows•
403 1 Minimum number of fixtures. Plumbing fixtures shall be provided for the type of
occupancy and in the minimum number as follows
1 Assembly Occupancies At least one drinking fountain shall be provided at each floor
level in an approved location
Exception: A drinking fountain need not be provided in a drinking or dining
establishment
2 Groups A, B, F, H, I, M and S Occupancies Buildings or portions thereof where
persons are employed shall be provided with at least one water closet for each sex except
as provided for in Section 403 2
3 Group E Occupancies Shall be provided with fixtures as shown in Table 403 1
4 Group R Occupancies Shall be provided with fixtures as shown in Table 403 1
It is recommended, but not required, that the minimum number of fixtures provided also
comply with the number shown in Table 403 1 Types of occupancies not shown in Table
403 1 shall be considered Individually by the code official The number of occupants
shall be determined by the International Building Code Occupancy classification shall be
determined in accordance with the International Building Code
(11) Add Section 403.1.2 to read as follows.
403.1.2 Finish material. Finish materials shall comply with Section 1209 of the
International Building Code
(12) Section 404.2, change to read as follows:
404.2 Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an
accessible unisex toilet room shall be provided where an aggregate of six or more male or
female water closets are required provided In buildings of mixed occupancy, only those
water closets required for the assembly or mercantile occupancy shall be used to
determine the unisex toilet room requirement In recreational facilities where separate -sex
bathing rooms are provided, an accessible unisex bathing room shall be provided
(13) Section 405 6, delete
Page 24
(14) Section 409.2; change to read as follows:
409 2 Water connection. The water supply to a commercial dishwashing machine shall
be protected against backflow by an air gap or backflow preventer in accordance with
Section 608
(15) Section 4101, change to read as follows:
410.1 Approval. Drinking fountains shall conform to ASME Al12191, ASME
A112 19 2 or ASME A112 19 9, and water coolers shall conform to ARI 1010 Where
water is served in restaurants or where bottled water coolers are provided in other
occupancies, drinking fountains shall not be required
Exception- A drinking fountain need not be provided in a drinking or dining
establishment
(16) Section 412.4; change to read asfollows,
412 4 Required location Public laundries and central washing facilities. Floor drains
shall be installed in the following areas
1 In public coin -operated laundries and in the central washing facilities of multiple
family dwellings, the rooms containing the automatic clothes washers shall be provided
with floor drains located to readily drain the entire floor area Such drains shall have a
minimum outlet cross section of not less than 3 inches (76 mm) in diameter
2 Commercial kitchens (In lieu of floor drains in commercial kitchens, the code official
may accept floor sinks)
(17) Section 413.4, change to read as follows:
413 4 Water supply required. All food waste grinders shall be provided with a supply
of cold water The water supply shall be protected against backflow by an air gap or with
the installation of a backflow preventer in accordance with Section 608
(18) Section 417.5, change to read as follows.
417.5 Shower floors or receptors. Floor surfaces shall be constructed of impervious,
noncorrosive, nonabsorbent and waterproof materials Thresholds shall be a minimum of
2 inches (51 mm) and a maximum of 9 inches (229 mm), measured from top of the dram
to top of threshold or dam Thresholds shall be of sufficient width to accommodate a
minimum twenty-two (22) inch (559 mm) door
Exception: Showers designed to comply with ICC/ANSI Al 17 1
(19) Section 417.5.2; change to read as follows.
417 5,2 Shower lining Floors under shower compartments, except where prefabricated
receptors have been provided, shall be lined and made water tight utilizing material
complying with Sections 417 5 2 1 through 417 5 2 4 Such liners shall turn up on all
sides at least 2 3 inches (51 mm) above the finished threshold level and shall extend
outward over the threshold and fastened to the outside of the threshold lamb Liners shall
be recessed and fastened to an approved backing so as not to occupy the space required
for wall covering, and shall not be nailed or perforated at any point less than 1 inch above
the finished threshold Liners shall be pitched one -forth unit vertical in 12 units
horizontal (2-percent slope) and shall be sloped towards the fixture drains and be securely
Page 25
fastened to the waste outlet at the seepage entrance, making a water -tight joint between
the liner and the outlet
(20) Add Section 417.7 to read as follows
417 7 Test for shower receptors. Shower receptors shall be tested for water tightness by
filling with water to the level of the rough threshold The dram shall be plugged in a
manner so that both sides of pans shall be subjected to the test at the point where it is
clamped to the drain
(21) Section 419.3; change to read as follows•
419.3 Surrounding material. Wall and floor space to a point 2 feet (610 mm) in front of
a urinal lip and 4 feet (1219 mm) above the floor and at least 2 feet (610 mm) to each side
of the urinal shall be waterproofed with a smooth, readily cleanable, hard, nonabsorbent
material
(22) Section 502.5, change to read as follows•
502.5 Water heaters installed in attics Attics containing a water heater shall be
provided with an opening and unobstructed passageway large enough to allow removal of
the water heater The passageway shall not be less than 30 inches high and 22 inches
wide and not more than 20 feet in length when measured along the centerline of the
passageway from the opening to the water heater The passageway shall have continuous
solid flooring not less than 24 inches wide A level service space at least 30 inches deep
and 30 inches wide shall be present at the front or service side of the water heater The
clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm
by 762 mm), or larger where such dimensions are not large enough to allow removal of
the water heater
(23) Add Section 502.51 to read as follows:
502.5.1 Electrical requirements. A lighting fixture controlled by a switch located at the
required passageway opening and a receptacle outlet shall be provided at or near the
equipment location in accordance with the electrical code
(24) Add Section 502 7 to read as follows
502.7 Water heaters above ground or floor When the attic, roof, mezzanine or
platform in which a water heater is installed is more than eight (8) feet (2438 mm) above
the ground or floor level, it shall be made accessible by a stairway or permanent ladder
fastened to the building
502 7.1 Whenever the mezzanine or platform is not adequately lighted or access to a
receptacle outlet is not obtainable from the main level, lighting and a receptacle outlet
shall be provided in accordance with Section 502 5 1
(25) Section 504.6.1, change to read as follows
504.6, 1 Discharge. The relief valve shall discharge through full size piping to a safe
place of disposal such as the floor drain, outside the building, or an indirect waste
receptor The discharge pipe shall not have any trapped sections When the drain pipe run
is exposed, in an area outside of the room where the water heater is located, in a manner
that would make it subject to damage, the dram and shall have a visible air gap or air gap
Page 26
fitting located in the same room as the water heater The discharge shall be installed in a
manner that does not cause personal injury to occupants in the immediate area or
structural damage to the building The end of the discharge pipe shall not be threaded
The discharge pipe shall not discharge into the pan required in Section 504 7 When
discharging outside the building, the point of discharge shall be with the end of the pipe
not more than two (2) feet (610 mm) nor less than six (6) inches (152 mm) above the
ground or the floor level of the area receiving the discharge and pointing downward
(26) Section 505.1; change to read as follows:
505.1 Unillred vessel insulation. Unfired hot water storage tanks shall be insulated so
that heat loss is limited as specified in Section 504, International Energy Conservation
Code {Delete remainder of section)
(27) Add Section 506, 506.1 to read as follows
SECTION 506 COMBUSTION AIR AND VENTILATION
506.1. Combustion air and ventilation. Combustion air and ventilation for fuel burning
water heaters, other than gas -fired, shall be in accordance with the International
Mechanical Code Combustion air and ventilation for gas -fired water heaters shall be in
accordance with the International Fuel Gas Code
(28) Add Section 604 41 to read asfollows*
604 4.1 State maximum flow rate. Where the State mandated maximum flow rate is
more restrictive than those of this section, the State flow rate shall take precedence
(29) Tables 605.4 and 605 5, delete "Polybutylene (PB) plastic pipe and tubing"
(30) Section 606.1; delete items #4, 5 and 6
(31) Section 606.2; items #1 and 2 changes to read as follows
1 On the fixture supply to each plumbing fixture in other than one- and two-family and
multiple family residential occupancies, and other than in individual guestrooms that are
provided with unit shutoff valves in hotels, motels, boarding houses and similar
occupancies
Exception: Tub and shower valves
2 On the water supply pipe to each sillcock when subject to freezing
(Reason To provide shut-off valves to every fixture)
(32) Section 6072.1; change to read as follows
607.2.1 Piping insulation. Piping in required return circulation systems shall be insulated
as required in Section 504, International Energy Conservation Code (Delete remainder
of section)
(33) Section 608.1; change to read as follows•
6081 General. A potable water supply system shall be designed, installed and
maintained in such a manner so as to prevent contamination from nonpotable liquids,
solids or gases being introduced into the potable water supply through cross -connections
Page 27
or any other piping connections to the system Back flow preventer applications shall
conform to applicable local regulations, Table 608 1, except and as specifically stated in
Sections 608 2 through 608 16 9
(34) Section 60817, change to read as follows:
608.17 Protection of individual water supplies An individual water supply shall be
located and constructed so as to be safeguarded against contamination in accordance with
applicable local regulations In the absence of other local regulations, installation shall be
in accordance with Sections 608 17 1 through 608 17 8
(35) Section 708.3.4, change to read as follows
708.3 4 Upper terminal Base of stack Each horizontal drain shall be provided with a
cleanout at its upper terminal A cleanout shall be provided at the base of each waste or
soil stack
Exception: Cleanouts may be omitted on a horizontal drain less those five (5) feet (1524
mm) in length unless such line is serving sinks or urinals
(36) Add Section 712.5 to read as follows•
712.5 Dual Pump System All sumps shall be automatically discharged and, when in any
"public use" occupancy where the sump serves more than 10 fixture units, shall be
provided with dual pumps or ejectors arranged to function independently in case of
overload or mechanical failure For storm drainage sumps and pumping systems, see
Section 1113 (Reason To address dual pump system To provide reference for storm
drainage systems )
(37) Section 714, 7141, change to read as follows
SECTION 714 ENGINEERED COMPUTERIZED DRAINAGE DESIGN
714.1 Design of drainage system The sizing requirements for plumbing drainage
systems shall be determined by approved computer program design methods
(38) Section 802.1.1; delete the exception
(39) Section 802.4, add a sentence to read as follows.
No standpipe shall be installed below the ground
(40) Section 904.1; changed to read as follows.
904.1 Roof extension. All open vent pipes that extend through a roof shall be terminated
at least six (6) inches (152 mm) above the roof, except that where a roof is to be used for
any purpose other than weather protection, the vent extensions shall be run at least 7 feet
(2134 mm) above the roof
(41) Section 912.1, change to read as follows.
912.1 Type of fixture. A combination drain and vent system shall not serve fixtures other
than floor drains, standpipes, sinks and lavatories indirect waste receptors Combination
drain and vent systems shall not receive the discharge of a food waste grinder
Page 28
(42) Section 912.2; change to read as follows.
912 2 Installation. The only vertical pipe of a combination drain and vent system shall
be the connection between the fixture dram of a sink, lavatory or standpipe, and the
horizontal combination dram and vent pipe The maximum vertical distance shall be 8
feet (2438 mm)
(43) Section 1002.10, delete
(44) Section 10031, added to read as follows.
Minimum construction standards for food service establishments are required when
1 A new building is constructed and occupied,
2 Prior to the issuance of a certificate of occupancy for an existing building
which has not been previously used as a food service establishment within the
last six (6) months
3 A change to a more restrictive class of food preparation occurs
Heavy Food Preparation shall mean any area in which foods are prepared utilizing a
grill, griddle, deep -fat flyer, commercial type ovens, and/or any similar food preparation
equipment, or any area subject to flooding type of wet cleaning procedures due to the
cutting or processing of meat, poultry, fish or pork Heavy food preparation includes but
is not limited to cafeterias, fast food restaurant, full service restaurants, pizza
preparation, donut preparation Meat and fish markets, (et cetera) A minimum 1,000-
gallon grease interceptor is required for heavy food preparation establishments
Light Food Preparation shall mean any area in which foods are prepared exclusive of
the use of fryers, grills or similar equipment Light food preparation is usually limited to
the preparation of hot dogs, sandwiches, salads or other similar foods and fountain -type
cold drinks Light food preparation includes, but is not limited to, sandwich shops,
limited menu concession stands (et cetera) A minimum 200-gallon grease interceptor is
required for light food preparation establishments
No Food Preparation shall mean any area in which foods are provided prewrapped,
from an approved source, with microwave oven type heating being the maximum
handling involved No food preparation is limited to pre -packaged sandwiches or similar
foods, candies and containerized beverages A grease interceptor is not required for no
food preparation establishments
(45)Section 1106.1, change to read as follows
1106.1 General. The size of the vertical conductors and leader, building storm drains,
building storm sewers, and any horizontal branches of such drains or sewers shall be
based on six (6) inches per hour the 100-year hourly rainfall rate indicated in Figure
1106 1 or on other rainfall rates determined from approved local weather data
(46) Section 1107.3, change to read as follows•
1107.3 Sizing of secondary drains. Secondary (emergency) roof drain system shall be
sized in accordance with Section 1106 based on the rainfall rate for which the primary
Page 29
system is sized in Tablesl106 2, 1106 3 and 1106 6 by two Scuppers shall be sized to
prevent the depth of pondmg water from exceeding that for which the roof was designed
as determined by Section 11017 Scuppers shall not have an opening dimension of less
than 4 inches The flow through the primary system shall not be considered when sizing
the secondary roof drain system
(47) Chapter 12; delete
Section 28-252 Deletions and amendments is amended to read
(1) Section 102.8, change to read as follows
102.8 Referenced codes and standards. The codes and standards referenced herein shall
be those that are listed in Chapter 15 and such codes, when specifically adopted, and
standards shall be considered part of the requirements of this code to the prescribed
extent of each such reference Where differences occur between provisions of this code
and the referenced standards, the provisions of this code shall apply Whenever
amendments have been adopted to the referenced codes and standards, each reference to
said code and standard shall be considered to reference the amendments as well Any
reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as
adopted
(2) Section 302.3; change to read as follows•
302.3 Cutting, notching and boring in wood framing When permitted by the
International Building Code, the cutting, notching and boring of wood framing members
shall comply with Sections 302 3 1 through 302 3 3
(3) Section 304.5, delete
(4) Section 304 8; change to read as follows
304.8 Clearances from grade. Equipment and appliances installed at grade level shall be
supported on a level concrete slab or other approved material extending above adjoining
grade a minimum of 3 inches (76 mm) or shall be suspended a minimum of 6 inches (152
mm) above adjoining grade
(5) Add Section 30411 to read as follows
304.11 Minimum burial depth. Underground fuel piping systems shall be installed a
minimum depth of 18 inches (458 mm) below grade
(6) Section 306.3; change to read as follows.
306 3 Appliances in attics Attics containing appliances requiring access shall be
provided with an opening and unobstructed passageway large enough to allow removal of
the largest component of the appliance The passageway shall not be less than 30 inches
high and 22 inches wide and not more than 20 feet in length when measured along the
centerline of the passageway from the opening to the equipment The passageway shall
have continuous solid floonng not less than 24 inches wide A level service space not less
than 30 inches deep shall be present at the front or service side of the appliance The clear
Page 30
access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by
762 imn), or larger where such dimensions are not large enough to allow removal of the
largest appliance As a minimum, access to the attic space of residential uses shall be
provided by one of the following
1 A permanent stair
2 A pull down stair
3 An access door from an upper floor level
Exception: The passageway and level service space are not required where the appliance
is capable of being serviced and removed through the required opening
(7) Section 306.3.1; add a sentence to read as follows
Low voltage wiring of 50 Volts or less shall be installed in a manner to prevent physical
damage
(8) Section 306.41, add a sentence to read as follows
Low voltage wiring of 50 Volts or less shall be installed in a manner to prevent physical
damage
(9) Section 306.5, change to read as follows
306.5 Equipment and appliances on roofs or elevated structures Where equipment
and appliances requiring access are installed on roofs or elevated structures at a height
exceeding 16 feet (4877 mm), such access shall be provided by a permanent approved
means of access the extent of which shall be from Permanent exterior ladders providing
roof access need not extend closer than 8 feet (2438 mm) to the finish grade or floor level
below and shall extend to the equipment and appliance's level service space Such access
shall not require climbing over obstructions greater than 30 inches high on roofs having a
slope greater than 4 units vertical in 12 units horizontal (33-percent slope) A receptacle
outlet shall be provided at or near the equipment and appliance location in accordance
with the Electrical Code Low voltage wiring of 50 Volts or less shall be installed in a
manner to prevent physical damage
(10) Section 306.6, add a second paragraph to read as follows
A receptacle outlet shall be provided at or near the appliance location in accordance with
the Electrical Code Low voltage wiring of 50 Volts or less shall be installed in a manner
to prevent physical damage
(11) Add Section 306.6.1 to read as follows:
306 6.1 Catwalk. On roofs having slopes greater than 4 units vertical in 12 units
horizontal, a catwalk at least 16 inches in width with substantial cleats spaced not more
than 16 inches apart shall be provided from the roof access to the working platform at the
appliance
(12) Add Section 306.7 to read as follows.
306 7 Water beaters above ground or floor. When the mezzanine or platform in which
a water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor
Page 31
level, it shall be made accessible by a stairway or permanent ladder fastened to the
building
306.7.1 Whenever the mezzanine or platform is not adequately lighted or access to a
receptacle outlet is not obtainable from the main level, lighting and a receptacle outlet
shall bb provided in accordance with Section 306 3 1
(13) Section 3072.1; modify second sentence to read as follows
307.2.1 Condensate disposal Condensate from all cooling coils and evaporators shall be
conveyed from the drain pan outlet to an approved place of disposal Condensate shall
not discharge in a publicly exposed area such as into a street, alley, sidewalk or other
areas so as to cause a nuisance
(14) Section 307.2 2, add a second paragraph to read as follows
Condensate waste pipes from air-cooling coils may be sized in accordance with
equipment capacity as follows
Equipment Capacity
in tong of refrigeration
Minimum Condensate Pipe
Inside Diameter
Up to 20 tons
3/4 inch
Over 0 to 40 tons
1 inch
Over 40 to 90 tons
1 1 /4 inch
Over 90 to 125 tons
1 %2 inch
Over 125 to 250 tons
2 inch
The size of condensate waste pipes may be for one unit or a combination of units, or as
recommended by the manufacturer The capacity of waste pipes assumes a 1/8-inch-per-
foot slope, with the pipe running three-quarters full
(15) Section 307.2.3; add item #4 to read as follows.
4 Discharge, as noted, shall be to a conspicuous point of disposal to alert occupants in
the event of a stoppage of the drain However, the conspicuous point shall not create a
hazard such as dripping over a walking surface or other areas so as to create a nuisance
(16) Section 403 2, add an exception to read as follows
Exception: Where the design professional demonstrates that an engineered ventilation
system is designed in accordance with ASHRAE 62, the minimum required rate of
outdoor air shall be permitted to be as specified in such engineered system design
(17) Section 403.2.1; add an item #4 to read as follows
4 Toilet rooms within private dwellings that contain only a water closet, lavatory or
combination thereof may be ventilated with an approved mechanical recirculating fan or
similar device designed to remove odors from the air
(18) Table 403.3, footnote g. change to read as follows
Page 32
g Transfer air permitted in accordance with Section 403 2 2 Toilet rooms within private
dwellings that contain only a water closet, lavatory or combination thereof may be
ventilated with an approved mechanical recirculating fan or similar device designed to
remove odors from the air
(20) Section 504.6, add a sentence to read as follows
The size of duct shall not be reduced along its developed length or at the point of
termination
(21) Section 504.61, change to read as follows
504 6.1 Maximum length The maximum length of a clothes dryer exhaust duct shall not
exceed 25 feet (7620 mm) from the dryer location to the outlet terminal with not more
than two bends When extra bends are installed, the maximum length of the duct shall be
reduced 2 5 feet (762 mm) for each 45-degree (0 79 rad) bend and 5 feet (1524 mm) for
each 90-degree (1 6 rad) bend that occur after the first two bends, measuring in the
direction of airflow
(Exception is unchanged)
(22) Section 506.3.11; change to read as follows•
506 3.11 Duct enclosure A grease duct serving a Type I hood that penetrates a ceiling,
wall or floor shall be enclosed from the point of penetration to the outlet terminal A duct
shall only penetrate exterior walls at a point where unprotected openings are permitted by
the International Building Code Ducts shall be enclosed in accordance with the
International Building Code requirements for shaft construction The duct enclosure shall
be sealed around the duct at the point of penetration and vented to the outside of the
building through the use of weather -protected openings The enclosure shall be separated
from the duct by a mimmum of 3 inches (152 76 mm) and a maximum of 12 inches (305
mm) and shall serve a single grease exhaust duct system
(Exceptions remain unchanged)
(23) Section 510.7, add a second exception to read as follows
Exceptions
1 (Existing exception unchanged)
2 Ducts where the largest cross -sectional diameter of the duct is less than 10 inches (254
mm)
(24) Section 604.1, change to read as follows:
604 1 General. Duct insulation shall conform to the requirements of Sections 604 2
through 604 1, Table 604 1 and the International Energy Conservation Code Should
there be any conflicts between this section and the energy code, the energy code shall
take precedence
Page 33
(25) Add Table No. 6041 to read as follows
Table 604.1 - Insulation of Ducts
Duct Location
Insulation Types
Heating Zone 1
Insulation
Mechanically
Types
Cooled
Heating Only
On roof on exterior
C, V 2 and W
I
A and W
of building
II
B and W
III
C and W
Attics, garages and
A and V 2
I
A
crawl spaces
II
A
III
B
Within the
None required
None required
conditioned space or
in Basements, return
ducts in air plenums
Cement slab or
None required
None required
within ground
Note. Where ducts are used for both heating and cooling, the minimum insulation shall
be as required for the most restrictive condition
1 Heating Degree Days
Zone I below 4,500 D D
Zone II 4,501 to 8,000 D D
Zone III over 8,000 D D
2 Vapor retarders shall be installed on supply ducts in spaces vented to the outside in
geographic areas where the summer dew point temperature based on the 2 3/2 percent
column of dry-bulb and mean coincident wet -bulb temperature exceeds 60 0 F (15 4 0
C)
3 Insulation may be omitted on that portion of a duct which is located within a wall- or a
floor -ceiling space where
3, Both sides of the space are exposed to conditioned air
3 2 The space is not ventilated
3 3 The space is not used as a return plenum
34 The space is not exposed to unconditioned air
Ceilings, which form plenums, need not be insulated
INSULATION TYPES 4
A -- A material with an installed conductance of 0 48 [2 72 W/(m*K)] or the equivalent
thermal resistance of 2 1 [0 367 (m*K)[W]
Example of materials capable of meeting the above requirements
Page 34
1-inch (25 mm), 0 60 lb /cu ft (9 6 kg/m 3 ) mineral fiber, rock, slag or glass
blankets
'/2-mch (13 mm), 15 to 3 lb /cu ft (24 to 48 kg/m 3 ) mineral fiber blanket duct
liner
Y2-inch (13 min), 3 to 10 lb /cu ft (48 to 160 kg/m 3 ) mineral fiberboard
B -- A� material with an installed conductance of 0 24 [1 36 W/(m*K)] or the equivalent
thermal resistance of 4 2 [0 735 (m*K)/W]
Example of materials capable of meeting the above requirements
2-inch (51 mm), 0 60 lb /cu ft (9 6 kg/m 3 ) mineral fiber blankets
1-inch (25 mm), 15 to 3 lb /cu ft (24 to 48 kg/m 3 ) mineral fiber blanket duct
liner
1-inch (25 mm), 3 to 10 lb /cu ft (48 to 160 kg/m 3 ) mineral fiber board
C -- A material with an installed conductance of 0 16 [0 9 W/(m*K)] or the equivalent
thermal resistance of 6 3 [1 1 (m*K)/W]
Example of materials capable of meeting the above requirements
3-inch (76 mm), 0 60 lb /cu ft (9 6 kg/m 3 ) mineral fiber blankets
1 '/2-mch (38 mm), 15 to 3 lb /cu ft (24 to 48 kg/m 3 ) mineral fiber blanket duct
liner
I '/2-inch (38 mm), 3 to 10 lb /cu ft (48 to 160 kg/m 3 ) mineral fiber board
V --Vapor Retarders Material with a perm rating not exceeding 0 05 perm [29
ng/Pa*s*m 2 ] All joints to be sealed
W - Approved weatherproof barrier
4 The example of materials listed under each type is not meant to limit other available
thickness and density combinations with the equivalent installed conductance or
resistance based on the insulation only
(26) $ecdon 604.11 Vapor retarders. Where ducts used for cooling are externally
insulated, the insulation shall be covered with a vapor retarder in accordance with Table
604 1 having a maximum permeance of 0 05 perm [2 87 ng/(Pa s in 2 )] or aluminum
foil having a minimum thickness of 2 mils (0 051 mm) Insulations having a permeance
of 0 05 perms [2 87 ng/(Pa s in 2 )] or less shall not be required to be covered All
joints and seams shall be sealed to maintain the continuity of the vapor retarder
(27) Section 607.2.2; change to read as follows
607.23 Hazardous exhaust ducts. Hazardous exhaust duct systems shall extend directly
to the exterior of the building and shall not extend into or through ducts and plenums
Penetfation of structural elements shall conform to this section and the International
Building Code except that fire dampers are not required at penetration of fire -resistance -
rated assemblies for hazardous exhaust duct system shall comply with Section 510
(28) $ecdon 607.5.1, change to read as follows:
607.5.1 Fire Walls. Ducts and transfer openings permitted in firewalls in accordance
with Section 705 11 of the International Building Code shall be protected with approved
fire dampers installed in accordance with their listing Hazardous exhaust ducts shall not
penetrate firewalls
Page 35
(29) Section 607.6.1; change to read as follows.
607 61 Through penetrations In occupancies other than Groups I-2 and I-3,
penetrations by an air duct through a fire -resistive -rated floor/ceiling assembly that
connects not more than two stones are permitted without shaft enclosure protection
where a fire damper is installed at the floor line
(30) Chapter 14, delete.
Section 28-254 Deletions and amendments is amended to read
(1) Section 101.3; amend as follows.
1013 Compliance. Compliance with this code shall be determined in accordance with
Sections 1013 1, and 1013 2, or 1013 3
(2) Add the following item
101.3.3. Alternative compliance. A building certified through a voluntary energy
performance testing program approved as meeting or exceeding the provisions of this
code may be deemed to comply with the requirements of this code
(3) Section 302.1; Replace blank Table 302.1 Exterior Design Conditions with the
following:
CONDITION
VALUE
Wintef a, design dry bulb o F 99 6%
17
Summer a, desi -bulb o F 0 4%
100
Summer a, design wet -bulb o f 0 4%
78
Degree days heating b
2407
days cooling b
2603
-Degree
Climate zone c
5B
(4) Delete note "a" and replace with the following
a These values are from ASHRAE Handbook of Fundamentals for Dallas/Ft Worth
International Airport 99 6% Winter DB, 0 4% Summer DB, and 0 4% Summer WB, and
from Local Climatological Data for Dallas -Ft Worth published by the National Climatic
Data Center, National Oceanic and Atmospheric Administration These values are for the
purpose of providing a uniform basis of requirements for North Central Texas This will
not preclude licensed professionals from submitting design analyses based on site
measurements or published data more specific to the building site Adjustments shall be
permitted to reflect local climates that differ from the tabulated values, or local weather
experience determined by the code official
(5) Delete Figures 3021 (1-43, 45-51).
(6) Section 502.1.1; delete exception #2 and substitute the following.
2 Buildings located in Climate Zones 1 through 9 as indicated in Table 302 1
Page 36
(7) Section 5021.5, add the following exceptions
Exceptions:
1 Any glazing facing within 45 degrees of true north,
2 Any glazing facing within 45 degrees of true south which is shaded along its full width
by a permanent overhang with a projection factor of 0 3 or greater
3 Any fenestration with attached screens where the screens have a rated shading
coefficient of 6 or less
(8) Section 502.2; Replace blank Table 502 2 Heating & Cooling Criteria with the
following.
Table 502.2 a,g
HEATING AND COOLING CRITERIA
Element
Mode
Type A-1
Type A-2
Residential
Residential
Buildings
Buildings
Uo
Uo
Walls
Heating or cool=
0 15
022
Roof/ceiling
Heating or cooling
003
003
Floors over
Heating or cooling
005
005
unheated spaces
Heated slab on
Heating
R-value = 6
R-value = 6
-grade
Unheated slab on
Heating
R-value = 0
R-value = 0
-grade,
Basement wall
Heating or coolie
U-Factor = 0 15
U-factor = 0 15
Crawls ace wall
Heating or coolie
U-factor = 0 15
1 U-factor = 0 15
(9) Delete Note "a" and replace with the following.
a The above values have been determined for all counties in the North Central Texas
Councyil of Governments region
(10) Add Note "g ":
g These requirements apply only to the boundaries of conditioned space Air
conditioning equipment is recommended, but not required, to be located within the
conditioned space in North Central Texas zones
(11) Delete Figures 502 2(1-6)
(12) Section 502.2; Add note to Fig 502 2(7)
All counties within the North Central Texas Council of Governments region are
designated as within the area of very heavy termite infestation probability for purpose of
uniform interpretation of this requirement
Page 37
(13) Section 502.2 4, Delete prescriptive Tables 502 2 4(1-9) and substitute the
following:
Table $02 2.4(1)
Prescriptive Building Envelope Requirements, Type A-1 Residential Buildings,
Based on Window Area as a Percent of Gross Exterior Wall Area (for zones 5b and
6b)
%
Maximum
Minimum
Glazing
Glazing
U-factor
Ceiling
R-value
Exterior
Wall R-
value
Floor
R-
value
Basement
Wall R-
value
Slab
Perimeter
R-value
and
depth
Crawl
space
wall R-
value
<8%
0 70
R-26
R-11
R-11
R-5
R-0
R-6
<12%
0 65
R-26
R-13
R 11
R-5
R-0
R-5
<15%
0 65
R-30
R-13
R-11
R-6
R-0
R-7
<18%
0 52
R-30
R-13
R-19
R-6
R-0
R-7
<20%
0 50
R-38
R-13
R-19
R-6
R-0
R-7
<25%
0 46
R-38
R-16
R-19
R-6
I R-0
R-7
(14) Replace Tables 502.2 4 (7-9) with: Table 502 2 4(2)
Prescriptive Building Envelope Requirements, Type A-2 Residential Buildings,
Based on Window Area as a Percent of Gross Exterior Wall Area
%
Maximum
Minimum %
Glazing
Glazing
Ceiling
Exterior
Floor
Basement
Slab
Crawl
U-factor
R-value
Wall R-
R-
wall R-
perimeter
space
value
value
value
R-value
wall R-
and
value
depth
<20%
0 55
R-30
R-13
R-11
R-5
R-0
R-6
<250X
055
R-30
R-13
R-11
R-5
R-0
R-5
<30%
047
R-38
R-13
R-19
R-7
R-0
I R-8
(15)Section 503.3.3 3, amend as follows•
All supply and return -air ducts and plenums installed as part of an HVAC air -distribution
system shall be thermally insulated in accordance with Table 503 3 3 3 or where such
ducts or plenums operate at static pressures greater than 2 in w g (500 Pa) in accordance
with Section 503 3 3 4 1
Page 38
(16) Section 503.3.3.4, amend subsections asfollows,
503 3.3.41 High- and medium -pressure duct systems All ducts and plenums operating
at static pressures greater than 2 in w g (500 Pa) shall be insulated and sealed in
accordance with Section 803 2 8 High pressure and medium pressure Ducts operating at
static pressures in excess of 3 in w g (750 Pa) shall be leak tested in accordance with
SMACNA HVAC Air Duct Leakage Test Manual with a rate of air leakage not to exceed
the maximum rate specified in that standard Section 803 3 6 Pressure classifications
specific to the duct system shall be clearly indicated on the construction documents in
accordance with the International Mechanical Code
503 3.3.4 2 Low-pressure duct systems. All longitudinal and transverse ,joints, seams
and connections of low-pressure supply and return ducts operating at static pressures less
than or equal to 2 in w g (500 Pa) shall be securely fastened and sealed with welds
gaskets, mastics (adhesives), mastic -plus -embedded fabric systems or tapes installed in
accordance with the manufacturer's installation instructions Pressure classifications
specific to the duct system shall be clearly indicated on the construction documents in
accordance with the International Mechanical Code
(Exception is unchanged)
(17) Section 802.2, Replace blank tables 802 2 (1-4) with the completed tables
provided on the following four pages. Delete tables 802 2 (5-37)
TABLE 802 2(1)
BUILLDING ENVELOPE REQUIREMENTS
WINDOW AND GLAZED DOOR !+AREA 10 PERCENT OR LESS OF ABOVPE GRADE WALL
AREA
ELEMENT
CONDITIONNALUE Zoness 5B 6B
Sk II hta U•faotor
1
SI b or below fade wall R value
R
0
Windows and glass doors
PF < 0 25
0 25 < PF < 0 50
PF > 0 50
SHGC
U factor
An
An
An
An
An
An
Roof assemblies (R value)
All -wood jolst/truss
Metal joisVtruss
Concrete slab or deck
Metal purlln with thermal block
Metal purlln without thermal block
Insulation between
framin
Continnuous Insulation
R 19
R-16
R 25
R-17
NA
RIB
R 25
R-17
X
R 17
Floors over outdoor air or
unconditioned space (R.value)
All -wood joisVtruss
Metal joist/truss
Concrete slab or deck
Insulation between
framin
Continnuous insulation
R-11
R 6
R-11
R 6
NA
R 6
Above- rade walls(R-value
No framin
Metalframing
Wood framing
Framed
-value cavil
NA
R
11
R-11
value continuous
NA
R-0
R 0
C U > 8 in with Into ral insulation i
value cavit
NA
R 0
R 0
-value continuous
R 0
R O
R-0
Other mason walls
value cavity
NA
R 0
R 0
R-value continuous
R 0
R 0
R-0
Page 39
TABLE 802 2(2)
BUILDING ENVELOPE REQUIREMENTS
WINDOW AND GLAZED DOOR AREA OVER 10 PERCENT BUT NOT GREATER THAN 25
PERCENT OF ABOVE GRADE WALL AREA
ELEMENT
CONDITIONNALUE
Sk II is U'actor
1
Slab or below- tads wall R value
R-0
Wind ws and glass doors
PF < 0 25
025<PF<050
PF > 0 50
SHGC
U factor
06
An
07
An
Any
An
Roof assemblies (R-value)
All wood joist1truss
Metal lolsVtruss
Concrete slab or deck
Metal purlin with thermal block
Metal purlm without thermal blockR-20
Insulation between
framing_.
Continuous
Insulation
R-19
R-20
R 19
R 20
MInsulatlon
Floor$ over outdoor air or
unconditloned space (R value)All woodjoistltruss
Metal jolst/truss
Concrete slab or deck
Continuous
insulation
R-6
R 11
R 6
NA
R-6
Abov • rade walls(R-value)
No framing
Metal framing
Wood framin
Framed
R va ue cavil
NA
R 11
R 11
R va ue continuous
NA
R 0
R-0
CMU > 8 in, with integral insulation
R-va ue cavity
NA
R 11
R 11
R value continuous
11 R 5
R 0
R O
Othermasonry walls
11
R value cavity
NA
R 11
R 11
R value contlnuous
R-5
R O
R-0
Page 40
TABLE 802 2(3)
BUILDING ENVELOPE REQUIREMENTS
WINDOW AND GLAZED DOOR AREA OVER 25 PERCENT BUT NOT GRREATER THAN 40
PERCENT OF ABOVE GRADE WALL AREA
ELEMENT
CONDITIONNALUUE
Skylights U factor
1
Slab or below grade wall R value
R 0
Windows and glass doors
PF<025
0255PF<050
PF>050
SHGC
U factor
04
07
05
07
06
07
Roof assemblies (R-value)
All -wood loistltruss
Metal JolsUtruss
Concrete slab or deck
Metal purlin with thermal block
Metal purlm without thermal block
Insulation between
framin
Contirinuous insulatlon
_
R 25
R 19 _
R 25
R 20
NA
R 19
R 30
R 20
X
R 20
Floors over outdoor air or
unconditioned space (R value)
Alkwood IoisUtruss
Metaljoist/truss
Concrete slab or deck
Insulation between
framin
Continnuous
Insulation
R 11
R 6
R 11
R 6
NA
R 6
Above -grade walls(R-value
No framin
Metal framin
Wood framin
Framed
R value cavity
NA
R 11
R 11
R value continuous
NA
R O
R O
CM > 8 in with into ral Insulation
R value cavIty
NA
R-11
I R-11
R value continuous
R 5
R O
R O
Other mason walls
R value cavit
NA
R 11
R 11
R-value continuous
R 5
R O
R O
Page 41
TABLE 802 2(4)
BOIL DING ENVELOPE REQUIREMENTS
WINDOW AND GLAZED DOOR ARREA OVER 40 PERCENT BUT NOT GRIEATER THAN 50
PERCENT OF ABOVE GRADE WALL AREA
ELEMENT
CONDITIONNALUIE
Sk I "a U factor
1
Slab or below
rade wall R value I
R 0
Windows and glass doors
PF<025
026<PF<050
PF>050
SHGC
U factor
04
07
05
07
06
07
Roo assemblies (R value)
All wood joist/truss
Metal joistltruss
Concrete slab or deck
Metal purlin with thermal block
Metal purlin without thermal block
Insulation between
framing
Contimuous insulation
R 25
R-19
R-25
R 20
NA
R 19
R 30
R 20
R 38
R 20
Floors over outdoor air or
unconditioned space (R value)
All wood joistltruss
Metal joistltruss
Concrete slab or deck
Insulation between
framing
Contimuous insulation
R 11
R-6
R 11
R 6
NA
R 6
Above grade walls R value
No framing
Metal framing
Wood framing
Framed
R-value cavil
NA
R-13
R 11
R value continuous
NA
R 3
R O
CM > 8 in with Integral insulation
R-value caw'
NA NA
R 11
R 11
R value continuous
R 5
R O
R O
Other masonry walls
R value cavity
NA
R 11
R 11
R value continuous
R 5
R O
R-0
(18) Section 805.21 Interior Lighting Controls; add a third sentence to read.
Large ispaces shall have a separate switch or control for each 2500 square feet of floor
area
(19) Chapter 9, Replace referenced standard as follows
ASHRAE/IES -- 93 Energy Code for Commercial and High -Rise Residential Buildings —
Based on ASHRAE/IES 90 1-1989 — with Revisions thru October 7, 1997 including
Errata and Addendum 90 is-1993 ASHRAE/IES -- 99 Energy Efficient Design of New
Buildings Except Low -Rise Residential Building -- 1999 Edition
SECTION 2. That if any provision of this ordinance or the application thereof to
any person or circumstances is held invalid, such invalidity shall not affect other
provisions or applications, and to this end the provisions of this ordinance are severable
SECTION 3. That all provisions of the ordinances of the City of Denton in
conflict with the provisions of this ordinance are hereby repealed, and all other provisions
of the ordinances of the City of Denton, not in conflict with the provisions of this
ordinance, shall remain in full force and effect
Page 42
SECTION 4. That any person violating any provision of this ordinance shall,
upon conviction, be fined a sum not to exceed two thousand dollars ($2000 00) Each day
that a provision of this Ordinance is violated shall constitute a separate and distinct
offense
SECTION 5 That this ordinance shall become effective fourteen (14) days from
the date of its passage, and the City Secretary is hereby directed to cause the caption of
this ordinance to be published twice in the Denton Record Chronicle, the official
newspaper of the City of Denton, Texas,,, within ten (10) days of the date of its passage
PASSED AND APPROVED this the 60 day of �1tgej4 � , 2001
&de'�Aj-
Euline Brock, Mayor
ATTEST
JENNIFER WALTERS, CITY SECRETARY
BY
APPROVED AS TO LEGAL FORM
HERBERT L PROUTY, CITY ATTORNEY
BY/
S \Our Documents\Ordinances\01\2000 Building I CODES doc
Page 43