Loading...
2001-447 ORDINANCE NO ~{~0/- ~t//~ AN ORDINANCE OF THE CITY OF DENTON, TEXAS AMENDING SECTION 28- 27 OF THE CODE OF ORDINANCES TO PROVIDE FOR THE ADOPTION OF THE 2000 INTERNATIONAL BUILDING CODE, 2000 INTERNATIONAL RESIDENTIAL CODE FOR ONE AND TWO FAMILY DWELLINGS, 2000 INTERNATIONAL FUEL GAS CODE, 2000 INTERNATIONAL PLUMBING CODE, 2000 INTERNATIONAL MECHANICAL CODE, AND THE 2000 INTERNATION ENERGY CONSERVTION CODE, ALL PUBLISHED BY THE iNTERNATIONAL CODE COUNCIL, PROVIDING FOR AMENDMENTS THERETO, PROVIDING FOR A PENALTY FOR VIOLATION OF A FINE NOT TO EXCEED $2,00000, PROVIDING FOR A SEVERABILITY CLAUSE, REPEALING ALL ORDINANCES IN CONFLICT THEREWITH, AND PROVIDING FOR AN EFFECTIVE DATE SECTION 1 That Chapter 28, Section 28-27 of the Code of Ordinances of the Caty of Denton m hereby amended so that smd section shall hereafter be and read as follows Adoption of the building code The International Bmld~ng Code, 2000 E&t~on, as pubhshed by the Intemataonal Conference of Bml&ng Officials, a copy of whmh shall be filed m the Office of the C~ty Secretary and available for pubhc anspect~on, as hereby adopted and designated as the building code for other than 1 & 2 family dwelhngs for the caty, the same as though the edltaon of such code were copied at length hereto subject to the deletions and amendments enumerated in sectaon 28-28, That Chapter 28, Sectaon 28- 33 of the Code of Or&nances of the Caty of Denton ~s hereby added so that smd seetaon shall hereafter be and read as follows Adoption of the resldentml code The International Remdenttal Code, 2000 edltaon as pubhshed by the Intematmnal Code Council, a copy of which shall be filed ~n the Office of the Caty Secretary and avmlable for pubhc mspectaon, as hereby adopted and demgnated as the remdentml code for the mty, the same as though the edition of such code were copaed at length here~n subject to the deletaons and amendments enumerated m section 28-34 That Chapter 28, Section 28-123 of the Code of Ordinances of the City of Denton is hereby added so that smd sectaon shall hereafter be and read as follows Adoption of the fuel gas code The Intemataonal Fuel Gas Code, 2000 e&t~on as pubhshed by the International Code Council, a copy of wtuch shall be filed m the Office of the Caty Secretary and avmlable for pubhc inspection, ~s hereby adopted and demgnated as the fuel gas code for the caty, the same as though the edat~on of such code were copaed at length here~n subject to the deletions and amendments enumerated m section 28-124 That Chapter 28, Section 28-144 of the Code of Ordinances of the City of Denton is hereby amended so that smd sectaon shall hereafter be and read as follows Adoption of the plumbing code The Intemataonal Plumbing Code, 2000 edataon as pubhshed by the International Code Council, a copy ofwhmh shall be filed an the Office of the City Secretary and avmlable for pubhc anspectlon, is hereby adopted and demgnated as the plumbing code for the mty, the same as though the e&taon of such code were cop~ed at length herean subject to the deletions and amendments enumerated ~n section 28-145 That Chapter 28, Section 28-251 of the Code of Ordinances of the Caty of Denton is hereby amended so that smd sectaon shall hereafter be and read as follows Adoptaon of the mechanmal code The Intemataonal Mechanmal Code, 2000 e&t~on as pubhshed by the International Code Councd, a copy of which shall be filed in the Office of the Caty Secretary and avmlable for pubhc mspectaon, is hereby adopted and designated as the mechamcal code for the mty, the same as though the edmon of such code were cop~ed at length herein subject to the deletions and amendments enumerated in section 28-252 That Chapter 28, Section 28-253 of the Code of Orchnances of the C~ty of Denton ~s hereby added so that smd section shall hereafter be and read as follows The International Energy Conservation Code, 2000 edition as pubhshed by the Intematmnal Code Council, a copy of which shall be filed ~n the Office of the City Secretary and available for pubhc ~nspectlon, ~s hereby adopted and designated as the energy code for the mty, the same as though the ed~tmn of such code were copied at length herein subject to the deletions and amendments enumerated in section 28-254 Section 28-28 ~s hereby amended to read as follows (1) Seetton 101.4, change to read as follows. 101.4 Referenced codes. The other codes hsted in Sections I01 4 1 through 101 4 7 and referenced elsewhere ~n th~s code, when specifically adopted, shall be considered part of the requirements of this code to the prescribed extend of each such reference Whenever amendments have been adopted to the referenced codes and standards, each reference to smd code and standard shall be considered to reference the amendments as well Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted (2) Section 109.3 5; delete. (3) Section 202; add a new defimtton to read as follows HIGH-RISE BUILDING xs a bmldmg hawng floors used for human occupancy located more than 55 feet (16 764 mm) above the lowest level of fire department vehmle access (4) Table 302.3.3, footnote e, change to read as follows e Assembly uses accessory to Group E Occupancy must comply with the provlmons for Group A Occupancy but for the purpose of Section 302 3 are not considered separate occupancies (5) Section 403.1; change to read as follows: 403.1~ Appheability. The provisions of th~s section shall apply to bmld~ngs having occupied floors located more than 55 feet (22 860 16 764 mm) above the lowest level of fire department vehmle access (6) Section 403.1, exception #3: change to read as follows: 3 Bmldlngs w~th an occupancy in Group A-5 in accordance with Sectmn 303 1 when used for open mr seatmg, however, thas exception does not apply to accessory uses including but not hm~ted to sky boxes, restaurants and similarly enclosed areas (7) Sactton 403.2, exceptton #2, delete. (8)Section 406.6.1; add a second paragraph to read as follows. Page 2 Th~s occupancy shall include garages ~nvolved ~n servm~ng of motor vehicles for ~tems such as lube changes, inspections, w~ndshmld repmr or replacement, shocks, minor part replacement and other such non-major repatr When the repmr garage ~s only ~nvolved ~n such minor repair, it need not comply with Section 406 6 2 (9) Section 506.2.2; add a sentence to read as follows In order to be considered as accessible, ffnot ~n direct contact with a street or fire lane, a mlmmum 10-foot w~de pathway from the street or approved tim lane must be prowded (See Internattonal Ftre Code Section 503 1 1 for hose lay measurement pathway mqmrements ) (I0) Sectton 705.11; change the exceptton to read as follows Exeelffion: For other than hazardous exhaust ducts, penetrations by ducts and mr transfer openings of fire walls that are not on the lot hne shall be allowed prowded the penetrations comply with Sections 711 and 715 The s~ze and aggregate w~dth of all openings shall not exceed the hm~tat~ons of Section 705 8 (11) Section 715.5.2, add exceptton #4 to read as follows 4 In the duct penetration of the separation between the private garage and its residence when constructed in accordance w~th Section 302 3 3, exceptions #2 and 3 (12) Section 901.3. Amend Amend Bmld~ng Officml to read F~re Marshal or h~s representative (13) Section 901.5' Amend. Amend Bmld~ng Offimal to read F~re Marshal or his representative (14) Section 901 6.3 Amend Amend Bmld~ng Offimal to read F~re Marshal or his representative (15) Sections 902 - 908 & Section 910 shall conform to the requtrements of the 2000 International Ftre Code. (16) Section 1005.2.1, change to read as follows 1005.2.1 Minimum number of ex~ts. Every floor area shall be prowded w~th the minimum number of approved independent exits as reqmred by Table 1005 2 1 based on the occupant load, except as modffied m Sectmn 1004 2 1 or 1005 2 2 For the purposes of th~s chapter, occupied roofs shall be prowded w~th ex~ts as reqmred for floors The reqmred number of ex,ts from any story, basement or mthwdual space shall be mmntamed until amval at grade or the pubhc way (17) Section 1101.2; add an exception to read as follows. Exception: Bmld~ngs regulated under State Law and bruit in accordance w~th State certified plans, including any variances or waivers granted by the State, shall be deemed to be m comphanee w~th the reqmrements of th~s Chapter (18) Sectton 1108 2.1; change to read as follows Page 3 1108.2.1 Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an accessible unisex toilet room shall be prowded where an aggregate of six or more male and or, female water closets are reqmred provided In bmldmgs of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the unisex to~let room reqmrement In recreational fatalities where separate-sex batlung rooms are provtded, an accessible umsex bathing room shall be provided F~xtures located within unisex toilet and bathing rooms shall be included m determining the number of fixtures provided in an occupancy (19) Section 1209 2, exceptton #2; change to read as follows' 2 Todet rooms that are not accessible to the pubhc and which have not more than one water closet, provided that walls around unnals comply with the minimum surrounding material specified by Section 419 3 of the Internattona! Plumbing Code (20) Section 1403.3; change to read as follows 1403.3 Vapor retarder An approved interior noncorrod~ble vapor retarder shall be prowded In all framed walls, floors and roof/cethngs comprising elements of the building thermal envelope, a vapor retarder, when installed, shall be installed m a manner so as to not trap mmsture Vapor retarders shall be tested in accordance with ASTM E 96 (Delete all exceptwns ) (21) Table 1505.1; replace footnotes b and c with the following. b All lndavldual replacement stungles or shakes shall be in comphance w~th the rating required by this table c Non-classified roof covenngs shall be permitted on bmldmgs of U occupanmes having not more than 120 sq ft of proJected roof area When exceeding 120 sq ft of projected roof area, bmldlngs of U occupancies may use non-rated non-combustible roof coverings d Untreated or flre-retardant treated wood shingles or shakes shall be prohibited Excel~t~on The roof covenng on existing dwelhngs and structures w~th wood shingles or shakes may be repmred w~th factory treated fire-retardant wood shingles or shakes or additions to these structures may be made w~th factory treated fire- retardant wood shingles or shakes (22) Sectton 1505. 7; delete (23) Add Section 2308 2.3 to read as follows: 2308.2.3 Appheation to engineered design. When accepted by the code officml, any portion of this sectmn is permitted to apply to bmldmgs that are otherwzse outside the hmltatmns of th~s section prowded that 1 The resulting design will comply w~th the requirements specffied in Chapter 16, 2 The load hmxtat~ons of various elements of this section are not exceeded, and 3 The portions of ttus section which w~ll apply are ~dentffied by an engineer m the construction documents (24) Section 2901 1; add a sentence to read as follows' Page 4 The promslons of this Chapter are meant to work ,n coordination w,th the prov,slons of Chapter 4 of the Internatmnal Plumb,ng Code Should any confl,cts arise between the two chapters, the Code Official shall detenmne which provision applies (25) Seetton 2902 1, change to read as follows 2902.1 Minimum number of fixtures. Plumb,ng fixtures shall be provided for the type of occupancy and m the mimmum number as follows 1 Assembly Occupancies At least one dnnkmg fountmn shall be prov,ded at each floor level in an approved location Exception' A dnnklng fountmn need not be provided ,n a drlnk,ng or dining establishment 2 Groups A, B, F, H, I, M and S Occupancies Bmldlngs or portmns thereof where persons are employed shall be provided w,th at least one water closet for each sex except as provided for in Sect,on 2902 2 3 Group E Occupanc,es Shall be provided with fixtures as shown ,n Table 2902 1 4 Group R Occupancies Shall be provided w~th fixtures as shown ,n Table 2902 1 It is recommended, but not mqmred, that the m,mmum number of fixtures prowded also comply with the number shown in Table 2902 1 Types of occupanmes not shown ,n Table 2902 1 shall be considered lnchvldually by the bmld~ng code official The number of occupants shall be determined by th,s code Occupancy classfficatlon shall be determined ~n accordance w~th Chapter 3 2902 1 1 Finish materml. Flmsh matenals shall comply w,th Section 1209 2902.2 Umsex toilet and bath fixtures. Fixtures located w~th~n umsex to,let and bathing rooms complying with Chapter 11 is permitted to be included ~n determ~mng the minimum required number of fixtures for assembly and memantlle occupancies $ectton 28-34. Deletton and Amendments ,s added to read The following sections of the residential code adopted by sect,on 28-32 are amended to read as follows (1) R102 4 Referenced codes and standards The codes, when specffically adopted, and standards referenced m this code shall be cons,tiered part of the reqmrements ofth, s code to thc prescribed extent of each such reference Whenever amendments have been adopted to the referenced codes and standards, each reference to sa,d code and standard shall be considered to reference the amendments as well Arty reference made to NFPA 70 or the ICC Electrtcal Code shall mean the Electrical Code as adopted Where differences occur between provisions of this code and referenced codes and standards, the prov,slons of this code shall apply Exception. Where enforcement of a code prows,on would violate the contht,ons of the hstmg of the equipment or apphance, the cond,tlons of the hstmg and manufacturer's instructions shall apply (2) $ectton R105.2, item gl and #2; change as follows Page 5 1 One-story detached accessory structures, provided the floor area does not exceed 120 square feet (18 58 11 15 m 2) 2 Delete (3) Section R109.1.3; change to read as follows R109.1.3 Floodplam inspections. For construction permitted in areas prone to floodtng as estabhshed by Table R301 2(1), upon placement of the lowest floor, meludmg basement, and prior to further verttcal eonstructton, the building offictal may shall requtre submission of a certification, prepared by a registered professional engineer or land surveyor, of the lowest floor, mcludmg basement, reqmred m Sectton R327 (4) Sectton R1JO (RllO 1 through RllO 4); delete (5) Section Rl12 2.2; delete (6) Sectton R202, change definttton of "Townhouse" to read as follows TOWBIHOUSE. A single-family dwelling unit constructed m a group of three or more attached units separated by property lines m whtch each umt extends from foundation to roof and wtth open space on at least two sides (7) Table R301.2(1); fill tn as follows Roof Snow Load Wind Setsm~c Design Category Speed (MPH) 5 lb/ft sq 90 (3-sec-gust) 75 fastest A mile Subject to damage Wmter Flood Weathenng Frost line Termite Decay Destgn Hazards depth Temp Moderate 6" Very Shght to 22 degrees Local code heavy moderate F (8) SectionR302.1; add a second exceptton as follows Exceptions' 1 Tool and storage sheds, playhouses and s~mflar structures exempted from permits by Section R105 2 are not requtred to provtde wall protectton based on locatton on the lot Project~ons beyond the exterior wall shall not extend over the lot hne 2 Open metal carport structures may be constructed wtthm zero (0) feet of the property line without fire-reslsttve or opanmg protection when the locatton of such ts approved as required by other adopted ordinances (9) Section R303.3, exception; change to read as follows Exception: The glazed areas shall not be requtred where arttficlal light and a mechanical ventilation system, complying with one of the followmg, are provtded Page 6 1 The m~mmum ventilation rates shall be 50 cfm (23 6 L/s) for ~ntermlttent ventilation or 20 cfm (9 4 L/s) for continuous ventilation Ventilation mr from the space shall be exhausted d~rectly to the outside 2 Bathrooms that contmn only a water closet, lavatory or combination thereof may be ventilated with an approved mechanmal remrculatlng fan or similar dewce designed to remove odors from the air (10) Section R$03.6, change to read as follows. 11303.6 Reqmred heating. When the winter design temperature in Table R301 2(1) is below 60 degrees F(16 degrees C), every dwelling unit shall be provided w~th heating famhties capable of mmntam~ng a minimum room temperature of 68 degrees F (20 degrees C) at a point 3 feet (914 mm) above the floor and 2 feet (610 mm)from exterior walls tn all habitable rooms at the design temperature (ID Seetton R314.8; change to read as follows R314.8 Under start protection. Enclosed accessible space under stmrs shall have walls, under stmr surface and any soffits protected on the enclosed side w~th 5/8-tach (15 8 mm) fire-rated (12 7 mm) gypsum board or one-hour fire-res~st~ve construction (12) Section R$21.1; add a second exeeptton to read as follows Exceptions' 1 {Extstzngexcepttonunchanged} 2 Two-family dwelhng umts that are also d~vlded by a property hne through the structure shall be separated as reqmred for townhouses (13) Section R322.1, change to read as follows' R322~1 Mmsture control. In all framed walls, floors and rooffced~ngs comprising elemertts of the bmldmg thermal envelope, a vapor retarder, when installed, shall be installed m a manner so as to not trap moisture on the warm-m-wrater side of the insulation (Delete the excepttons ) (14) 2~ectlon R327.1; change to read as follows R327~1 General. All bmld~ngs and structures, when permitted to be erected ~n areas prone to flooding as ~dentffied m Table R301 2(1) and classified as e~ther flood hazard areas, (mcludmg V-Zones), shall be constructed and elevated as required by the provlsmns contmned m this section or by other local prowslons as apphcable (15) Section R328; added to read as follows R328 All Occupancies. An automatm sprinkler system shall be installed throughout all bmldmgs 7,500 sq ft or larger For the purpose of th~s prowmon, fire walls shall not define separate bmld~ngs (16) Section R703. 7 4 1; add a second paragraph to read as follows Page 7 For 3~,4 square feet (0 302 m 2 ) of wall area, the following dimensions shall be adhered to 1 When ties are placed on studs 16" o c, they shall be spaced no further apart than 29" vertically starting approximately 15" from the foundation 2 When ties are placed on studs 24" o c, they shall be spaced no further apart than 19" vertically starting approximately 10" from the foundation (17) Section R 703. 7.4.2, add a second paragraph to read as follows: When using tles that will flex when pushed, spot bedding of cement mortar shall be installed on all t~es (18) Add Sectton R902.3 to read as follows R902.3 Minimum Roof Class. All roof covermgs shall be a minimum Class C All mdlmdual replacement slungles or shakes shall be a minimum Class C Exception: Non-classffied roof coverings shall be permitted on bmldmgs of U occupancies hawng not more than 120 sq ft of projected roof area When exceedmg 120 sq fi of projected roof area, bmldmgs of U occupancies may use non-rated non- combustible covenngs (19) Sectton R9071; add a sentence to read as follows All individual replacement shmgles or shakes shall comply with Section R902 3 (20) Sectton RlO05 2, changed to read as follows R1005.2 Exterior mr ~ntake The exterior mr intake shall be capable of provldmg all combustion mr from the exterior of the dwelhng or from spaces wtth~n the dwelhng ventilated w~th outside mr such as crawl or attic spaces The exterior mr retake shall not be located w~th~n the garage or basement of the dwelhng nor shall the mr ~ntake be located at an elevation h~gher than the firebox The exterior mr intake shall be covered with a corrosion-res~stant screen of 1/4 -tach mesh (21) Sectton NllO1.2; amend as follows: NIl01.2.1 Residentml Braidings, Type A-1 Comphance shall be demonstrated by e~ther one of the following 1 Meeting the requirements of this chapter for bmldlngs w~th a glazing area that does not exceed 15 percent of the gross area of exterior walls, or 2 Meeting the reqmrements of this chapter for bmld~ngs w~th a glazing area that ~s greater than 15 pement but not exceeding 20 percent of the gross area of exterior walls and air condlt~omng eqmpment rated 12 SEER or h~gher, 3 Meeting the reqmrements of th~s chapter for bmld~ngs with a glazmg area that ~s greater than 20 pement but not exceeding 25 percent of the gross area of exterior walls and air condlt~onmg eqmpment rated 14 SEER or higher, or 4 Meeting the reqmrements of the Internattonal Energy Conservation Code for residential braidings, Type A-1 (22) Add Section Nl101.3.4 to read as follows Page 8 Nl101.3.4 Exterior basement or slab insulation When suscept~blhty to termite damage ts classified as "very heavy" according to Table R301 2(1), dcstgns employing basement or slab exterior msulatmn capable of harbonng termttes shall not be utthzed (23) Section Nl102 1 amend as follows: Nl102.1 Thermal performance cmtena The mmtmum reqmred tnsulatlon R-value or maximum reqmred U-factor for each element tn the bmldmg thermal envelope (fenestration, roof/cellmg, opaque wall, floor, slab edge, crawl space wall and basement wall) shall be tn accordance w~th the criteria m Table N101 4 2 5 of thc Internattonal Energy Conservation Code Res~dential budding, Type A-l, wtth greater than 15-percent glazing area, resldenttal buddtngs, Type A-2, wtth greater than 25-percent glazing area, and any bmldmg tn chmates with HDD equal to or greater than 13,000, shall determtne comphance using the bmldmg envelope reqmrements of the Internattonal Energy Conservatton Code (24) Replace Table Nl102 1 wtth: TABLE Nl102.1 SIMPLIFIED PRESCRIPTIVE BUILDING ENVELOPE THERMAL COMPONENT CRITERIA MINIMUM REQUIRED THERMAL PERFORMANCE (U-FACTOR AND R- VALUE) Maximum MINIMUM INSULATION R-VALUE ((HR-FT SQ ) * Glazmg DEGREES F/Btu) U-Factor Cethngs Rafter Walls Floors Basement Slab Crawl (Btu/(hr*ftsq.* open to Assembly Walls Perimeter Space degrees F)) Attic Walls Space 65 R-38 R-22 R-13 R-19 R-O R-O R-O (25) Section Nl102.2 amend as follows Nl102.2 Maximum solar heat gain coefficient for fenestration products The area- weighted-average solar heat gmn coefficient (SHGC) for glazed fenestration mstalled m climate zones 1 and 2 (to a maximum of w~th less than 3,500 HDD) shall not exceed 0 40 (26) Add Seetion M1304 2 to read as follows' M1304.2 Mmimnm burial depth. Underground fuel p~ptng systems shall be ~nstalled a mtmmum depth of 18 tnches (458 mm) below grade (27) Section M1305 1 3, change to read as follows' M1305.1.3 Appliances in attics. Attics commnmg apphances requmng access shall be provided w~th an opening and a clear and unobstructed passageway large enough to allow removal of the largest apphance, but not less than 30 inches high and 22 tnches w~de and not more than 20 feet tn length when measured along the centerhne of the passageway from the opemng to the apphance The passageway shall have a continuous solid flooring in accordance with Chapter 5 not less than 24 tnches wide A level service space at least 30 tnches deep and 30 tnches wtde shall be present along all stdes of the apphance where Page 9 access is required The clear access opemng dimensions shall be a rmnlmum of 20 mches by 30 inches (508 mm by 762 mm), or larger where such d~mens~ons are not large enough to allow removal of the largest apphance As a m~nlmum, access to the attic space shall he prowded by one of the following 1 A pgrmanent stair 2 A pttll down stair 3 An access door from an upper floor level Exception: The passageway and level service space are not reqmred where the appliance is capable of being serviced and removed through the required opemng (28) Add Sectton M1505.1 5, M1305 1 $1 to read as follows M1305.1.$ Water heaters above ground or floor When the mezzanine or platform in which a water heater is ~nstalled ~s more than eight (8) feet (2438 mm) above the ground or floor level, ~t shall be made accessible by a stairway or permanent ladder fastened to the burldmg (29) M1305.1.5 1 Whenever the mezzanine or platform is not adequately hghted or access to a receptacle outlet is not obtainable from the main level, hghtmg and a receptacle outlet shall be provided ~n accordance w~th Section M1305 1 3 1 (30) Section M1305.1 3 1, add a sentence to read as follows: Low voltage wrong of 50 Volts or less shall be installed in a manner to prevent physical damage 01) Section M1305 1.4.1, change to read as follows M130S.1.4.1 Ground clearance. Appliances supported from the ground shall be level and firmly supported on a concrete slab or other approved material extending above the adjo~mng grade a m~mmum of 3 roches (76 mm) Appliances suspended from the floor shall have a clearance of not less than 6 roches (152 mm) above the ground (32) Section M1305. L4.3; add a sentence to read as follows Low voltage wrong of 50 Volts or less shall be installed m a manner to prevent physical damage (33) Section M1307 3.1, delete. (34) Section M1501.2; change to read as follows M1501.2 Exhaust duct size. The minimum d~ameter of the exhaust duct shall be as recommended by the manufacturer, and shall be at least the d~ameter of the appliance outlet and shall be a mlmmum nominal size of 4 inches (102 mm) in dmmeter The size of duet shall not be reduced along ~ts developed length nor at the poem of termmat~on (35) Section M1501.3; change to read as follows M1501.3 Length hmitation. The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet (7620 mm) from the dryer location to the wall or roof termmat~on with not more than two bends When extra bends are installed, the maximum length of the Page 10 duct shall be reduced 2 5 feet (762 mm) for each 45-degree (0 79 rad) bend and 5 feet (1524 mm) for each 90-degree (1 6 rad) bend that occur after the first two bends, measunng ~n the d~rect~on of mrflow The maximum length of the exhaust duct does not ~nclude the transition duct (36)Sectton M1601 3.4, item gl; change to read as follows 1 Duct insulation shall conform to the reqmrements of Table M1601 3 4 and Section N1101 2 Should there be any conflicts between th~s section and the energy effimency provisions, the energy efficiency provisions shall take precedence A vapor retarder m accordance with Table M1601 3 4 hawng a maximum permeance of 0 05 perm [2 87 ng/(s ra 2 Pa)] m accordance w~th ASTM E 96, or aluminum fo~l having a minimum thmkness of 2 mils (0 051 mm), shall be installed on the exterior of insulation on coohng supply ducts that pass through noncond~tmned spaces conducive to condensation Insulatmns hawng a permeance of 0 05 perms [2 87 ng/(Pa s m 2 )] or less shall not be reqmred to be covered Page 11 (37) Add Table M1601.3.4 to read as follows Duct Location Insulation Types Heating Insulation Types Mechameally Zone Heating only Cooled On roof on exterior of braiding C,V (2) W I A & W II B &W III C & W Attics, garages & crawl spaces A & V (2) I A II A III B In walls (3), w~th~n floor ceiling A & V (2) I A spaces (3) II A III B W~thm conditioned space or in None Reqmred None Reqmred basements, return ducts in mr plenums Cement slab or w~th~n ground None Reqmred None Reqmred Note: Where ducts are used for both heating and cooling, the minimum insulation shall be as required for the most restrictive condition 1 Heating Degree Days Zone I below 4,500 D D Zone II 4,501 to 8,000 D D Zone III over 8,000 D D 2 Vapor retarders shall be installed on supply ducts in spaces vented to the outside in geographm areas where the summer dew pmnt temperature based on the 2 ½ percent column of dry-bulb and mean coincident wet-bulb temperature exceeds 60 0 F (15 4 0 C) 3 Insulation may be omitted on that portion of a duct which is located w~th~n a wall- or a floor-ceiling space where 3 1 Both sides of the space are exposed to conditioned mr 3 2 The space is not ventilated 3 3 The space ~s not used as a retum plenum 3 4 The space is not exposed to unconditioned air Cethngs which form plenums need not be insulated INSULATION TYPES 4 A -- A material wath an ~nstalled conductance of 0 48 [2 72 W/(m*K)] or the equivalent thermal resistance of 2 1 [0 367 (m*K)/W] Example of materials capable of meeting the above reqmrements l-tach (25 mm), 0 60 lb/cu ft (9 6 kg/m 3 ) m~neral fiber, rock, slag or glass blankets Page 12 ½-tach (13 mm), 1 5 to 3 lb/cu ft (24 to 48 kg/m 3 )mtneral fiber blanket duct hner V2qnch (13 mm), 3 to 10 lb/cu ft (48 to 160 kg/m 3 ) mineral fiber board B -- A material wtth an installed conductance of 0 24 [1 36 W/(m*K)] or the equivalent thermal resastance of 4 2 [0 735 (m*K)/W] Example of materials capable of meeting the above reqmrements 2qnch (51 mm), 0 60 lb/cu ft (9 6 kg/m 3 ) m~neral fiber blankets 1-mch (25 mm), 1 5 to 3 lb/cu fl (24 to 48 kg/m 3 )mtneral fiber blanket duct hner l-tach (25 mm), 3 to 10 lb/cu ft (48 to 160 kg/m 3 )mtneral fiber board C -- A matenal with an anstalled conductance of 0 16 [0 9 W/(m*K)] or the eqmvalent thermal resistance of 6 3 [1 1 (m*K)/W] Example ofmatenals capable ofmeetang the above reqmrements 3-tach (76 mm), 0 60 lb/cu ft (9 6 kg/m 3 )mtneral fiber blankets 1 V2-mch (38 mm), 1 5 to 3 lb/cu ft (24 to 48 kg/m 3 ) maneral fiber blanket duct liner 1 ½-1nch (38 mm), 3 to 10 lb/cu ft (48 to 160 kg/m 3 ) mineral fiber board V --Vapor Retarders Material wath a perm rattng not exceeding 0 05 perm [29 ng/Pa*s*m 2 ] All joints to be sealed W - Approved weatherproof bamer 4 The example of matenals lasted under each type is not meant to limit other available thmkness and densaty combtnataons wtth the eqmvalent ~nstalled conductance or resastance based on the ~nsulat~on only (38) Section M2005 2; change to read as follows M2005.2 Prohibited locations. Fuel-fired water heaters shall not be installed in a room used as a storage closet Water heaters located tn a bedroom or bathroom shall be tnstalIed m a sealed enclosure so that combustton mr will not be taken from the hwng space Access to such enclosure may be from the bedroom or bathroom when through a sohd door, weather-stripped in accordance with the exterior door air leakage requirements of the Internattonal Energy Conservaaon Code and eqmpped wtth an approved self-closing devace Direct-vent water heaters are not reqmred to be tnstalled wtthln an enclosure (39) Sectton G2403, amend deflnitton of "Unvented Room Heater" to add a sentence to read as follows. For the purpose of installation, thts defimtlon shall also mclude "Unvented Decorative Apphances" (40) Sectton G2407.15, item #1, change the exceptton to read as follows. Exception: Unobstructed stud and .lmst spaces wtthln dwelhng units shall not be prohabated from eonveytng combustaon atr, provtded that not more than one required fireblock ts removed (41) Section G2408.3, detete Page 13 (42) Sectton G2411.5; add a second paragraph to read as follows. Both ends of each section of medium pressure corrugated stainless steel tubing (CSST) shall ~dentffy ~ts operatmg gas pressure w~th an approved tag The tags are to be composed of aluminum or stamless steel and the following wording shall be stamped ~nto the tag "WARNING 1/2 to 5 ps~ gas pressure Do Not Remove" (43) Section G2412.3; add an exceptton to read as follows Exceptmn: Corrugated stainless steel tubing (CSST) shall be a mm~mum of 1/2" (44) Section G2414.6; change to read as follows G2424.6 (404.6) Piping ~n solid floors. P~pmg m sohd floors shall be la~d ~n channels ~n the floor and covered m a manner what will allow access to the p~p~ng w~th a mm~mum amount of damage to the budding Where such piping ~s subject to exposure to excessive mo~stttre or corrosive substances, the p~pmg shall be protected m an approved manner As an alternative to mstallat~on m channels, the p~pmg shall be ~nstalled ~n accordance w~th Section G2414 11 (404 11) a casmg of schedule 40 steel, wrought ~ron, PVC or AB S p~pe w~th tightly sealed ends and joints Both ends of such casing shall extend not less than 2 mches (51 mm) beyond the point where the p~pe emerges from the floor (45) Section G2414 9; change to read as follows. G2414.9 (404.9) Minimum burml depth Underground p~pmg systems shall be installed a minimum depth of 12 18 ~nches (305 458 mm) below grade, except as prowded for ~n Section G2414 9 1 (46) Section G2414 9 1, delete (47) Sectton G2416 4; add a sentence to read as follows The eqmpment used shall be of an appropriate scale such that pressure loss can be easily determined (48) Section G2416 4 1, change to read as follows G2416 4.1 (406 4 1) Test pressure The test pressure to be used shall be not less than one and one-half t~mes the proposed maximum working pressure, but not less than 3 10 ps~g (20 68 9 kPa gauge), or at the d~scret~on of the Code Official, the p~pmg and valves may be tested at a pressure of at least s~x (6) roches (152 mm) of mercury, measured w~th a manometer or slope gauge ~rrespect~ve of design pressure Where the test pressure exceeds 125 ps~g (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress m the p~pmg greater than 50 percent of the specified minimum y~eld strength of the p~pe For welded p~p~ng, and for plpmg carrying gas at pressures ~n excess of fourteen (14) inches water column pressure (3 48 kPa), the test pressure shall not be less than sixty (60) pounds per square inch (413 4 kPa) (49) Section G2416.4 2; change to read as follows. G2416 4.2 (406 4.2) Test duration. Test duration shall be held for a length of t~me satisfactory to the Code Officml, but m no case for less than fifteen (15) minutes For Page 14 welded piping, and for piping carrying gas at pressures ~n excess of fourteen (14) inches water column pressure (3 48 kPa), the test duration shall be held for a length of time satisfactory to the Code Official, but in no case for less than thirty (30) minutes (50) Add Sectton G2419. L4 to read as follows. G2419.1.4 Valves m CSST installations. Shutoff valves installed with corrugated stmnloss steel (CSST) piping systems shall be supported with an approved termination fitting, or equivalent support, suitable for the size of the valves, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration but in no case greater than 12qnches from the centex of the valve Supports shall be installed so as not to interfere with the free expansion and contraction of the system's piping, fittings, and valves between anchors All valves and supports shall be designed and installed so they will not be disengaged by movement of the supporting piping (5D Section G2420.1; add a second paragraph and exception to read as follows: Access to regulators shall comply with the requirements for access to appliances as specified m Section M1305 Excegtion: A passageway or level service space is not required when the regulator is capable of being serviced and removed through the required attic opening (52) Seetton G2437 5, add a sentence to read as follows The size of duct shall not be reduced along its developed length nor at the point of termination (53) Sectton G243 7. 5.1; change to read as follows' G2437.5.1 (613.6.1) Maximum length. The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet (7620 mm) from the dryer location to the outlet terminal with not more than two bends When extra bends are installed, the maximum length of the duct shall be reduced 2 1/2 feet (762 mm) for each 45-degree (0 79 rad) bend and 5 feet (1524 mm) for each 90-degree (1 6 rad) bend that occur after the first two bends, meastmng in the direction of mrflow {Exceptton ts unchanged} (54) Section G2443.2; change to read as follows G2443.2 (620.2) Prohibited use. One or more unvented room heaters shall not be used as the sole source of comfort heating in a dwelling unit Exceptmn Existing approved unvented heaters may continue to be used in dwelling units, in accordance with the code provisions in effect when installed, when approved by the Code Official unless an unsafe condition is determined to exist as described in International Fuel Gas Code Section 108 7 (55) Section G2446. L1; change to read as follows. G2446.1.1 (623.1.1) Installation requirements. The requirements for water heaters relative to access, sizing, relief valves, drain pans and scald protection shall be in accordance with tins code access ) Page 15 (56) Section P2503.5.1, ttem 1, add a second paragraph to read as follows' Shower receptors shall be tested for water t~ghtness by filhng with water to the level of the rough threshold The drmn shall be plugged ~n a manner so that both s~des of pans shall be subjected to the test at the pmnt where ~t ~s clamped to the drmn (57) Sectton P2503. 7 2; change to read as follows P2503.7.2 Testing. Reduced pressure pnnc~ple backflow preventers, double check assembhes, double-detector check valve assembhes, and pressure vacuum breaker assembhes shall be tested at the t~me of ~nstallat~on, ~mmed~ately after repmrs or relocation and at regular intervals as reqmred by apphcable state or local prows~ons least annually (58) Add Section P2603.6.1 to read as follows. P2603.6.1 Sewer depth. Bmldmg sewers shall be a mtmmum of 12 roches (304 mm) below grade (59) Sectton P2708 1, change to read as follows P2708.1 General. Shower compartments shall have at least 900 square roches of floor area and be suffiment s~ze to ~nscnbe a mrele w~th a dmmeter not less than 30 ~nches H~nged shower doors shall open outward The wall area above bulltqn tubs hawng mstalled shower heads and ~n-shower compartments shall be constructed as per Section R307 2 R702 4 Such walls shall form a water-tight jmnt w~th each other and wath e~ther the tub, receptor or shower floor (60) Sectton P2708.1; add a sentence to read as follows Thresholds shall be of sufficient w~dth to accommodate a m~mmum twenty-two (22) ~nch (559 mm) door (61) Sectton P2709.1; add an exception to read as follows Exception: Showers designed to comply w~th ICC/ANSI A117 1 (62) Section P2710.1, change to read as follows P2710.1 Finished. Shower walls shall be fimshed ~n accordance w~th Sectmn R307 2 R702 4 (63) Section P2803.6.1; change to read as follows: P2803.6.1 Requirements for discharge The outlet of a pressure rehef valve, temperature relief valve or combination thereof, shall not be darectly connected to the drmnage system The d~scharge from the relief valve shall be p~ped full s~ze separately to the outside of the bmld~ng or to an ~ndlrect waste receptor located ~ns~de the bmld~ng In areas subject to freemng, the rehef valve shall d~scharge through an mr gap ~nto an ~nd~rect waste receptor located w~th~n a heated space, or by other approved means The d~scharge p~pe shall not d~scharge ~nto the pan reqmred ~n Section P2801 5 The d~scharge shall be installed ~n a manner that does not cause personal ~njury or property damage and that ~s readily observable by the bmld~ng occupants The d~scharge from a rehef valve shall not be trapped The dmmeter of the &scharge p~p~ng shall not be less Page 16 than the &meter of the relief valve outlet The discharge p~pe shall be mstalled so as to drain by grawty flow and shall terminate atmospherically not more than 6 roches (152 mm) above the floor When d~schargmg outside the building, the point of d~scharge shall be w~th the end of the p~pe not more than two (2) feet (610 mm) nor less than slx (6) ~nches (152 mm) above the ground or the floor level of the area receawng the discharge and pointing downward The end of the discharge pipe shall not be threaded (64) Table P2904 4.1; delete "Polybutylene (PB) plasttc ptpe and tubing". (65) Secttons P2904.5, 2904 5.1 and 2904 12; delete reference to "PB "plasttc pipe (66) Sectton P3005.2.6; changed to read as follows P300fi.2.6 Upper terminal Base of stacks Each horizontal dram shall be provided w~th a cleanont at ~ts upper terminal Accessible cleanouts shall be provided near the base of each vertical waste or soft stack Alternatively, such cleanonts may be installed outside the bmlthng wltlun 3 feet (914 mm) of the building wall Exeegtion: Cleanouts may be omitted on a horizontal drain less that five (5) feet (1524 mm) m length unless such hne as serwng sinks or unnals (67) Section P3103.1; changed to read as follows P3103.1 Roof extension All open vent pipes which extend through a roof shall be terminated at least s~x (6) inches (152 mm) above the roof or [number] roches above the anticipated snow accumulation, except that where a roof is to be used for any purpose other than weather protection, the vent extensions shall be run at least 7 feet above the roof (68) Sections P3105 2 and P3105.3 and Ftgure P3105 3, delete (69) Sectton P31II.1, change to read as follows P3111.1 Type of fixture A combination waste and vent system shall not serve fixtures other than floor drams, standpipes, s~nks and lavatories indirect waste receptors Combination dram and vent systems shall not receive the d~scharge of a food waste gnnder (70) Sectton P3111.2; change to read as follows P3111.2 Installation The only vertical p~pe ofa combmat~on drain and vent system shall be the cormect~on between the fixture dram of a sink, lavatory or standpipe, and the horizontal combination waste and vent p~pe The maximum vertical distance shall be 36 roches 8 feet (914 2438 mm) (71) Section E3301 I; add a sentence to read as follows: All references to NFPA 70 shall mean the Electrical Code as adopted (72) Section E3306 3; change to read as follows: E3306.3 Minimum s~ze of conductors. The minimum size of conductors for feeders and branch clremts shall be No 14 copper and No 12 aluminum The minimum s~ze of Page 17 servme conductors shall be as specified ~n Chapter 35 The m~mmum s~ze of class 2 remote, signaling and power-limited clrcmts conductors shall be as specffied ~n Chapter 42 (73) Sectton E3306.6; change to read as follows E3306.6 Conductors in parallel. C~rcmt conductors that are electrically joined at each end to form a single conductor shall be limited to s~zes No 1/0 and larger Conductors ~n parallel shall be of the same length, same conductor material, same clmular md area and same insulation Conductors m parallel shall be terminated m the same manner Where run ~n separate raceways or cables, the raceway or cable shall have the same physical characteristics (74) Sectton E3802.8; change to read as follows. E3802.8 Exempt receptacles. Receptacles installed under exceptions to Sections E3802 2 and E3802 4 E3802 5 shall not be considered as meeting the reqmrements of Section E3801 10 E3801 9 Section 28-124. Deletion and Amendments ~s added to read (1) Sectton 102.2; add an exception to read as follows Exception: Existing dwelhng umts shall comply w~th Section 620 2 (2) Section 102.8, change to read as follows. 102.8 Referenced codes and standards The codes and standards referenced here~n shall be those that are listed ~n Chapter 7 and such codes, when specifically adopted, and standards shall be considered part of the reqmrements of this code to the prescribed extent of each such reference Where d~fferences occur between provisions of this code and the referenced standards, the prows~ons of this code shall apply Whenever amendments have been adopted to the referenced codes and standards, each reference to smd code and standard shall be considered to reference the amendments as well Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted (3) Section 202; amend definition of "Unvented Room Heater" to add a sentence to read as follows' For the purpose of installation, th~s defimtlon shall also ~nclude "Unvented Decorative Appliances" (4) Section 302 3, change to read as follows 302 3 Cutting, notching and boring m wood members. When permitted by the Internattonal Bud&ng Code, the cuttmg, notching and bonng of wood members shall comply with Sections 302 3 1 through 302 3 3 (5) Section 305 4, delete (6) Add Sectton 305.5 to read as follows' Page 18 305 5 Clearances from grade. Equipment and appliances installed at grade level shall be supported on a level concrete slab or other approved material extending above adjoining grade a mimmum of 3 inches (76 mm) or shall be suspended a minimum of 6 roches (152 mm) above adjolmng grade (7) Section 306 3; change to read as follows. 306 3 Appliances in attics. Attics contmmng appliances requmng access shall be provided with an opening and unobstructed passageway large enough to allow removal of the largest appliance The passageway shall not be less than 30 roches high and 22 inches wide and not more than 20 feet in length measured along the centerhne of the passageway from the opening to the appliance The passageway shall have a continuous solid flooring not less than 24 roches wide A level service space not less than 30 inches deep and 30 inches wide shall be present at the front or service side of the equipment The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), or larger where such dimensions are not large enough to allow removal of the largest appliance As a munmum, access to the attic space of resldentml uses shall be provided by one of the following 1 A permanent sttur 2 A pull down statr 3 An access door from an upper floor level Exception' The passageway and level service space are not required where the appliance is capable of being serviced and removed through the mqmred opemng (8) Section 306.3.1; add a sentence to read as follows Low voltage wrong of 50 Volts or less shall be installed in a manner to prevent physical damage (9) Section 306.4 1, add a sentence to read as follows Low voltage wrong of 50 Volts or less shall be installed in a manner to prevent physical damage (10) Section 306 5; change to read as follows: 306.5 Apphanees on roofs or elevated structures Where appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet (4877 mm), such access shall be provided by a permanent approved means of access the extent of which shall be from Permanent exterior ladders providing roof access need not extend closer than 8 feet (2438 mm) to the finish grade or floor level below and shall extend to the apphance's level service space Such access shall not require climbing over obstructions greater than 30 inches high or walkang on roofs hawng a slope greater than 4 umts vertical in 12 umts horizontal (33-percent slope) (Il) ,~dd Section 306 $.1.1 to read as follows: 306.5.1.1 Catwalk. On roofs having slopes greater than 4 units vertical in 12 units horizontal, a catwalk at least 16 roches in width with substantial cleats spaced not more than 16 inches apart shall be provided from the roof access to the working platform at the appliance Page 19 (12) Section 306.5.2; add a sentence to read as follows: Low voltage wlnng of 50 Volts or less shall be installed in a manner to prevent physical damage (13) ,,ldd Sectton 306. 7 to read as follows. 306 7 IWater heaters above ground or floor. When the attic, roof, mezzanine or platform m which a water heater is installed is more than eight (8) feet (2438 mm) above the ground or floor level, ~t shall be made accessible by a stairway or permanent ladder fastened to the bmld~ng 306.7.1. Whenever the mezzanine or platform is not adequately lighted or access to a receptacle outlet ~s not obtainable from the mmn level, lighting and a receptacle outlet shall he provided in accordance with Section 306 3 1 (14) Section 401 5; add a second paragraph to read as follows' Both ends of each section of mechum pressure corrugated stmnless steel tubing (CSST) shall identify its operating gas pressure with an approved tag The tags are to be composed of aluminum or sttunless steel and the following wording shall be stamped into the tag "WARNING 1/2 to 5 ps1 gas pressure Do Not Remove" (15) Section 402.3; add an exception to read as follows Exception. Corrugated stmnless steel tubing (CSST) shall be a minimum of 1/2" (16) Section 404.6; change to read as follows' 404.6 ,Piping m sohd floors. P~pmg in solid floors shall be lind in channels in the floor and covered m a manner that will allow access to the piping with a minimum amount of damage to the bmldmg Where such piping ~s subject to exposure to excessive moisture or corrosive substances, the piping shall be protected in an approved manner As an alternative to installation in channels, the p~plng shall be installed ~n accordance with Sectmn 404 11 a casmg of schedule 40 steel, wrought iron, PVC or ABS pipe w~th tightly sealed ends and jmnts Both ends of such casing shall extend not less than 2 roches (51 mm) beyond the pomt where the p~pe emerges from the floor (17) Section 404.9; change to read as follows: 404 9 Mimmum burial depth. Underground p~plng systems shall be installed a mlmmum depth of 18 inches (305 458 mm) below grade, except as provided for in Sect~qn 404 9 1 (18) Section 404.9.1; delete (19) Section 406.4; add a sentence to read as follows The equipment used shall be of an appropriate scale such that pressure loss can be easily determined (20) Section 406.4.1; change to read as follows Page 20 406.4.1 Test pressure The test pressure to be used shall be not less than 1 1/2 times the proposed maximum working pressure, but not less than 10 ps~g (20 68 9 kPa gauge), or at the discretion of the Code Official, the p~plng and valves may be tested at a pressure of at least six (6) roches (152 mm) of mercury, measured w~th a manometer or slope gauge ~rrespectlve of design pressure Where the test pressure exceeds 125 pslg (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress m the p~pmg greater than 50 percent of the specified minimum yield strength of the pipe For welded p~pmg and for p~pmg carrying gas at pressures in excess of fourteen (14) inches water column pressure (3 48 kPa), the test pressure shall not be less than s~xty (60) pounds per square meh (413 4 kPa) (2D Sectton 406.4 2, change to read as follows 406 4.2 Test duration. Test duration shall be held for a length of time satisfactory to the Code Official, but m no case for not less than fifteen (15) minutes For welded piping, and for p~pmg carrymg gas at pressures m excess of fourteen (14) inches water column pressure (3 48 kPa), the test duration shall be held for a length of time satisfactory to the Code Official, but m no case for less than thirty (30) minutes 1/2 hour for each 500 cubic feet (14 m 3 ) of pipe volume or fraction thereof When testing a system having a volume less than 10 cubic feet (0 28 m 3) or a system m a single-family dwelling, the test duration shall be permitted to be reduced to 10 minutes For piping systems hawng a volume of more than 24,000 cubic feet (680 m 3), the duration of the test shall not be reqmred to exceed 24 hours (22) .4dd Sectton 409.1.4 to read as follows 409.1.4 Valves in CSST installations Shutoff valves installed with corrugated stainless steel (CSST) piping systems shall be supported with an approved termtnatlon fitting, or equivalent support, statable for the s~ze of the valves, of adequate strength and quahty, and located at intervals so as to prevent or damp out excessive vibration but in no case greater than 12-roches from the center of the valve Supports shall be mstalled so as not to interfere w~th the free expansion and contraction of the system's p~pmg, fittings, and valves between anchors All valves and supports shall be designed and installed so movement of the supporting piping will not d~sengage them (23) Section 410.1, add a second paragraph and exceptton to read as follows: Access to regulators shall comply w~th the requirements for access to apphanccs as specified m Section 306 Exception. A passageway or level service space is not required when the regulator ~s capable of being serviced and removed through the required attic opemng (24) Section 613 6; add a sentence to read as follows The s~ze of duet shall not be reduced along ~ts developed length or at the point of termmatton (25) Sectton 613.6 1; change to read as follows 613.6.1 Maximum length The maximum length of a clothes dryer exhaust duct shall not exceed 25 feet (7620 mm) from the dryer location to the outlet terminal with not more Page 21 than two bends When extra bends are installed, the maximum length of the duct shall be reduced 2 5 feet (762 mm) for each 45-degree (0 79 rad) bend and 5 feet (1524 mm) for each 90-degree (1 6 rad) bend that occur after the first two bends, measunng ~n the d~rect~gn of mrflow {Exception ts unchanged} (26) Section 620.2; change to read as follows' 620 2 Prohibited use. One or more unvented room heaters shall not be used as the sole source of comfort heating ~n a dwelhng umt Exception. Ex~stmg approved unrented heaters may continue to be used ~n dwelhng umts, in accordance w~th the code provisions m effect when installed, when approved by the Code Official unless an unsafe condition is determined to ex,st as described m Section 108 7 (27) Section 623.1 1; change to read as follows 623.1.1 Installation requirements. The reqmrements for water heaters relative to access, s~zmg, rebel valves, dram pans and scald protectmn shall be m accordance w~th the International Plumbing Code Sectton 28-145 Deletions and amendments is amended to read (1) Section 102.8, change to read as follows. 102.8 ~Referenced codes and standards The codes and standards referenced m th~s code shall be those that are hsted m Chapter 13 and such codes, when specffically adopted, and standards shall be considered part of the reqmrements of th~s code to the prescribed extent of each such reference Where the reqmrements of reference standards or manufacturer's mstallatmn mstmctmns do not conform to mimmmn prowsmns of th~s code, lhe prows~ons of this code shall apply Whenever amendments have been adopted to the referenced codes and standards, each reference to smd code and standard shall be considered to reference the amendments as well Any reference to NFPA 70 or the ICC Electmcal Code shall mean the Electrical Code as adopted (2) Section 305.6.1; change to read as follows. 305.6.1 Sewer depth Bmldurg sewers that connect to private sewage d~sposal system shall be a minimum of [number] roches (mm) below fimshed grade at the point of septm tank connection Building sewers shall be a mm~mum of 12 ~nches (304 mm) below grade, disposal beeanse a private sewage disposal code ~s not typmally adopted m th~s reg~oa ) (3) Section 305 9, change to read as follows' 305.9 Protection of components of plumbing system Components of a plumbing system installed w~thm 3 feet along alleyways, driveways, parking garages or other locatluns m a manner m which they would be exposed to damage shall be recessed into the wall or otherwise protected m an approved manner (4) Section 310 4, delete Page 22 (5) Seettons 312.9 1 and 312 9 2; change to read as follows 312 9.1 Inspections. Annual inspections shall be made of all backflow prevention assembhes and a~r gaps to determine whether they are operable In the absence of local prows~ons, the owner ~s responmble to ensure that testing ~s performed 312.9.2 Testing. Reduced pressure pnnclple backflow preventer assembhes, double check-valve assembhes, double-detector check valve assembhes and pressure vacuum breaker assembhes shall be tested at the time of installation, ~mmedmtely after repmrs or reloca~mn and at least annually The testing procedure shall be performed ~n accordance w~th apphcable local prowmons In the absence of local provisions, the owner is responmble to ensure that testmg ~s done m accordance w~th one of the following standards ASSE 5010-1013-1, Secttons 1 and 2 ASSE 5010-1015-1, Sections 1 and 2 ASSE 5010-1015-2 A$SE 5010-1015-3, Sectlons 1 and 2 ASSE 5010-1015-4, Sections 1 and 2 ASSE 5010-1020-1, $ecttons 1 and 2 ASSE 5010-1047-1, Secttons 1,2,3 &4 A$$E 5010-1048-1, Sections 1,2,3 &4 ASSE 5010-1048-2 ASSE 5010-1047-3, Sections 1,2,3 &4 ASSE 5010-1047-4, Secttons 1,2,3 &4 CAN/CSA B64 10 (6) Sectton 314.2 1, modify second sentence to read as follows 314.2.1 Condensate disposal. Condensate from all coohng coils and evaporators shall be conveyed from the drmn pan outlet to an approved place of disposal Condensate shall not d~scharge m a pubhcly exposed area such as ~nto a street, alley, s~dewalk or other areas so as to cause a nuisance (7) Sectton 314.2.2; add a second paragraph to read as follows: Condensate waste p~pes from alr-coohng co~ls may be stzed ~n accordance w~th eqmpment capacity as follows Eqmpment Capacity m tons of Minimum Condensate P~pe refrigeration Inside Dmmeter Up to, 20 tons 3/4 tnch Over 20 to 40 tons 1 inch Over 40 to 90 tons 1 1/4 ~nch Over 90 to 125 tons l ½ tach Over 125 to 250 tons 2 ~nch The size of condensate waste p~pes may be for one umt or a comblnataon of umts, or as Page 23 recommended by the manufacturer The capacity of waste pipes assumes a 1/8qnch-per- foot slope, with the pipe running three-quarters full (8) Section 314.2.3; add item g4 to read as follows 4 Discharge, as noted, shall be to a conspicuous point of d~sposal to alert occupants ~n the event of a stoppage of the drmn However, the conspicuous pmnt shall not create a hazard such as dripping over a walking surface or other areas so as to create a nmsance (9) Section 401 1; add a sentence to read as follows' The provisions of th~s Chapter are meant to work in coordination w~th the provisions of the Bmldmg Code Should any conflicts arise between the two chapters, the Code Official shall determine which provision apphes (10) Section 403.1; change to read as follows' 403 1 Minimum number of fixtures. Plumbing fixtures shall be prowded for the type of occupancy and in the minimum number as follows 1 Assembly Oecupanmes At least one dnnkmg fountmn shall be prowded at each floor level in an approved location Exception: A dnnkmg fountmn need not be prowded in a dnnkmg or dlmng establishment 2 Groups A, B, F, H, I, M and S Occupancies Buildings or portions thereof where persons are employed shall be provided w~th at least one water closet for each sex except as prowded for in Section 403 2 3 Group E Occupancies Shall be provided with fixtures as shown in Table 403 1 4 Group R Occupancies Shall be provided w~th fixtures as shown ~n Table 403 1 It ~s recommended, but not reqarmd, that the m~mmum number of fixtures prowded also comply with the number shown in Table 403 1 Types of occupancies not shown in Table 403 1 shall be considered Individually by the code official The number of occupants shall be determined by the Internatzonal Butldtng Code Occupancy classification shall be determined in accordance with the Internattonal Butldtng Code (Il) Add Section 403.1.2 to read as follows. 403.1,2 Finish material. Fm~sh matermls shall comply wtth Section 1209 of the Internattonal Butldtng Code (12) Section 404.2, change to read as follows: 404.2 Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an accessible umsex toilet room shall be provided where an aggregate of stx or more male or female water closets are required provided In bmldlngs of m~xed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the unisex tmlet room requirement In recreational faclhtles where separate-sex bathing rooms are provided, an accessible tin,sex bathing room shall be provided (13) Section 405 6; delete Page 24 (14) Section 409.2; change to read as follows: 409 2 Water connection. The water supply to a commcrmal d~shwashmg machtne shall be protected against backflow by an air gap or backflow preventer m accordance wtth Section 608 (15) Sectton 410 1, change to read as follows: 410.1 Approval. Dnnkmg fountains shall conform to ASME All2 19 1, ASME All2 19 2 or ASME All2 19 9, and water coolers shall conform to ARI I010 Where water ~s served tn restaurants or where bottled water coolers are prowded tn other occupancies, dnnktng fountains shall not be reqmred Exception' A dnnkmg fountain need not be provided tn a dnnk~ng or dtnmg estabhshment (16) Section 412.4; change to read as follows' 412 4 Required location Public laundries and central washing facilities. Floor drams shall be installed m the following areas 1 In pubhc co~n-operated laundries and m the central washing famht~es of multtple famdy dwelhngs, the rooms contaimng the automatm clothes washers shall be provtded w~th floor drains located to readdy drain the entire floor area Such drmns shall have a mmtmutn outlet cross sectton of not less than 3 ~nches (76 mm) tn dtameter 2 Commercml k~tchens (In heu of floor drains tn commercml kttchens, the code offimal may accept floor smks ) (17) Section 413.4; change to read as follows: 413 4 Water supply reqmred. All food waste gnnders shall be provtded wtth a supply of cold water The water supply shall be protected agmnst backflow by an mr gap or wtth the ~nstallat~on of a backflow preventer m accordance w~th Sectton 608 (18) Section 417.5; change to read as follows. 417.5 Shower floors or receptors. Floor surfaces shall be constructed of ~mpervtous, noncon'os~ve, nonabsorbent and waterproof materials Thresholds shall be a m~mmum of 2 ~nches (51 mm) and a maximum of 9 tnches (229 mm), measured from top of the drain to top of threshold or dam Thresholds shall be of suffiment w~dth to accommodate a mtmmum twenty-two (22) ~nch (559 mm) door Exception: Showers designed to comply wtth ICC/ANSI A117 1 (19) Section 417.5.2; change to read as follows. 417 5.2 Shower lining Floors under shower compartments, except where prefabricated receptors have been provtded, shall be hned and made water tight utthztng material complying w~th Sections 417 5 2 1 through 417 5 2 4 Such hners shall turn up on all s~des at least 2 3 ~nches (51 mm) above the fimshed threshold level and shall extend outward over the threshold and fastened to the outstde of the threshold jamb Ltners shall be recessed and fastened to an approved backtng so as not to occupy the space mqmred for wall covenng, and shall not be nailed or perforated at any potnt less than 1 ~nch above the fimshed threshold Ltners shall be pitched one-forth umt vertmal tn 12 umts horizontal (2-percent slope) and shall be sloped towards the fixture drains and be securely Page 25 fastened to the waste outlet at the seepage entrance, making a water-tight jmnt between the liner and the outlet (20) Add Section 417. 7 to read as follows' 417 7 Test for shower receptors. Shower receptors shall be tested for water tightness by filhng with water to the level of the rough threshold The dratn shall be plugged in a manner so that both sides of pans shall be subjected to the test at the point where tt is clamped to the drmn (21) Section 419.3; change to read as follows' 419.3 Surrounding material. Wall and floor space to a point 2 feet (610 mm) in front of a unnal lip and 4 feet (1219 mm) above the floor and at least 2 feet (610 mm) to each side of the unnal shall be waterproofed with a smooth, readily cleanable, hard, nonabsorbent material (22) Sectton 502.5; change to read as follows' 502.5 Water heaters installed matttcs Atttcs containing a water heater shall be provtded wtth an openmg and unobstructed passageway large enough to allow removal of the water heater The passageway shall not be less than 30 inches high and 22 ~nches wtde and not more than 20 feet tn length when measured along the centerhne of the passageway from the openmg to the water heater The passageway shall have contmuous sohd floonng not less than 24 roches wtde A level service space at least 30 inches deep and 30 inches w~de shall be present at the front or service side of the water heater The clear access opanmg dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), or larger where such dtmenslons are not large enough to allow removal of the water heater (23) Add Sectton 502.5 1 to read as follows: 502.541 Electrical requirements. A hghtmg fixture controlled by a sw~tch located at the reqmred passageway opemng and a receptacle outlet shall be provided at or near the equipment locatmn m accordance with the electrical code (24) Add Section 502 7 to read as follows 502.7 Water heaters above ground or floor When the attic, roof, mezzanine or platform m whmh a water heater ~s installed ~s more than etght (8) feet (2438 mm) above the ground or floor level, tt shall be made accesstble by a stmrway or permanent ladder fastened to the bmldmg 502 7.1 Whenever the mezzanine or platform ts not adequately hghted or access to a receptacle outlet ts not obtamable from the mmn level, hghtmg and a receptacle outlet shall be provided in accordance wtth Section 502 5 1 (25) Section 504.6.1, change to read as follows 504.6 1 Discharge. The relief valve shall dtscharge through full stze ptpmg to a safe place of dmposal such as the floor drain, outside the building, or an redirect waste receptor The d~acharge pipe shall not have any trapped sections When the dratnptpe run ts exposed, tn an area outside of the room where the water heater ts located, m a manner that would make it subject to damage, the dram and shall have a mslble mr gap or att gap Page 26 fitting located m the same room as the water heater The d~scharge shall be ~nstalled ~n a manner that does not cause personal injury to occupants in the ~mmedlate area or structural damage to the braiding The end of the d~scharge p~pe shall not be threaded The dtscharge pipe shall not chscharge rote the pan required ~n Section 504 7 When dmchargmg outside the bmldmg, the point of d~scharge shall be w~th the end of the p~pe not more than two (2) feet (610 mm) nor less than six (6) inches (152 mm) above the ground or the floor level of the area mce~vtng the d~scharge and pmntmg downward (26) Sectton 505.1; change to read as follows: 505.1 Unfired vessel insulation. Unfired hot water storage tanks shall be insulated so that heat loss ~s hm~ted as specified m Sectmn 504, Internattonal Energy Conservatton Code {Delete remainder of section} (2 7) Add Sectton 506, 506.1 to read as follows SECTION 506 COMBUSTION AIR AND VENTILATION 506.1. Combustion air and ventilation. Combustion mr and ventilation for fuel burning water heaters, other than gas-fired, shall be m accordance w~th the Internattonal Mechamcal Code Combustion air and ventilation for gas-fired water heaters shall be m accordance w~th the Internattonal Fuel Gas Code (28) Add Sectton 604 4 1 to read as follows' 604 4.1 State maximum flow rate. Where the State mandated maximum flow rate ~s more restrictive than those of this section, the State flow rate shall take precedence (29) Tables 605.4 and 605 5; delete "Polybutylene (PB) plasttc ptpe and tubing' (30) Sectton 606.1; delete ttems g4, 5 and 6 (31) Sectton 606.2; items #1 and 2 changes to read as follows 1 On the fixture supply to each plumbing fixture in other than one- and two-family and multiple family res~dentml occupancies, and other than m individual guestrooms that are provided w~th umt shutoff valves ~n hotels, motels, boarding houses and s~mflar occupancies Exeeptmn: Tub and shower valves 2 On the water supply p~pe to each sfllcock when subject to freezing (Reason To provide shut-offvalves to every fixture ) (32) Section 607 2.1; change to read as follows 607.2.1 Piping insulation. Piping in reqmred return c~rculatmn systems shall be insulated as reqmred m Section 504, Internattonal Energy Conservatton Code {Delete rematnder of sectzon) (33) Section 608.1; change to read as follows' 608 1 General. A potable water supply system shall be designed, installed and mam~mned m such a manner so as to prevent contamination from nonpotable liquids, sohds or gases being introduced rote the potable water supply through cross-connect~ons Page 27 or any other piping connections to the system Back flow preventer applications shall conform to applicable local regulations, Table 608 1, except and as specffically stated in Sections 608 2 through 608 16 9 (34) Sectton 608 17, change to read as follows: 608.17 Protection of individual water supplies An ~nd~wdual water supply shall be located and constructed so as to be safeguarded agmnst contamination ~n accordance w~th apphcable local regulations In the absence of other local regulations, installation shall be ~n accordance with Sections 608 17 1 through 608 17 8 (35) Sectton 708.3.4, change to read as follows 708.3 4 Upper terminal Base of stack Each horizontal drmn shall be provided with a cleanout at its upper terminal A cleanout shall be prowded at the base of each waste or soil stack Exception: Cleanouts may be omitted on a horizontal drmn less those five (5) feet (1524 mm) m length unless such hne ~s servmg sinks or unnals (36) Add Section 712.5 to read as follows' 712.5 Dual Pump System All sumps shall be automatically d~scharged and, when in any "pubhe use" occupancy where the sump serves more than 10 fixture un,ts, shall be provided with dual pumps or ejectors arranged to function independently in case of overload or mechanical failure For storm drainage sumps and pumping systems, see Section 1113 (Reason To address dual pump system To provide reference for storm drainage systems ) (37) Sectton 714, 714 1, change to read as follows SECTION 714 ENGINEERED COMPUTERIZED DRAINAGE DESIGN 714.1 Design of drainage system The s~mng requirements for plumbing drmnage systems shall be determined by approved computer program design methods 08) Section 802.1.1; delete the exception (39) Sectton 802.4, add a sentence to read as follows. No standpipe shall be installed below the ground (40) Section 904.1; changed to read as follows. 904.1 Roof extension. All open vent pipes that extend through a roof shall be terminated at least slx (6) inches (152 mm) above the roof, except that where a roof ~s to be used for any ptupose other than weather protection, the vent extensions shall be run at least 7 feet (2134 mm) above the roof (41) Sectton 912.1, change to read as follows. 912.1 Type of fixture. A combination drmn and vent system shall not serve fixtures other than floor drtuns, standpipes, sinks and lavatories indirect waste receptors Combination drmn and vent systems shall not receive the discharge of a food waste gnnder Page 28 (42) Section 912.2; change to read as follows. 912 2 Installation. The only vertical pipe of a combination drain and vent system shall be the connectzon between the fixture drmn of a sink, lavatory or standpipe, and the horizontal combination drmn and vent pipe The maximum vertzcal distance shall be 8 feet (2438 mm) (43) Section 1002.10, delete (44) Section 1003 1, added to read as follows. Mmzmum construction standards for food servzce estabhshments are required when 1 A new building zs constructed and occupied, 2 Prior to the issuance of a certfficate of occupancy for an ex~sttng building which has not been previously used as a food servme estabhshment wlthzn the last six (6) months 3 A change to a more restrictive class of food preparatzon occurs Heavy Food Preparatton shall mean any area ~n which foods are prepared utthmng a grill, griddle, deep-fat fryer, commercial type ovens, and/or any s~mllar food preparation eqmpment, or any area subject to flooding type of wet cleaning procedures due to the cutting or processzng of meat, poultry, fish or pork Heavy food preparation includes but ts not limited to cafeterias, fast food restaurant, full servme restaurants, pizza preparation, donut preparatzon Meat and fish markets, (et cetera) A mmtmum 1,000- gallon grease interceptor is reqmred for heavy food preparation estabhshments Light Food Preparatton shall mean any area ~n which foods are prepared exclusive of the use of fryers, grills or s~mllar eqmpment L~ght food preparation is usually hmlted to the preparatzon of hot dogs, sandwiches, salads or other s~mzlar foods and fountain-type cold dnnks Light food preparataon xncludes, but ~s not hmzted to, sandwich shops, hmlted menu concessaon stands (et cetera) A mimmum 200-gallon grease ~nterceptor ~s required for hght food preparation estabhshments No Food Preparation shall mean any area in which foods are provided prewrapped, from an approved soume, wzth m~crowave oven type heating being the maximum handllng revolved No food preparation ~s hmlted to pre-packaged sandwmhes or similar foods, candies and contmnenzed beverages A grease xntemeptor ~s not required for no food preparation estabhshments (45)Section 1106.1, change to read as follows 1106.1 General. The s~ze of the vertical conductors and leader, building storm drmns, building storm sewers, and any horizontal branches of such drmns or sewers shall be based on six (6) ~nches per hour the 100-year hourly rmnfall rate lndmated in Fagure 1106 1 or on other rainfall rates determined from approved local weather data (46) Section 1107.3, change to read as follows' 1107.3 Sizing of secondary drains. Secondary (emergency) roof drain system shall be sized m accordance wath Section 1106 based on the ratnfall rate for whmh the primary Page 29 system is sized ~n Tablesll06 2, 1106 3 and 1106 6 by two Scuppers shall be s~zed to prevent the depth of pondlng water from exceeding that for which the roof was designed as determined by Section 1101 7 Scuppers shall not have an opemng d~menslon of less than 4 ~nches The flow through the primary system shall not be considered when sizing the secondary roof drmn system (47) Chapter 12; delete Section 28-252 Deletions and amendments ts amended to read (1) Section 102.8, change to read as follows 102.8 Referenced codes and standards. The codes and standards referenced hereto shall be those that are hsted m Chapter 15 and such codes, when specffically adopted, and standards shall be considered part of the reqmrements of th~s code to the prescribed extent of each such reference Where differences occur between provm~ons of th~s code and the referenced standards, the prowsmns of th~s code shall apply Whenever amendments have been adopted to the referenced codes and standards, each reference to smd code and standard shall be considered to reference the amendments as well Any reference to NFPA 70 or the ICC Electrtcal Code shall mean the Electrical Code as adopted (2) Section 302.3; change to read as follows' 302.3 Cutting, notching and bonng ~n wood framing When permttted by the Internattonal Buddtng Code, the cutting, notching and bonng of wood framing members shall comply w~th Sections 302 3 1 through 302 3 3 (3) Section 304.5, delete (4) Section 304 8; change to read as follows 304.8 Clearances from grade. Eqmpment and apphances installed at grade level shall be supported on a level concrete slab or other approved material extending above adjoining grade a mlmmum of 3 roches (76 mm) or shall be suspended a munmum of 6 roches (152 mm) above adjommg grade (5) ~tdd Section 304 11 to read as follows 304.11 Mimmum burml depth. Underground fuel p~pmg systems shall be ~nstalled a m~mmum depth of 18 roches (458 mm) below grade (6) Sectton 306.3; change to read as follows. 306 3 Appliances in attics Attics contarmng apphances reqmrmg access shall be prowded w~th an openmg and unobstructed passageway large enough to allow removal of the largest component of the apphance The passageway shall not be less than 30 roches h~gh and 22 roches w~de and not more than 20 feet m length when measured along the centerhne of the passageway from the opening to the eqmpment The passageway shall have continuous sohd floonng not less than 24 ~nches w~de A level servme space not less than 30 roches deep shall be present at the from or servme rode of the apphance The clear Page 30 access opemng thmenaons shall be a minimum of 20 aches by 30 inches (508 mm by 762 mm), or larger where such dlmansaons are not large enough to allow removal of the largest apphance As a mm~mum, access to the attm space of res~dentml uses shall be prowded by one of the followmg 1 A permanent star 2 A pull down stair 3 An access door from an upper floor level Exception: The passageway and level service space are not reqmred where the apphance ~s capable of being serviced and removed through the required opening (7) Seetton 306.3.1; add a sentence to read as follows Low voltage wang of 50 Volts or less shall be ~nstalled in a manner to prevent physmal damage (8) Section 306.4 1, add a sentence to read as follows Low voltage wang of 50 Volts or less shall be tnstalled ~n a manner to prevent physmal damage (9) Section 306.5; change to read as follows' 306.5 Equipment and applmnees on roofs or elevated structures Where eqmpment and apphances requmng access are ~nstalled on roofs or elevated structures at a height exceedmg 16 feet (4877 mm), such access shall be prowded by a permanent approved means of access the extent of which shall be from Permanent exterior ladders prowd~ng roof access need not extend closer than 8 feet (2438 mm) to the flash grade or floor level below and shall extend to the equipment and apphance's level servme space Such access shall not reqmre chmb~ng over obstructions greater than 30 ~nches h~gh on roofs havmg a slope greater than 4 umts vertmal m 12 umts horizontal (33-percent slope) A receptacle outlet shall be promded at or near the eqmpment and apphance location ~n accordance w~th the Electrical Code Low voltage wang of 50 Volts or less shall be ~nstalled in a manner to prevent physmal damage (10) Section 306.6; add a second paragraph to read as follows A receptacle outlet shall be prowded at or near the apphance location ~n accordance w~th the Electrical Code Low voltage wang of 50 Volts or less shall be mstalled ~n a manner to prevent physmal damage (11) Add Section 306.6.1 to read as follows: 306 6,1 Catwalk. On roofs hawng slopes greater than 4 umts vertical m 12 units horizontal, a catwalk at least 16 aches in w~dth w~th substantml cleats spaced not more than 16 aches apart shall be provided from the roof access to the working platform at the apphance (12) Add Section 306. 7 to read as follows. 306 7 Water heaters above ground or floor. When the mezzanine or platform ~n which a water heater ~s mstalled ~s more than eaght (8) feet (2438 mm) above the ground or floor Page 31 level, it shall be made accessible by a stmrway or permanent ladder fastened to the building 306.7.i Whenever the mezzanine or platform is not adequately lighted or access to a receptacle outlet is not obtmnable from the mmn level, lighting and a receptacle outlet shall b~ provided m accordance w~th Sectmn 306 3 1 (13) Section 307 2.1; modify second sentence to read as follows 307.2.1 Condensate disposal Condensate from all coohng co~ls and evaporators shall be conveyed from the dram pan outlet to an approved place of dmposal Condensate shall not d~seharge m a pubhcly exposed area such as into a street, alley, s~dewalk or other areas so as to cause a nuisance (14) Section 307.2 2, add a second paragraph to read as follows' Condensate waste p~pes from mr-cooling cmls may be s~zed m accordance with equipment capacity as follows Equlp~nent Capacity Minimum Condensate Pipe in tons of refrigeration Inside Diameter Up to 20 tons 3/4 inch Over ~0 to 40 tons 1 tach Over 40 to 90 tons 1 1/4 inch Over 90 to 125 tons 1 t/2 tach Over !25 to 250 tons 2 tach The s~ze of condensate waste p~pes may be for one umt or a combination of ttmts, or as recommended by the manufacturer The capacity of waste p~pes assumes a 1/8-inch-per- foot slope, with the p~pe mnnmg three-quarters full (15) Section 307.2.3; add item #4 to read as follows. 4 D~seharge, as noted, shall be to a conspicuous point of d~sposal to alert occupants ~n the event of a stoppage of the drmn However, the conspicuous point shall not create a hazard such as dripping over a walkmg surface or other areas so as to create a nuisance (16) Section 403 2, add an exception to read as follows Exception: Where the design professmnal demonstrates that an engineered ventdatmn system ~s designed m accordance with ASHRAE 62, the minimum reqmred rate of outdoor mr shall be permitted to be as specffied in such engineered system design (17) Sectton 403.2.1; add an Item g4 to read as follows 4 Tollet rooms within private dwelhngs that contain only a water closet, lavatory or combinatmn thereof may be ventilated w~th an approved mechanical rec~rculatmg fan or s~mdar device designed to remove odors from the mr (18) Table 403.3, footnote g. change to read as follows Page 32 g Transfer mr permitted in accordance with Section 403 2 2 Toilet rooms within private dwellings that contmn only a water closet, lavatory or combination thereof may be ventilated w~th an approved mechanical rec~rculatlng fan or similar device designed to remove odors from the air (20) Section 504.6; add a sentence to read as follows The s~ze of duct shall not be reduced along its developed length or at the point of termination (21) Sectton 504.6 1, change to read as follows 504 6.1 Maximum length The maximum length ora clothes dryer exhaust duct shall not exceed 25 feet (7620 mm) from the dryer location to the outlet terminal with not more than two bends When extra bends are installed, the maximum length of the duct shall be reduced 2 5 feet (762 mm) £or each 45-degree (0 79 tad) bend and 5 feet (1524 mm) £or each 90-degree (1 6 tad) bend that occur after the first two bends, measuring m the direction of mrflow {Exceptton ts unchanged} (22) Section 506.3.11; change to read as follows' 506 3.11 Duct enclosure A grease duct serving a Type I hood that penetrates a cethng, wall or floor shall be enclosed from the point o£penetrat~on to the outlet terminal A duct shall only penetrate exterior walls at a point where unprotected openings are permitted by the International Butldtng Code Ducts shall be enclosed in accordance with the ~rnternattonal Butldtng Code reqmrements £or shaft construction The duct enclosure shall be sealed around the duct at the point of penetration and vented to the outside of the bufldmg through the use of weather-protected openings The enclosure shall be separated from the duct by a mlmmum of 3 inches (152 76 mm) and a maximum of 12 inches (305 mm) and shall serve a single grease exhaust duct system {Excepttons rematn unchanged } (23) Section 510. 7; add a second exception to read as follows Exceptions 1 {Extstmg exception unchanged} 2 Ducts where the largest cross-seet~onal diameter of the duct is less than l0 inches (254 mm) (24) Section 604.1, change to read as follows: 604 1 General. Duct insulation shall conform to the reqmrements of Sections 604 2 through 604 1, Table 604 1 and the Internattonal Energy Conservatton Code Should there be any conflicts between this section and the energy code, the energy code shall take precedence Page 33 (25) Add Table No. 604 1 to read as follows Table 604.1 - Insulation of Ducts Duet Location Insulation Types Heating Zone 1 Insulation Mechamcally Types Cooled Heating Only On roof on exterior C, V 2 and W I A and W of bmldmg II B and W III C and W Attics, garages and A and V 2 I A crawl spaces II A III B Wlthm the None required None required conditioned space or in Basements, return ducts in air plenums Cement slab or None required None required within ground Note. Where ducts are used for both heating and cooling, the m~mmum insulation shall be as required for the most restrictive condition 1 Heating Degree Days Zone I below 4,500 D D Zone II 4,501 to 8,000 D D Zone III over 8,000 D D 2 Vapor retarders shall be installed on supply ducts in spaces vented to the outside in geographic areas where the summer dew point temperature based on the 2 ½ percent column of dry-bulb and mean commdent wet-bulb temperature exceeds 60 0 F (15 4 0 C) 3 Insulation may be omitted on that portion of a duct whmh is located within a wall- or a floor~ceiling space where ~ ~Both sides of the space are exposed to conditioned air 32 The space is not ventilated ~ 3The space is not used as a return plenum 34 The space is not exposed to unconditioned air Celhngs, which form plenums, need not be insulated INSULATION TYPES 4 A -- A material with an installed conductance of 0 48 [2 72 W/(m*K)] or the equivalent thermal resistance of 2 1 [0 367 (m*K)/W] Example of materials capable of meeting the above requirements Page 34 l-inch (25 mm), 0 60 lb/cu ft (9 6 kg/m 3 ) mineral fiber, rock, slag or glass blankets ¼-meh (13 mm), 1 5 to 3 lb/cu ft (24 to 48 kg/m 3 ) mineral fiber blanket duct :liner Va-tach (13 mm), 3 to 10 lb/eu ft (48 to 160 kg/m 3 ) mineral fiberboard B -- A, mater~al with an installed conductance of 0 24 [1 36 W/(m*K)] or the equivalent thermal resistance of 4 2 [0 735 (m*K)/W] Example of materials capable of meeting the above requirements 2-meh (51 mm), 0 60 lb/cu i~ (9 6 kg/m 3 ) mineral fiber blankets l-tach (25 mm), 1 5 to 3 lb/cu ft (24 to 48 kg/m 3 ) mineral fiber blanket duct hner l-tach (25 mm), 3 to 10 lb/cu ft (48 to 160 kg/m 3 ) mineral fiber board C -- A mater~al with an installed conductance of 0 16 [0 9 W/(m*K)] or the equivalent thermal resistance of 6 3 ~1 1 (m*K)/W] Example of materials capable of meeting the above requirements 3-tach (76 mm), 0 60 lb/cu ft (9 6 kg/m 3 ) mineral fiber blankets 1 ½-meh (38 mm), 1 5 to 3 lb/cu fi (24 to 48 kg/m 3 ) mineral fiber blanket duct liner 1 ½-inch (38 mm), 3 to 10 lb/cu ft (48 to 160 kg/m 3 ) mineral fiberboard V --Vapor Retarders Mater~al with a perm rating not exceeding 0 05 perm [29 ng/Pa*s*m 2 ] All joints to be sealed W - Approved weatherproof hamer 4 The example of materials hsted under each type is not meant to limit other available thickness and density combinations with the equivalent installed conductance or resistance based on the insulation only (26) Section 604.11 Vapor retarders. Where ducts used for cooling are externally insulated, the insulation shall be covered w~th a vapor retarder in accordance with Table 604 1 having a maximum permeance of 0 05 perm [2 87 ng/(Pa s m 2 )] or aluminum foil hawng a minimum thickness of 2 mils (0 051 mm) Insulations having a permeance of 0 05 perms [2 87 ng/(Pa s m 2 )] or less shall not be required to be covered All joints ,and seams shall be sealed to maintain the contmmty of the vapor retarder (27) .~ection 607.2.2; change to read as follows 607.2~2 Hazardous exhaust duets. Hazardous exhaust duct systems shall extend d~rectly to the exterior of the building and shall not extend into or through ducts and plenums Penetration of structural elements shall conform to this section and the Internattonal ButM~ng Code except that fire dampers are not reqmred at penetration of fire-resistance- rated assemblies for hazardous exhaust duct system shall comply with Section 510 (28) Section 607.5.1, change to read as follows: 607.$,.1 Fire Walls. Ducts and transfer openings permitted in firewalls in accordance w~th Section 705 11 of the Internattonal Building Code shall be protected with approved fire dampers installed m accordance with their listing Hazardous exhaust ducts shall not penetrate firewalls Page 35 (29) Section 607.6.1; change to read as follows. 607 6 1 Through penetrations In occupancies other than Groups I-2 and I-3, penetrations by an air duct through a fire-resistive-rated floor/cethng assembly that connects not more than two stones are permitted without shaft enclosure protection where a fire damper is installed at the floor line (30) Chapter 14, delete. Section 28-254 Deletions and amendments is amended to read (1) Section 101.3; amend as follows. 101 3 Compliance. Compliance with this code shall be determined in accordance with Sections 101 3 1, and 101 3 2, or 101 3 3 (2) Add the following item' 101.3.3. Alternative compliance. A building certified through a voluntary energy performance testing program approved as meeting or exceeding the provisions of this code may be deemed to comply with the requirements of this code (3) Section 302.1; Replace blank Table 302.1 Exterior Design Conditions with the following: CONI}ITION VALUE Wmte~ a, deadpan dry bulb ( o F) (99 6%) 17 S~rnmer a, design dry-bulb ( o F) (0 4%) 100 S~mrner a, design wet-bulb ( o F) (0 4%) 78 Degree days heating b 2407 Degree days cooling b 2603 Climate zone c 5B (4) Delete note "a" and replace with the following a These values are from ASHRAE Handbook of Fundamentals for Dallas/Ft Worth International Airport 99 6% Winter DB, 0 4% Summer DB, and 0 4% Summer WB, and from Local Climatological Data for Dallas-Ft Worth published by the National Climatic Data Center, National Oceanic and Atmospheric Administration These values are for the purpose of providing a uniform basis of requirements for North Central Texas This will not preclude licensed professionals from submitting design analyses based on site measurements or published data more specific to the building site AdJustments shall be permitted to reflect local climates that differ from the tabulated values, or local weather experience determined by the code official (5) Delete Ftgures 302 1 (1-43, 45-51). (6) Section 502.1.1; delete exception #2 and substitute the following. 2 Bulldmgs located in Climate Zones 1 through 9 as indicated in Table 302 1 Page 36 (7) Section 502 1.5; add the followmg excepttons Exceptions: 1 Any,glazing facing within 45 degrees of true north, 2 Any glazing facing w~thin 45 degrees of tree south which is shaded along its full width by a pe~rmanent overhang with a projecuon factor of 0 3 or greater 3 Any fenestration with attached screens where the screens have a rated shading coefficient of 6 or less (8) Section 502.2; Replace blank Table 502 2 Heating & Coohng Criteria with the followlng: Table S02.2 a,g HEATING AND COOLING CRITERIA Element Mode Type A-1 Type A-2 Residential Residential Buildings Buildings Uo Uo Walls' Heating or eoohng 0 15 0 22 Roof/ceiling Heating or eoohng 0 03 0 03 Floors over Heating or coohng 0 05 0 05 unheated spaces Heated slab on Heating R-value = 6 R-value = 6 grade Unheated slab on Heating R-value -- 0 R-value = 0 gradeI Basement wall Heating or cooling Uffactor = 0 15 U-factor = 0 15 Crawl space wall Heating or eoohng U-factor = 0 15 U-factor = 0 15 (9) Delete Note "a" and replace with the followtng. a The above values have been determined for all counties in the North Central Texas CounCil of Governments region (I0) Add Note "g": g These reqmrements apply only to the boundaries of conditioned space Air con&t~onmg equipment is recommended, but not required, to be located within the concht~oned space m North Central Texas zones (11) Delete Figures 502 2(1-6) (12) Section 502.2; Add note to Fig 502 2(7)' All counties w~ttun the North Central Texas Council of Governments region are deslgtaated as within the area of very heavy termite infestation probablhty for purpose of umform interpretation of this requirement Page 37 (13) Section 502.2 4, Delete prescriptive Tables 502 2 4(1-9) and substitute the following: Table 502 2.4(1) Prescriptive Building Envelope Requirements, Type A-1 Residential Buildings, Based on Window Area as a Percent of Gross Exterior Wall Area (for zones 5b and 6b) % Maximum Minimum Glazing Glazing Ceiling Exterior Floor Basement Slab Crawl U-factor R-value Wall R- R- Wall R- Perimeter space value value value R-value wall R- and value depth <8% 0 70 R-26 R-11 R-11 R-5 R-0 R-6 <12% 0 65 R-26 R-13 R-11 R-5 R-0 R-5 <15% 0 65 R-30 R-13 R-11 R-6 R-0 R-7 <18% 0 52 R-30 R-13 R-19 R-6 R-0 R-7 <20% 0 50 R-38 R-13 R-19 R-6 R-0 R-7 <25% 0 46 R-38 R-16 R-19 R-6 R-0 R-7 (14) Replace Tables 502.2 4 (7-9) with: Table 502 2 4(2) Prescriptive Building Envelope Requirements, Type A-2 Residential Buildings, Based on Window Area as a Percent of Gross Exterior Wall Area % Maximum Minimum % Glazing Glazing Ceiling Exterior Floor Basement Slab Crawl U-factor R-value Wall R- R- wall R- perimeter space value value value R-value wall R- and value depth <20% 0 55 R-30 R-13 R-II R-5 R-0 R-6 <25% 0 55 R-30 R-13 R-11 R-5 R-0 R-5 <30% 0 47 R-38 R-13 R-19 R-7 R-0 R-8 (15)Section 503.3.3 3, amend as follows' All supply and return-air ducts and plenums installed as part of an HVAC air-distribution system shall be thermally insulated in accordance w~th Table 503 3 3 3 or where such ducts or plenums operate at stat~c pressures greater than 2 in w g (500 Pa) in accordance with Section 503 3 3 4 1 Page 38 (16) Sectton 503.3.3.4, amend subsections as follows' 503 3.3.4 1 High- and medmm-pressure duct systems All ducts and plenums operanng at statm pressures greater than 2 m w g (500 Pa) shall be insulated and sealed m accordance w~th Section 803 2 8 H~gh pressure and medmm pressure Ducts operanng at stanc pressures m excess of 3 ~n w g (750 Pa) shall be leak tested m accordance w~th SMACNA HVAC A~r Duct Leakage Test Manual w~th a rate ofa~r leakage not to exceed the maximum rate spec~f'md m that standard Section 803 3 6 Pressure classifications spemfic to the duet system shall be clearly mdmated on the construction documents m accordance w~th the Internattonal Mechantcal Code 503 3.3.4 2 Low-pressure duct systems. All longitudinal and transverse joints, seams and connections of low-pressure supply and return ducts operating at stanc pressures less than or equal to 2 m w g (500 Pa) shall be securely fastened and sealed w~th welds gaskets, mast]cs (adhesives), mastic-plus-embedded fabric systems or tapes ~nstalled m accordance w~th the manufacturer's mstallanon mstrnct~ons Pressure class]ficanons spec]tic to the duct system shall be clearly mdmated on the construction documents m accordance w~th the Internattonal Mechamcal Code {Exceptton ts unchanged} (17) Sectton 802.2, Replace blank tables 802 2 (1-4) with the completed tables provtded on the followmg four pages. Delete tables 802 2 (5-37) TABLE 802 2(1) BUILLOINO ENVELOPE REQUIREMENTS WINDOW AND GLAZED DOOR .aAREA 10 PERCENT OR LESS OF ABOV£E GRADE WALL AREA ELEMENT CONDITION/VALUE (Zonees 5B~6B) Skylights (U-factor) 1 Sl~b or below ~lrade wall (R value)~) R 0 Windows and glass doors SHGC U factor PF < 0 25 Any Any O 25 <_ PF < 0 50 Any Any PF · 0 50 Any Any Roof assemblies (R value) Insulation between Continnuous insulation framlns All-wood Joist/truss R 19 R-16 Metal joist/truss R 25 R-17 Concrete slab or deck NA R 16 Metal purlin with thermal block R 25 R-17 Metal purlin without thermal block X R 17 FJQors over outdoor a r or insulation between Continnuous insulation unconditioned space (R-value) framln~ Ail-wood joist/truss R-I 1 R 6 Metal Joist/truss R-11 R 6 Concrete slab or deck NA R 6 Above-grade walls (R-value) No frarnln9 Metal framing Wood framln~l Framed c~r~l-value cavity NA R 11 R-11 value continuous NA R-O R 0 U, _> 8 in ~ with nte,~ral msutahon ~ R value cavity NA R 0 R 0 R-value continuous R 0 R 0 R-0 Other masonry walls R value cavity NA R 0 R 0 R-value continuous R 0 R 0 R-0 Page 39 TABLE 802 2(2) BUILDING ENVELOPE REQUIREMENTS WINOOW AND GLAZED DOOR AREA OVER t0 PERCENT BUT NOT GREATER THAN 25 PERCENT OF ABOVE GRADE WALL AREA ELEMENT CONDITION/VALUE Skylights (U factor) Slab o'r below-grade wall (R vatua) R-O Wlndc~wa and glass doors SHGC U factor PF < 0 25 0 6 Any 0 25.< PF < 050 07 Any PF > 0 50 Any Any Roof assemblies (R-value) Insulation between Continuous insulation framing All wood jolsUtmse R 25 R-19 Metal joist/truss R 25 R-20 Concrete slab or deck NA R 19 Metal purlin with thermal block R-30 R 20 Metal purhn without thermal block X R-20 Floor~ over outdoor air or Insulation between Continuous insulation unconditioned space (R value) framing All wood joist/truss R 11 R-6 Metal joist/truss R 11 R 6 Con~3reta slab or deck NA R-6 Above-grade wails {R-value) No framing Metal framing Wood framing Framed R value cavity NA R 11 R 11 R value conhnuous NA R 0 R~O CMU? 8 in ~ w~th integral Insulat~on R-value cawty NA R 11 R 11 R va!ua continuous R 5 R 0 R 0 Other,masonry walls R va)ua cavity NA R 11 R 11 R value continuous R-5 R 0 R-0 Page 40 TABLE 802 2(3) BUILDING ENVELOPE REQUIREMENTS WINDOW AND GLAZED DOOR AREA OVER 25 PERCENT BUT NOT GRREATER THAN 40 PERCENT OF ABOVE GRADE WALL AREA ELEMENT CONDITION/VALUUE Skylights (U factor) 1 Slab or below grade wall (R value) R 0 Windows and glass doors SHGC U factor PF<025 04 07 025<PF<050 05 07 PF>050 06 07 Roof assembllee {R-value) Insulation between Contmnuous insulation framing All-wood jo~st/truss R 25 R 19 Metal joist/truss R 25 R 20 Concrete slab or deck NA R 19 Metal purhn with thermal block R 30 R 20 Metal purhn without thermal block X R 20 Floors over outdoor air or Insulation between Continnuous Insulat~on unconditioned space (R value} framing All,wood lolst/truss R 11 R 6 Metal joist/truss R 11 R 6 Concrete slab or deck NA R 6 Above-grade walls (R-value) No framing Metal framing Wood framing Framed R yalue cavity NA R 11 R 11 R value continuous NA R 0 R 0 CMtJ~ ,,>,, 8 in ~ w~th integral Insulation R value cavity NA R-11 R-I 1 R value continuous R 5 R 0 R 0 Other masonry walls R value cavity NA R 11 R 11 R-value continuous R 5 R 0 R 0 Page 41 TABLE 802 2(4) BUlL DING ENVELOPE REQUIREMENTS WINDOW AND GLAZED DOOR A~REA OVER 40 PERCENT BUT NOT GRtEATER THAN 50 PERCENT OF ABOVE GRADE WALL AREA ELEMENT CONDITION/VALUlE Skyl ~hta (U factor) 1 Slab er balow~rade wall (R value)l R O Win( owe and glass doors SHGC U factor PF<02$ 04 07 025_< PF < 0 50 05 07 PF>050 06 07 Roo~assembllas (R value) Insulation between Contimuous ~nsulatlon framing All wood joist/truss R 25 R-19 Metal joist/truss R-25 R 20 Concrete slab or deck NA R 19 Metal purlin w~th thermal block R 30 R 20 Metal purlin without thermal block R 38 R 20 Floors over outdoor air or Insulatlon between Contimuous Insulabon unconditioned space (R value) framing All wood joist/truss R 11 R-6 Metal joist/truss R 11 R 6 Concrete slab or deck NA R 6 Aboye grade wails (R value) No framing Metal framing Wood framing Frarqed R-v91ue cavity NA R-13 R 11 R value continuous NA R 3 R 0 CMtj, _> 8 in with Inte,~ral insulation R-value cav ty NA~ NA R 11 R 11 R ~a ue continuous R 5 R 0 R 0 Other masonry walls R value cavity NA R 11 R 11 R value continuous R 5 R 0 R-0 (18) Sqctton 805.2 1 Intertor Lighting Controls; add a thtrd sentence to read. Large ispaees shall have a separate swtteh or control for each 2500 square feet of floor area (19) Chapter 9; Replace referenced standard as follows ASHRAE/IES -- 93 Energy Code for Commerctal and Htgh-l~tse Restdenttal Buddings - Based on ASHRAE/IES 90 1-1989 - w~th Rews~ons thru October 7, 1997 ~ncludmg Errata and Addendum 90 lc-1993 ASHRAE/IES -- 99 Energy Efficient Destgn of New Bmldmgs Except Low-Past Res~denttal Bmldmg -- 1999 Edttton SECTION 2. That ff any prowston of thts ordinance or the apphcat~on thereof' to any person or ctrcumstances ts held mvahd, such mvahd~ty shall not affect other provtstons or appheattons, and to thts end the prov~stons of thts ordinance are severable SECTION 3. That all provtstons of the ordinances of the Ctty of Denton tn conflict with the provtstons of thts ordinance are hereby repealed, and all other provtstons of the orchnanees of the C~ty of Denton, not m confltct w~th the provtstons of thts orchnance, shall rem~un tn full force and effect Page 42 SECTION 4. That any person wolat~ng any provis~on of this ordinance shall, upon conviction, be fined a sum not to exceed two thousand dollars ($2000 00) Each day that a provmon of th~s Ordinance ~s wolated shall constitute a separate and &stmct offense SECTION 5 That this or&nance shall become effective fourteen (14) days from the date of its passage, and the C~ty Secretary ~s hereby &rected to cause the caption of this ordinance to be pubhshed twice m the Denton Record Chromcle, the officml newspaper of the C~ty of Denton, Texas, within ten (10) days of the date of~ts passage PASSED AND APPROVED th~s the ~7~ day of )k~~ ,2001 Euhne Brock, Mayor ATTEST JENNIFER WALTERS, CITY SECRETARY APPROVED AS TO LEGAL FORM HERBERT L PROUTY, CITY ATTORNEY S \Our Documents\Ordinances\01\2000 Building I CODES doc Page 43